6.7 Analog Output
Table 26 Aerr Command
Syntax
Description
aerr ?
<cr>
Show currently set analog output error level for
both channels.
aerr
<cr>
Show currently set analog output error levels,
prompt to enter new values.
aerr [ch1] [ch2]
<cr>
Set error level for both channels without
prompting.
ch1 = error level for analog output channel 1 in
mA.
ch2 = error level for analog output channel 2 in
mA.
Example (set error level for both analog output channels to 21 mA):
aerr
Ch1 error out : 3.600 I ?
21
Ch2 error out : 3.600 I ?
21
Table 27 Amode Command
Syntax
Description
amode
<cr>
Show currently set analog output mode.
Example:
amode
Ch1 output : 4 ... 20 mA
Ch2 output : 4 ... 20 mA
Table 28 Aover Command
Syntax
Description
aover
<cr>
Show current aover status.
aover [on|off]
<cr>
Set analog output overrange to:
on = Allow output to exceed the scaled range
by 10 %.
off = Keep the analog output always in the
scaled range. Note that error state behavior
overrides this setting.
HMDW110 User Guide
M211726EN-D
46