ecoTEC exclusive installation and maintenance instructions / 0020017768_02

10

4.3 Installation 

site

The site of erection of the boiler should allow proper 
connection of the air/exhaust ducting. In addition, there 
should be adequate room for maintenance work and air 
circulation around the boiler. The boiler can be installed 
in any room, however, in rooms with a bath or a shower, 
the special requirements of BS 7671 (IEE Regulations), 
the electro-technical stipulations of the Building Stand-
ards (Scotland) Regulations and, in IE, the current issue 
of IS 813 and the current ETCI Stipulations must espe-
cially be observed.

h

 Danger!

Danger of death by electric shock! If a room 
sealed boiler is installed in a room with a bath 
or a shower, the electrical switches and the 
boiler controller, which operate at mains volt-
age must be mounted in locations where any 
person in the bath or in the shower cannot 
reach them

In the event of installation in unusual locations, special 
provisions may have to be made. Detailed instructions 
for this can be found in BS 5546 and in BS 6798. The 
boiler must be installed on a flat vertical wall which is 
adequately robust to carry the weight of the boiler. 
It is possible to mount onto a wall made of flammable 
material if the regulations of the Local Authority and 
the legal building stipulations are fulfilled.
In this case however, the unit would have to be mounted 
in a specially made enclosure. (You can also use an 
existing cabinet or existing enclosure as long as it can 
be modified accordingly to suit the new application.) 
Further details concerning the fundamental characteristics 
when modifying existing cabinets or enclosures, including 
the requirements for ventilation, are described in BS 6798. 
If the boiler is to be installed in a half-timbered house, 
the installation must be undertaken in accordance with 
the Institute of Gas Engineers Publication "IGE/UP/7 
Edition 2 Gas installation in timber framed and light steel 
framed buildings". Please note the following instructions 
before choosing where to 
install the heater:

a

  Caution!

Do not install the appliance in rooms prone to 
frost. In rooms with aggressive steam or dust, 
the appliance must be operated independently 
of the ventilation!

When choosing the place of installation and while oper-
ating the appliance, make sure that the combustion air 
is free from chemical substances such as e.g. fluorine, 
chlorine, sulphur, ammonia etc. Sprays, solvents and 
cleaning agents, paints, adhesives etc. contain these 
kinds of substances, which - in the worst case scenario - 
can lead to corrosion, even in the exhaust system, dur-
ing ambient air dependent operating of the appliance.

Particularly in hairdessing salons, lacquering and finish-
ing workshops, cleaning facilities, etc., the appliance 
must be operated independently of the ambient air. Oth-
erwise, a separate installation room is required to guar-
antee that the combustion air supply is free from the 
above substances.

4.4 

Required minimum gaps/assembly clearances

 min

min 5

min 5

min 500**

 min 145

165/246*

Fig. 4.3 Required minimum gaps/assembly clearances

The boiler must be mounted on a flat, vertical wall sur-
face which is large enough for the boiler including the 
required minimum space requirement and the space re-
quired for assembly (Fig. 4.3). These are shown on the 
mounting template supplied with the boiler, and are:
–  5 mm on each side of the boiler
–  145 mm underneath the boiler
–  165 mm* above the boiler if using a flue pipe of 100 

mm outside diameter

–  246 mm* above the boiler if using a flue pipe of 125 

mm outside diameter

–  500 mm** in front of the boiler

h

 Note!

If the boiler is to be installed in a timber framed 
building, it should be fitted in accordance with 
“IGE/UP/7 Edition 2 Gas installations in timber 
framed and light steel framed buildings“.

It is not necessary to maintain a clearance between the 
appliance and combustible materials or components, 
since, at the rated heating power of the appliance, the 
temperature here is always lower than the permitted 
temperature of 85 °C.

4 Assembly

Summary of Contents for ecoTEC exclusive SERIES

Page 1: ...For the installer Installation and maintenance instructions ecoTEC exclusive Gas wall boilers with condensing appliance technology ecoTEC exclusive 832 ecoTEC exclusive 838 GB...

Page 2: ...1 4 Filling the condense trap 22 6 2 Checking the gas setting 22 6 2 1 Checking the connection pressure gas inlet working pressure 22 6 2 2 Checking CO2 content and setting if necessary setting the a...

Page 3: ...the operator of the in stallation in order for him or her to store it so that it is available whenever it is required 1 2 Safety instructions and symbols Please observe the safety instructions in thi...

