6 Installation, FT model
6.1 FT model installation locations
FT model sensor installation to vertical and horizontal pipelines is illustrated in the fol-
lowing picture. The sensor should always be installed as close to dilution water injec-
tion as possible to ensure minimum control delay. The process pressure should be al-
ways > 1.5 bar.
Recommended installation sites are numbered in order of preference, the best one
first:
Figure 5: Installation locations FT model.
1.
Directly after a pump.
2.
On a vertical pipeline.
3.
On a horizontal pipe after a vertical pipe section.
4.
On a horizontal pipe after a bend.
5.
On a vertical pipe after a horizontal pipe section.
Installation, FT model | 14 (93)
K17122 V1.1 EN - 1 - 06/2020