In weather stations with stainless steel flanges, check that the sensor cable shields have been
grounded to the cable glands.
•
In cable glands with EMC springs, the cable shield must be firmly connected to the EMC
spring.
1
2
1
Cable gland
2
EMC spring
•
In cable glands without EMC springs, the cable shield must be grounded to the cable gland
using a sealing insert.