Section 3—General Wiring Guidelines
Routing Low-Voltage Leads
When routing low-voltage leads, follow these guidelines:
•
Do not route low-voltage leads in the same conduit as wires carrying a high-current load.
•
Do not route low-voltage leads adjacent to, or across wires carrying a high-current load. If low-voltage
leads must cross or run parallel to wires carrying high current, keep the leads at least 6" (152 mm) from
high-current wires.
•
Do not splice or solder leads.
•
Trim leads to the required length. Leads should be only as long as necessary for installation.
•
All wiring should be in conduits or wireways.
Connecting the Supply of Electrical Power
WARNING! Electrical connections should be made only by experienced
service personnel! OTHERWISE, DEATH, PERSONAL INJURY, OR EQUIP-
MENT DAMAGE COULD OCCUR.
When connecting the supply of electrical power, follow these guidelines:
•
Connect the control to a “clean” supply of electrical power. Use a dedicated circuit if possible.
Note!
If a dedicated circuit is not available, do not connect the control to a circuit that supplies high-
amperage equipment—use another circuit such as a lighting circuit. Otherwise, equipment may not
function properly.
WARNING! Electrical installation should be accomplished only by experi-
enced service personnel! OTHERWISE, DEATH, PERSONAL INJURY, OR
EQUIPMENT DAMAGE COULD OCCUR.
Summary of Contents for VC350A
Page 1: ...VC350A Flexoseal System Manual Number MC037 Release Date May 2001 ...
Page 8: ...Section 1 Introduction VC350A Flexoseal System Valco Cincinnati 1 2 Figure 1 1 VC350A Control ...
Page 68: ...Section 9 Maintenance VC350A Flexoseal System Valco Cincinnati 9 9 Figure 9 4 Fluid Regulator ...
Page 133: ...Section 12 Part Number List VC350A Flexoseal System Valco Cincinnati 12 44 400EZ Glue Valve ...
Page 163: ...Section 12 Part Number List VC350A Flexoseal System Valco Cincinnati 12 74 Fittings ...