lonworks interface
vacon
• 25
24-hour service: +358-40-8371 150
•
Email: [email protected]
6
6.4
Network Configuration Variables
Function
Variable Name
SNVT type
Maximum motor speed
nciMaxSpeed
SCPTmaxSetpoint
Minimum motor speed
nciMinSpeed
SCPTminSetpoint
Receive heartbeat time
nciRcvHrtBt
SCPTmaxRcvTime
Send heartbeat time
nciSndHrtBt
SCPTmaxSndTime
Minimum output time
nciMinOutTime
SCPTminSndTime
Nominal motor speed in RPM
nciNmlSpeed
SCPTnomRPM
Nominal motor frequency
nciNmlFreq
SCPTnomFreq
Minimum ramp up time
nciRampUpTm
SCPTrampUpTm
Minimum ramp down time
nciRampDownTm
SCPTrampDownTm
Default value for nviDrvSpeedScale
nciDrvSpeedScale
SCPTdefScale
Table 6-10. Network configuration variables
nciMaxSpeed
This configuration property is used to define the maximum speed of a motor. The value is entered as a
percentage of nominal speed in RPM, as defined by the Nominal Speed (nciNmlSpeed) configuration
value. The value of the maximum speed must be validated against the value of the minimum speed as
follows:
-163.840 < minimum speed < maximum speed < 163.830
nciMinSpeed
This configuration property is used to define the minimum speed of the motor. The value is entered as
a percentage of nominal speed in RPM, as defined by the Nominal Speed (nciNmlSpeed) configuration
value. The value of the minimum speed must be validated against the value of the maximum speed as
follows:
-163.840 < minimum speed < maximum speed < 163.830
nciRcvHrtBt
This configuration property is used to control the maximum time that elapses after the last update of
the network variables nviDrvSpeedStpt or nviDrvSpeedScale before the VSD object starts to use the
default values.
nciSndHrtBt
This configuration property defines the maximum period that expires before the network variables
nvoDrvSpeed, nvoDrvCurnt and nvoDrvPwr are automatically updated.