42
20901559_EN_RE_RZ_V7_230523
Commissioning (operation)
Operation with condensable vapors
>
Allow the pump to attain its operating temperature before
pumping condensable vapors. Keep the vapor inlet pressure
below the permitted maximum.
>
Open the manual gas ballast valve in case of pumping signif
‑
icant amounts of vapor,
see chapter:
.
Oil level check
NOTE
NOTE
A too low oil level during operation may damage the
vacuum pump.
>
Check the oil level of the vacuum pump every time before
starting the pump.
>
Check the oil level of the vacuum pump at least once a
week.
>
Check the oil level more frequently if high amounts of gas
or vapor are pumped or if operating the vacuum pump with
open gas ballast valve.
>
Oil consumption will increase at inlet pressures above
75 Torr (100 mbar). In that case check the oil level more fre
‑
quently.
>
Adjust the oil level, if necessary,
see chapter:
.
Pay attention to pumped media
CAUTION
Possible damage due to aggressive or cor-
rosive media.
Aggressive or corrosive gases or vapors can damage per
‑
sonnel, environment or the vacuum pump.
>
Use appropriate accessories to protect personnel, envi‑
ronment, and the vacuum pump.
>
Use accessories such as cold trap, separator, oil sepa‑
rator, or shut‑off valves
,
see chapter:
>
Use special oil to protect the pump, if necessary.
Condensable vapors
Check oil level
Summary of Contents for RE 2.5
Page 24: ...24 20901559_EN_RE_RZ_V7_230523 Introduction ...
Page 40: ...40 20901559_EN_RE_RZ_V7_230523 Installation and connection ...
Page 48: ...48 20901559_EN_RE_RZ_V7_230523 Installation and connection ...
Page 73: ...73 20901559_EN_RE_RZ_V7_230523 Appendix 8 8 8 8 CU Certificate CU Certificate CU Certificate ...
Page 76: ...76 20901559_EN_RE_RZ_V7_230523 ...
Page 77: ...77 20901559_EN_RE_RZ_V7_230523 ...
Page 78: ...78 20901559_EN_RE_RZ_V7_230523 ...