Property
Description
Storage temperature range
-40 ... +60 °C (-40 ... +140 °F)
1)
The fire point [of transformer oil] is normally approximately 10 °C [18 °F] higher than the
closed flash point. See, for example, Heathcote, Martin J. The J & P Transformer Book. 13th
ed. Elsevier, 2007.
Table 15 Power Supply
Property
Description
Operating voltage
100 ... 240 VAC, 50 ... 60 Hz, ±10 %
Overvoltage category
III
Maximum current consumption
10 A
Maximum power consumption
500 W
Typical power consumption at +25 °C
(+77 °F)
100 W
Connector
Screw terminals (inside power supply unit)
Wire size 2.5 ... 4 mm
2
(14 ... 12 AWG)
Table 16 Outputs
Property
Description
RS-485 Interface
Connector
Screw terminals (inside OPT100 housing)
Wire size 0.5 ... 4 mm
2
(20 ... 12 AWG)
Supported protocols
Modbus RTU
Galvanic isolation
2 kV RMS, 1 min
Ethernet Interface
Connector
Industrial RJ45 connector with protective plug (outside
OPT100 housing)
Supported protocols
DNP3 (Distributed Network Protocol), Modbus TCP, HTTP,
IEC 61850 (optional feature)
Standard
IEEE 802.3
Physical layer
Base-T
Data rate
10/100 Mbps
Galvanic isolation
4 kV AC (50 Hz, 1 min)
Insulation voltage
250 V
rms
Chapter 6 – Technical Data
55
Summary of Contents for Optimus OPT100
Page 1: ...M211858EN E User Guide Vaisala Optimus DGA Monitor for Transformers OPT100...
Page 24: ...Figure 11 Measurement Graph for 1 Day Rate of Change Values OPT100 User Guide M211858EN E 22...
Page 72: ...OPT100 User Guide M211858EN E 70...
Page 76: ...OPT100 User Guide M211858EN E 74...
Page 77: ......
Page 78: ...www vaisala com...