Page 4: ...N 483 EN 625 EN 677 EN 50165 EN 55014 EN 60335 1 EN 60529 EN 61000 3 2 EN 61000 3 3 hVaillant Ltd supports the Benchmark Initiative You will find the Benchmark Logbook on the last page of this instruc...

Page 5: ...n problems can be caused if the tank is not bled properly In such cases first contact the person in charge of filling the tank Affix tank sticker Affix the enclosed tank sticker propane quality on the...

Page 6: ...e current Version of I S 813 Domestic Gas Instal lations and the current Building Regulations The current ETCI Regulations for the installa tion of electrical equipment must also be ob served a Cautio...

Page 7: ...rriage of carton from point of delivery to point of installation first or higher floor cellar Recommend 2 person lift or 1 person with use of sack truck If 1 person is performing lift straddle the loa...

Page 8: ...nd ensure good grip when handling appliance Positioning of Appliance for Final Installation within compartment etc restricting installation If appliance weight is over 25 kg always use 2 persons to mo...

Page 9: ...ing and dimensions for connection 70 190 480 800 2 25 450 7 20 100 100 20 5 3 7 20 20 R 1 2 180 4 6 Fig 4 2 Dimensions for connection mm Key to Fig 4 2 1 Flue connection 2 Mounting bracket 3 Heating r...

Page 10: ...stallation in timber framed and light steel framed buildings Please note the following instructions before choosing where to install the heater a Caution Do not install the appliance in rooms prone to...

Page 11: ...together so that the front cladding releases Pull the housing forwards at the lower edge and re move the front cladding upwards 5 Installation d Danger The Vaillant ecoTEC exclusive may only be in sta...

Page 12: ...for natural gas and 37 mbar for propane gas The gas pipe should first be cleaned by blowing out with compressed air This prevents damage to the appliance Connect the compression gas service cock and...

Page 13: ...ed with the appliance for top connection of the flow and return pipework within the casing 5 5 Pressure Relief Valve Fig 5 4 Fitting the pressure relief valve The pressure relief valve and filling loo...

Page 14: ...ity during installation 1435 10 550 880 40 Fig 5 6 Item No 303900 5 6 2 Optional 125 mm flue pipe A concentric flue pipe having an outside diameter of 125 mm is available which can be extended to a le...

Page 15: ...iler Installation which recommends 2 5 m from wall fence or boundary Where a plume diverter terminal is used this is measured in the direction of the flow of products BS 5440 1 We recommend that the t...

Page 16: ...re must be a ventilation valve between the two siphons This is normally provided in a drain c Draining into a gully 5 under the grid 6 and above the water level The external piping should be kept as s...

Page 17: ...7 8 9 Danger of destroying the electronics hNote There is no provision set in the factory for connection of an installation thermostat for underfloor heating hNote Make sure that the connection cables...

Page 18: ...been made The cover is secured with two clips Controller Item no Connection VRT 400 single circuit weather compensator 307 409 Installation in electronics box plug and play VRT 240 room thermostat 307...

Page 19: ...Room thermostat 230 V 50 Hz Remove bridge when connecting Heating pump Mains connection 230 V 50 Hz Igniter Caution Do not connect mains voltage Danger of damage to the electronics Diagnosis via eBUS...

Page 20: ...NTC X 20 5 red X 20 7 black X 20 7 black X 20 8 blue X 2 12 green X 2 11 red X 2 9 black Pump X 20 18 red 24 VDC X 20 9 blue Earth X 20 16 blue Earth X 20 4 grey PWM X 20 3 black Hall signal X 20 17...

Page 21: ...e by pushing the minus button Turn the rotary knobs 1 and 4 to the left hand stop and switch the unit on using the main switch 3 h Note Use the test programme P 6 for filling the heating system The pr...

Page 22: ...ion out of the heating system before the boiler is started up Close the 1 2 KFE drain cocks Re fill the heating system with water as described in Section 6 1 1 Check that the over pressure valve in th...

Page 23: ...the sealing screw is not leaking Put the front cover back on and turn on the device If the connection pressure is not within the permissible range and you cannot resolve the problem inform the gas su...

Page 24: ...m a function check before commissioning the ap pliance and handing over to the user Commission the appliance in accordance with the in structions in the relevant operating manual Check the gas infeed...

Page 25: ...m cover upwards until the spring retaining clips engage at the side of the appliance It may be necessary to adapt the bot tom cover by removing the easy break sections 6 4 Handing over the appliance t...

Page 26: ...ion see Chapter 8 Using the following description you can select the rele vant parameters Press the i and buttons simultaneously The display shows d 0 Scroll to the desired diagnosis number with the o...

Page 27: ...You can enter your settings in the end column after setting the appliance specific parameters hNote The diagnosis points d 17 d 71 and d 84 are lo cated in the 2nd diagnosis level see Chapter 9 1 2 7...

Page 28: ...d thermal properties of the heating installa tion In the factory the burner anti cycle time is set to a value of 20 minutes It can be varied under diagnosis point d 02 within the range 2 minutes to 60...

Page 29: ...1 Volumeflow l h Lift mbar Fig 7 2 Characteristic pump line for ecoTEC exclusive 832 and 838 Key to Fig 7 2 1 at 27 kW 2 at 30 kW 7 3 Adjusting the bypass valve The appliances have a bypass valve The...

Page 30: ...maintenance cocks if fitted in the heating flow and return and the cold water inlet valve on the inlet combination Remove the front cover from the device Always perform the following steps after perfo...

Page 31: ...2 3 or 5 above Clean the primary heat exchanger Fit a new burner door seal kit spareparts no 0020026401 observe the assembly instructions enclosed with the seal kit Refit the burner module and tighten...

Page 32: ...ion und grounding lines off the ignition electrode 4 Only ecoTEC exclusive 832 Pull the cable plug off the fan motor and the cable off the gas fitting Only ecoTEC exclusive 838 Open the mains coupling...

Page 33: ...3 2 1 6 Fig 8 5 Installing compact thermal module Place the entire compact thermal module 5 onto the integral condensation heat exchanger Tighten the five nuts 2 across the diagonal until the burner d...

Page 34: ...pliance Release the nut 4 on the secondary heat exchanger Release the clamp 1 on the preference changeover valve Release the clamps 2 and 3 on the secondary heat exchanger Remove the secondary heat ex...

Page 35: ...8 1 Checking the connection pressure gas inlet working pressure To check the connection pressure proceed as described in Chapter 6 1 2 8 8 2 Checking CO2 content and adjusting if necessary To check t...

Page 36: ...water Storage tank charging heat retention mode Page 20 Water pump flow S 21 Fan start S 23 Ignition S 24 Burner mode S 25 Fan and water pump return water S 26 Fan return flow S 27 Water pump return w...

Page 37: ...y flashes Save the new value by holding down the i button for approx 5 seconds until the display no longer blinks You can end the diagnosis mode as follows Press the i and buttons simultaneously or Do...

Page 38: ...ostat 24V DC on terminal 3 and 4 0 Room thermostat open no heat request 1 Room thermostat closed heat request d 22 Hot water demand 1 on 0 off d 23 Summer mode heating on off 1 heating on 0 heating of...

Page 39: ...ssful ignitions in the last attempt d 64 Average ignition time in seconds d 65 maximum ignition time in seconds d 68 Unsuccessful ignitions at the first attempt number d 69 Unsuccessful ignitions at t...

Page 40: ...25 Interruption in cable harness Cable harness faulty F 27 External light Gas solenoid valve defective flame detector defective F 28 Appliance does not start Attempts to ignite during start failed Fa...

Page 41: ...is turned on and the button is pressed for 5 seconds simultaneously The display shows P 0 Press the key to start counting the test pro gramme number upwards Press the i to operate the appliance now an...

Page 42: ...Use only new gaskets and O rings After completing the work check for gas leaks and perform a function check see Chapter 6 10 2 Replacing burner d Danger Before replacing the component comply with the...

Page 43: ...afety instructions in Section 10 1 Disconnect the appliance from the mains as described in Chapter 10 1 and close the gas cock in the gas supply pipe Close the maintenance cocks if fitted in the heati...

Page 44: ...ge F 70 In the second diagnosis level under the diagnosis point d 93 enter the number of appliance variant according to Table 10 1 see Chapter 9 1 2 The electronics is now set to the appliance type an...

Page 45: ...r Required connection pressure 0 35 0 35 bar Hot water discharge temperature range 35 65 35 65 C General Gas connection 15 15 mm Heating connection 22 22 mm Hot and cold water connection 15 15 mm Exha...

Page 46: ......

Page 47: ......

Page 48: ...0020017768_02_GB 03 2008...

Reviews: