background image

8

TIP

 

You can detach the 

unit from the ceiling 

mounting plate by 

pulling the spring-

loaded moulding to the 

direction shown by the 

arrow (more detailed 

information provided 

with the ceiling 

mounting plate).

INS
TALLA
TION

a

b

1

B

2

4

5

3

B

F

A

A

Installing the ventilation unit to the ceiling 

mounting plate

1.  Install the ceiling mounting plate with M8 thread bars so that it 

is horizontally level.

NOTE 

The end of the thread bars must be 5 mm or less below the 

fastening nut. Do not fasten the ceiling mounting plate too 

tight to the ceiling. Ensure that the sliding bars move and 

restore to their original position by pulling from the operating 

levers (A). The top edge of the white covering strip of the 

ceiling mounting plate can be installed against the ceiling. 

Alternatively, a concealed mounting method can be used, in 

which case the ceiling can be 20 mm below the top of the 

white covering strip.

2.  096 - Install the insulation washers into the outlet collars of the 

ventilation unit. 

110 - Ensure that the insulation washers are in place in the 

outlet collars below the ceiling mounting plate.

3.  Remove the door before installing the ventilation unit to the 

ceiling mounting plate.

4.  Lift the ventilation unit close to the ceiling mounting plate and 

feed the cables and the connection box through the hole in the 

ceiling mounting plate on top of the ceiling. 

NOTE

Remember to make a service door in the ceiling so that 

the cables and the connection box can be accessed. The 

distance between the service door and the ceiling mounting 

plate must be around 500 mm.

Alternatively, the cables can be fed between the ceiling 

mounting plate and the ventilation unit to the rear wall. When 

the ventilation unit is lifted against the ceiling mounting plate, 

the unit locks in place. Where needed, guide the mounting 

hooks on the ceiling mounting plate (B) to the grooves on the 

side panels of the ventilation unit. There are operating levers 

(A) on the front bottom corners of the ceiling mounting plate. 

When the levers have been restored to the same level with the 

white covering strip of the ceiling mounting plate, the unit has 

been locked in place.

5.  Where required, the unit can be detached from the ceiling 

mounting plate. Remove the door of the unit. Lift the unit 

slightly upwards and pull simultaneously from both operating 

levers (A) of the ceiling mounting plate to detach the unit from 

the ceiling mounting plate.

Attic floor penetration plate

The attic floor penetration plate (F) is optional. When an attic floor 

penetration plate is used, the tightness of the vapour barrier has to 

be ensured.

The minimum distance of the attic floor penetration plate from 

the rear wall is 5mm. The minimum distance of the attic floor 

penetration plate from the side walls is 15mm.

Summary of Contents for 096 MV

Page 1: ...Manual Model Vallox 096 MV Vallox 110 MV Vallox 145 MV Type A3722 A3702 A3712 Document D5326 Valid from 17 03 2020 Updated 05 02 2020 Ventilation units MANUAL...

Page 2: ...iphon 10 Space required by the alternative Vallox Silent Klick siphon installation method elbow 10 Vallox 096 MV Vallox 110 MV and Vallox 145 MV 10 Dimensions and duct outlets 11 Vallox 096 MV 11 Vall...

Page 3: ...odifications or changes made to the software INTENDED USE All Vallox ventilation units have been designed to provide appropriate and continuous ventilation so as to present no threat to health and to...

Page 4: ...ways be installed on the floor by using a floor rack NOTE The standard equipment and available accessories vary from country to country DANGER Indicates a hazard that will result in death or serious i...

Page 5: ...lling ventilation remotely also using e g a smartphone or tablet Also the unit software is updated automatically through the cloud service To connect to the cloud service the ventilation unit must be...

Page 6: ...behind the extract air duct 8 R model in the figure MAIN PARTS Vallox 096 MV Vallox 110 MV and Vallox 145 MV Safety switch 9 Internal humidity sensor 10 Internal carbon dioxide sensor 10 Control pane...

Page 7: ...the outdoor air and exhaust air duct against condensation also between the unit and the ceiling mounting plate Mounting the ceiling mounting plate 1 Fasten the thread bars on the rafter frames or oth...

Page 8: ...ection box through the hole in the ceiling mounting plate on top of the ceiling NOTE Remember to make a service door in the ceiling so that the cables and the connection box can be accessed The distan...

Page 9: ...unit on top of the base so that the bars of the base fit in the holes at the bottom of the unit Mount the ventilation unit on the wall with a mounting plate as shown in the adjacent figure Make sure t...

Page 10: ...is used the ring seal and the locking part must be moved to the pipe connection part that is mounted on the wall INSTALLATION Dimensioning figure and space required for installation of the Vallox Sil...

Page 11: ...cell 5 Bypass damper of the HR R model in the figure In the L model the parts are mirrored cell 6 Coarse filter for supply air 7 Coarse filter for extract air 8 Post heating resistor behind the extra...

Page 12: ...ract air 8 Post heating resistor behind the extract air duct 9 Safety switch 10 Additional heating resistor behind the extract air duct Dimensions and duct outlets Dimensions Duct outlets R model Inne...

Page 13: ...o the unit L model Inner diameter of the female collar 200mm 1 Exhaust air flowing outdoors from the unit 2 Outdoor air to the unit 3 Supply air from the unit to the apartment 4 Extract air from the a...

Page 14: ...tration It is recommended that the filters be replaced every spring and autumn or at the very least once a year To replace the filters 1 Disconnect the ventilation unit from the mains electricity supp...

Page 15: ...ergent has been added 8 Rinse the cell clean with a water spray Do not use a high pressure cleaner 9 When all the water has drained from between the layers reassemble the ventilation unit in the rever...

Page 16: ...ee chapters Replacing the filters and Cleaning the heat recovery cell 5 Pull out the temperature sensor figure 1 located at the top of the extract air duct G Remove the stopper screw I at the bottom o...

Page 17: ...gure 9 c Pry the plastic lock to the right of the fan with a screwdriver for example figure 10 d The fan falls downwards e Pull the fan out of the unit figure 11 f Disconnect the fan wire quick connec...

Page 18: ...5 Open the four screws figure 1 on the extract air fan cover and remove the cover figure 2 The fan can now be cleaned in place 6 To remove the fan for cleaning a Push the fan gently upward figure 3 b...

Page 19: ...ate climate A A Operating efficiencies Annual efficiency Supply air efficiency Specific Fan Power SFP 75 A 85 7 1 0 kW 38 dm3 s B Dimensions w x h x d 600 x 545 x 428 mm Weight 53 kg Sound power level...

Page 20: ...in a temperate climate A A Operating efficiencies Annual efficiency Supply air efficiency Specific Fan Power SFP 75 A 85 7 0 9 kW 38 dm3 s A Dimensions w x h x d 638 x 678 x 472 mm Weight 64 kg Sound...

Page 21: ...SO Coarse 75 Specific energy consumption SEC in a cold climate in a temperate climate A A Operating efficiencies Annual efficiency Supply air efficiency Specific Fan Power SFP 75 A 85 1 0 9 kW 75 dm3...

Page 22: ..._B Local hardware Modbus B signal NTC External temperature sensor connector D I1 Digital input 1 D I2 Digital input 2 11V1 11 1 V operating voltage AN I Analog input 0 10VDC RM I 24V relay input RM O...

Page 23: ...r fan tacho WT 5 GND GN 6 Supply air fan PWM YE C 1 Extract air 2 Outdoor air 3 Supply air 4 Exhaust air 5 Supply air from the HR cell D LAN MB_A External Modbus A signal MB_B External Modbus B signal...

Page 24: ...ut EXTERNAL ELECTRICAL CONNECTION 3x1 5S 2x2x0 5 0 5 2x0 5 2x0 5 7028350 2014 08 29 JS 2x2x0 5 0 5 2x0 5 2x2x0 5 0 5 2x2x0 5 0 5 2x2x0 5 0 5 2x0 5 2x0 5 CAT Analog input two different functions Potent...

Page 25: ...r NTC 4K7 MB_A External Modbus A signal MB_B External Modbus B signal 24V 24V voltage DC GND Digital and analog ground potential RS_A Local hardware Modbus A signal RS_B Local hardware Modbus B signal...

Page 26: ...the supply air temperature will be maintained at the level specified in the temperature setting In winter the duct radiator will turn on when the outdoor temperature falls below the winter setting Ma...

Page 27: ...ve Not included in the delivery The valve that is chosen must be compatible with the heat collection circuit fluid for example ELV05006 Stig Wahlstr m K Condensing water tube Not included in the deliv...

Page 28: ...22 NTC sensor kit 3480500 5 Coarse filter for supply air 978044 13 Extract air outlet 985026 23 Glass tube fuse 63mA slow 5x20mm 952490 6 Fine filter for supply air 978220 14 Internal humidity and ca...

Page 29: ...filter for supply air 978157 15 Internal humidity and carbon dioxide sensor 4107982 24 NTC sensor kit 3457900 7 Lower support for HR cell 3450100 16 Motherboard 949032 1 25 Glass tube fuse 63mA slow...

Page 30: ...24 NTC sensor kit 3482300 7 Lower support for HR cell 3469000 16 Motherboard 949032 1 25 Glass tube fuse 63mA slow 5x20mm 952490 8 HR cell 933270 17 Safety switch 948377 26 MyVallox Control panel 949...

Page 31: ...CONFORMITY CERTIFICATES...

Page 32: ...D5326 04 02 2020FIN 05 02 2020ENG PDF www vallox com Vallox Oy Myllykyl ntie 9 11 32200 LOIMAA FINLAND Customer service 358 10 7732 200 Aftersales 358 10 7732 270...

Reviews: