background image

4

Operating instructions 0020262548_01

2

Notes on the documentation

2.1

Observing other applicable documents

Always observe all operating instructions enclosed with
the installation components.

2.2

Storing documents

Store these instructions and all other applicable docu-
ments for further use.

2.3

Validity of the instructions

These instructions apply only to:

VRC 700/6

article number

Great Britain

0020184838

2.4

Nomenclature

The following terms are used for simplification:

System control: This refers to the

VRC 700

system con-

trol.

Remote control: If this refers to the

VR 91

remote control.

2.5

Function availability

The functions described in these operating instructions are
not available for all system configurations.

The system control only shows the functions that are avail-
able in the system configuration you have installed.

3

Product description

3.1

Product design

1

2

3

4

5

6

5

1

Display

2

Wall base

3

Diagnostics socket

4

Wall base cover

5

Selection button

6

Rotary knob

3.2

Main function

The system control is a weather-compensated system con-
trol with an outdoor temperature sensor installed in the open
air.

The system control is connected to the outdoor temperat-
ure sensor and the heat generator. The system control con-
trols the heating installation and other connected compon-
ents, e.g. the domestic hot water generation for a connected
domestic hot water cylinder or the ventilation of a connected
ventilation unit.

3.2.1

Heating

The outdoor temperature sensor measures the outdoor
temperature and forwards the values to the system control.
When the outdoor temperature is low, the system control in-
creases the flow temperature of the heating installation. If the
outdoor temperature increases, the system control reduces
the flow temperature. The system control responds to the
fluctuations in the outdoor temperature and uses the flow
temperature to ensure that the room temperature remains at
the desired temperature.

3.2.2

Cooling

The room temperature sensor measures the room temper-
ature and sends the data to the system control. If the room
temperature is higher than the desired temperature that is
set, the system control switches cooling on.

3.2.3

Ventilation

Using a controlled exchange of air, the ventilation unit en-
sures that the living rooms are ventilated and aerated. The
system control controls the air volume flow via the ventilation
levels that are set.

3.2.4

Domestic hot water generation

A temperature sensor measures the temperature of the wa-
ter in the domestic hot water cylinder and forwards the val-
ues to the system control. If the temperature lies below the
set value, the system control increases the temperature in
the domestic hot water circuit and therefore heats up the wa-
ter to the set domestic hot water temperature.

3.2.5

Circulation

The secondary return pipe is connected to the domestic hot
water pipe and forms a circuit with the domestic hot water
cylinder. The circulation pump pumps the domestic hot water
through the domestic hot water pipe, either continuously or
on a time-controlled basis. This means that domestic hot
water is available at the draw-off points.

3.3

Zones

A building is divided into several zones if the heat demand
differs between different sections of the building.

If underfloor heating and radiator heating are installed in
a house.

If a house contains more than one independent residen-
tial unit.

If more than one zone is available, the system control con-
trols the available zones.

Summary of Contents for VRC 700/6

Page 1: ...en Operating instructions Weather compensated system control VRC 700 6 0020262548_01 28 11 2022...

Page 2: ...4 Operation 5 4 1 Operating structure 5 4 2 Basic display 6 4 3 Operating concept 6 5 Operating and display functions 8 5 1 Information 8 5 2 Settings 10 5 3 Operating modes 14 5 4 Advanced functions...

Page 3: ...physical sensory or mental capabil ities or lack of experience and knowledge if they have been given supervision or instruc tion concerning use of the product in a safe way and understand the hazards...

Page 4: ...flow temperature of the heating installation If the outdoor temperature increases the system control reduces the flow temperature The system control responds to the fluctuations in the outdoor temper...

Page 5: ...ine 3 9 CE marking The CE marking shows that the products comply with the basic requirements of the applicable directives as stated on the declaration of conformity The declaration of conformity can b...

Page 6: ...energy Off Day Set back off Empty line 4 2 3 2 Basic display for the Cooling operating mode Mode Time periods Symbol Information field Auto On Desired cooling temp Off Empty line Day Desired cooling...

Page 7: ...nge to the Max vent stage Day Set back Direct permanent change to the Max vent stge Night 4 3 1 4 Desired temperature in the Manual cooling advanced function Mode Time periods Effect Activated On Dire...

Page 8: ...inform ation that provides an overview of the current system status and current settings that you can change there 5 1 1 1 System Menu Information System status Fault status If no maintenance is requ...

Page 9: ...set the desired set back temperature for the zone Set back temp heat is the temperature that you want to have in the rooms during the night or when you are away from home night mode Menu Information S...

Page 10: ...e total yield is displayed on the bottom right The highest value achieved in one month for the last two years is dis played in the top right 5 1 2 4 Diagram Reading the electrical consumption Menu Inf...

Page 11: ...ge 12 You can create up to three time periods for each individual day and for predefined blocks Monday Friday Saturday Sunday Monday Sunday When entering time periods for individual days or blocks the...

Page 12: ...n Within the time period the circulation is switched on Outside the time period the circulation is switched off 5 2 3 8 Setting the Ventilation time programme Menu Time programmes Ventilation The time...

Page 13: ...g Button lock Menu Basic settings Display Button lock You can use this function to activate the button lock After one minute of not pressing any button or operating the rotary knob the button lock is...

Page 14: ...ogrammes or for Everything to the default setting Menu Basic settings Default setting Time pro grammes With Time programmes you reset all the settings you have made in the Time programmes function to...

Page 15: ...of air using the value that you set in the Max vent stage Day ventilation level Set back The operating mode constantly controls the ex change of air using the value that you set in the Max vent stge N...

Page 16: ...st The Cylinder boost advanced function heats the water in the domestic hot water cylinder until it reaches the set desired temperature Domestic hot water The advanced function is active for one hour...

Page 17: ...ears again in the display 7 Care 7 1 Caring for the product Clean the casing with a damp cloth and a little solvent free soap Do not use sprays scouring agents detergents solvents or cleaning agents t...

Page 18: ...ription of the functions for ZONE1 also applies for all available zones Setting level Values Unit Increment select Default setting Min Max Information System status System Fault status Current value N...

Page 19: ...ast month kWh Hot water Electricity Total value since start up kWh Fuel Total value since start up kWh Information Consumption History Heating Electricity Total value since start up kWh Fuel Total val...

Page 20: ...NE1 Cooling Time programmes Circulation Time programmes Ventilation Individual days and blocks Monday Tuesday Wednes day Thursday Friday Sat urday Sunday and Monday Friday Saturday Sunday Monday Sunda...

Page 21: ...Button lock off On off Preferred display Heating Cooling Vent Heating Basic settings Costs Tariff for aux heater 1 999 1 12 Low tariff elec rate 1 999 1 16 High tariff elec rate 1 999 1 20 Basic setti...

Page 22: ...Fault Heat generator 1 the specific fault code e g F 33 and the specific heat generator appear behind F in the display Heat generator faults 1 Carry out a Reset fault message Page 16 2 If the fault p...

Page 23: ...basic display 6 Outdoor temperature setting the offset 14 P Party 16 Preventing a malfunction 5 R Reading the article number 5 10 Reading the electrical consumption 10 Reading the environment yield 1...

Page 24: ...24 Operating instructions 0020262548_01 Time programme 11 quick setting 11 Setting 11 V Ventilation 4 Ventilation boost 16 Ventilation level 11 Z Zone 4 10 Zone in the basic display 6...

Page 25: ......

Page 26: ......

Page 27: ......

Page 28: ...isher manufacturer Vaillant GmbH Berghauser Str 40 D 42859 Remscheid Tel 49 2191 18 0 Fax 49 2191 18 2810 info vaillant de www vaillant de These instructions or parts thereof are protected by copyrigh...

Reviews: