background image

12

CLEANING THE HEAT RECOVERY CELL

Check that the heat recovery cell is clean roughly once a year, 

or whenever the filters are being replaced. Clean by washing 

as required.
To check and clean the heat recovery cell:

1.  Disconnect the ventilation unit from the mains electricity 

supply.

2.  Open the door of the Vallox ventilation unit by undoing the 

finger screws.

3.  Lift the door off. 

CAUTION

The door is heavy.

4.  Remove the supply air filter (A).

5.  Turn the upper support of the HR cell (B) to the upper 

position (anti-clockwise).

6.  Remove the extract air filter (C).

7.  Lift and pull the HR cell (D) out of the unit.

8.  If the cell is dirty, clean it by immersing it in warm water, to 

which a small amount of a mild detergent has been added.

9.  Rinse the cell clean with a water spray. Do not use a high-

pressure cleaner.

10.  When all the water has drained from between the layers, 

reassemble the ventilation unit as follows:

11.  Ensure that the lower support (E) is in place against the 

knobs at the bottom of the unit.

12.  Lift the HR cell in place.

13.  Turn the upper support against the cell. Ensure that the 

upper support is properly nestled against the cell (remains 

upright). 

14.  Install the extract air filter (C) and the supply air filters (A) in 

place.

15.  Close the door. Ensure that the safety switch catch of the 

door is touching the safety switch.

16.  Plug the ventilation unit back into the mains. 

 

The heat recovery cell has now been checked and 

cleaned.

MAINTENANCE

IMPORTANT

Handle the cell 

carefully! For example, 

do not lift the cell by the 

layers. The cell layers 

are very thin and easily 

damaged.

CONDENSING WATER

In the heating season, the extract air humidity condenses to 

water. In new buildings, the volume of condensing water can be 

high. Condensed water must be able to freely leave the unit. 

At some time before the heating season begins (e.g. during 

autumn maintenance), check that the siphon or the condensing 

water outlet in the bottom pool are not clogged. To check this, 

pour some water into the pool. Clean as required.

NOTE

Some condensing water 

may have accumulated 

in the bottom pool 

of the unit; this is 

normal and requires no 

corrective action. 

WARNING

Water must at all times 

be kept out of the 

electrical system.

 

D

C

B

A

E

Summary of Contents for 99 MV

Page 1: ...Manual Model Vallox 99 MV Type 3755 Document D10813 Valid from 01 01 2022 Updated 19 06 2023 Ventilation unit MANUAL...

Page 2: ...he Vallox Silent Klick siphon 9 Space required by the alternative Vallox Silent Klick siphon installation method elbow 9 Measuring and adjusting the air flows of the ventilation unit 9 Dimensions and...

Page 3: ...ctrical installations and connections must be carried out only by an electrician and in compliance with local regulations WARRANTY The guarantee and liability exclude damage resulting from Inappropria...

Page 4: ...sult in death or serious injury if not avoided IMPORTANT Indicates a hazard that can result in damage to property or loss of data if not avoided CAUTION Indicates a hazard that can result in minor or...

Page 5: ...ed automatically by using the optional carbon dioxide humidity or VOC air quality sensor When these are used ventilation remains optimal even when the dwelling is unoccupied Each user can use the week...

Page 6: ...supply air fan 8 R model in the figure MAIN PARTS Additional heating resistor 9 Safety switch 10 Internal carbon dioxide and humidity sensor 11 Ceiling bushing for electric wires 12 Control panel 13 C...

Page 7: ...The top edge of the white covering strip of the ceiling mounting plate can be installed against the ceiling Alternatively a concealed mounting method can be used in which case the ceiling can be 30 m...

Page 8: ...x can be accessed The distance between the service door and the ceiling mounting plate must be around 500 mm Alternatively the cables can be fed to the rear wall between the ceiling mounting plate and...

Page 9: ...ing tubes These can be inserted in the ducts to allow for easier ventilation adjustment NOTE The Vallox Silent Klick siphon package is delivered with the unit Installation instructions for the siphon...

Page 10: ...re mirrored 8 Post heating resistor in front of the supply air fan 9 Additional heating resistor 10 Safety switch 11 Internal humidity and carbon dioxide sensor 12 Ceiling bushing for electric wires D...

Page 11: ...oncentration It is recommended that the filters be replaced every spring and autumn or at the very least once a year To replace the filters 1 Disconnect the ventilation unit from the mains electricity...

Page 12: ...e HR cell in place 13 Turn the upper support against the cell Ensure that the upper support is properly nestled against the cell remains upright 14 Install the extract air filter C and the supply air...

Page 13: ...r feedthrough K L through the intermediate floor and to the bottom part of the unit 7 Remove the plastic screws used to fasten the fans I 2 per fan Remove the wing screws J 2 pcs of the post heating r...

Page 14: ...7 31 33 36 38 38 4000 19 26 35 41 45 50 52 54 56 57 17 17 17 18 20 23 26 28 30 31 8000 21 21 23 28 33 39 43 46 48 49 21 21 21 21 21 21 22 22 23 24 LW dB LWA dB A 63 64 67 70 73 80 77 82 80 81 53 53 59...

Page 15: ...r connector D I1 Digital input 1 D I2 Digital input 2 11V1 11 1 V operating voltage AN I Analog input 0 10VDC RM I 24V relay input RM O 24V relay output T Supply air fan P Extract air fan M Damper mot...

Page 16: ...NTC 4K7 Digital input 1 8 different functions Digital input 2 8 different functions Ethernet connection on top of the unit RJ45 female 0 3W 1 2W 1 W 1 W MyVallox VOC sensor 2W MB_A External Modbus A s...

Page 17: ...rd MLV control External temperature sensor NTC 4K7 MB_A External Modbus A signal MB_B External Modbus B signal 24V 24V voltage DC GND Digital and analog ground potential RS_A Local hardware Modbus A s...

Page 18: ...ature setting In winter the duct radiator will turn on when the outdoor temperature falls below the winter setting Manual In summer the duct radiator will turn on when the outdoor temperature rises ab...

Page 19: ...alve Not included in the delivery The valve that is chosen must be compatible with the heat collection circuit fluid for example Danfoss 032U161431 K Condensing water tube Not included in the delivery...

Page 20: ...ly 4115315 22 Connection box 3526700 5 Coarse and fine filter for supply air 4114075 14 Additional heating resistor 4115412 23 MyVallox Control panel MyVallox Touch panel 949033 949090 6 Damper motor...

Page 21: ...CONFORMITY CERTIFICATES...

Page 22: ...22...

Page 23: ...23 Vallox Oy All rights reserved...

Page 24: ...D10813 19 06 2023FIN 19 06 2023ENG PDF www vallox com Vallox Oy Myllykyl ntie 9 11 32200 LOIMAA FINLAND...

Reviews: