3.3

 

Bus termination resistors 

To assure a proper data transmission, termination of the network segments is required. Depending 

on the type of network, either one or two terminations are necessary. Free topology network segment 

requires only one termination whereas a doubly terminated bus topology requires two. 

The jumper X5 on the Vacon LonWorks board must be set accordingly. Use 94-ohm termination 

resistance when only one termination is needed and 47-ohm for two terminations. 

 

Figure 3-7. Using jumper X5 to set the bus termination. 

 

3.4

 

LED indications 

The three LED indications next to the connector show the present statuses of the Neuron (green H3), 

the LonWorks board (yellow H2) and the Fieldbus Module (green H1). From the user's viewpoint, the 

first two are the most significant. 

 

Figure 3-8. LED indications on the LonWorks board 

 

H3 

Neuron Service LED  

GREEN  

H2 

Board Status 

YELLOW 

H1 

Bus Status 

GREEN 

 

21

22

23

H3
H2
H1

X5

lw1.fh8

 

47

94

no termination

X5

 

21

22

23

H3
H2
H1

X5

lw1.fh8

 

Summary of Contents for OPTC4

Page 1: ...vacon nx ac drives optc4 lonworks option board user manual...

Page 2: ...2 Grounding of bus cable shield in OPT C4 8 3 3 Bus termination resistors 10 3 4 LED indications 10 4 INSTALLATION OF VACON NX LonWorks BOARD 12 4 1 Board information sticker 14 5 COMMISSIONING 15 5 1...

Page 3: ...es on a network communicate with each other using LonTalk protocol Interoperable nodes use Standard Network Variable Types SNVT for communicating over the network The definition of an SNVT includes un...

Page 4: ...Pluggable connector 5 mm Communications Channel type TP FT 10 Transfer cable Twisted pair Baud rate 78 Kbit s Environment Ambient operating temperature 10 C 50 C Storing temperature 40 C 70 C Humidit...

Page 5: ...Echelon s LPT 10 Link Power Transceiver and these transceivers can communicate with each other on a single twisted pair cable termination termination Figure 2 1 Doubly Terminated Bus Topology termina...

Page 6: ...sion speeds 2 3 Profiles LonMark Functional Profiles describe in detail the application layer interface including the network variables configuration properties and default and power up behaviors requ...

Page 7: ...d to the fieldbus through 3 pin pluggable bus connector The communication with the control board takes place through the standard Vacon Interface Board Connector 3 1 LonWorks OPT C4 option board Figur...

Page 8: ...talled in slot E of the control board It is not necessary to detach the whole board for the grounding of the bus cable shield Just detach the terminal block 3 2 1 Grounding the bus cable shield direct...

Page 9: ...he data cables and the shield in their respective terminals See Table 3 1 Figure 3 5 4 If the LonWorks board was detached from the control unit place it into slot E of the control board see board inst...

Page 10: ...t be set accordingly Use 94 ohm termination resistance when only one termination is needed and 47 ohm for two terminations Figure 3 7 Using jumper X5 to set the bus termination 3 4 LED indications The...

Page 11: ...is ready for external communication Blinking slow once 5 s Option board is activated and in FAULT state Internal fault on option board Bus status LED H1 GREEN LED is Meaning OFF Fieldbus module is wai...

Page 12: ...205 4 4 INSTALLATION OF VACON NX LONWORKS BOARD NOTE MAKE SURE THAT THE FREQUENCY CONVERTER IS SWITCHED OFF BEFORE AN OPTION OR FIELDBUS BOARD IS CHANGED OR ADDED A Vacon NX frequency converter B Remo...

Page 13: ...d in slot E on the control board of the frequency converter Make sure that the grounding plate see below fits tightly in the clamp 21 22 23 H3 H2 H1 X5 lw1 fh8 E Make a sufficiently wide opening for y...

Page 14: ...livered by the factory includes a sticker shown below Please mark the board type 1 the slot into which the board is mounted 2 and the mounting date 3 on the sticker Finally attach the sticker on your...

Page 15: ...ntrol board and 2 to reach and edit the parameters associated with the expander board Enter the following menu level G with the Menu button right At this level you can browse through slots A to E with...

Page 16: ...for the active control place see Vacon NX User s Manual Chapter 7 3 3 Master software 1 Write 100 0 1 to nviDrvSpeedStpt 2 Frequency converter status is RUN and output frequency is 1 00 nviDrvSpeedSc...

Page 17: ...Direct control of Vacon NX e g Run Stop Direction Speed reference Fault reset Full access to all Vacon NX parameters Monitor Vacon NX status e g Output frequency Output current Fault code 6 1 General...

Page 18: ...IN5 SNVT_lev_percent nv15 nviProcessIN6 SNVT_lev_percent nv16 nviProcessIN7 SNVT_lev_percent nv17 nviProcessIN8 SNVT_lev_percent nv31 nvoProcessOut2 SNVT_lev_percent nv32 nvoProcessOut3 SNVT_lev_perce...

Page 19: ...the Node object or the Variable Speed Motor Drive object within a node Supported requests are RQ_NORMAL RQ_UPDATE_STATUS RQ_CLEAR_STATUS RQ_REPORT_MASK RQ_DISABLED RQ_ENABLE and RQ_CLEAR_ALARM nviDrv...

Page 20: ...able provides a mechanism to clear the kWh trip counter or the Drive total running hours trip counter 1 MWh trip counter 2 Operation day trip counter nviProcessIn1 8 These input network variables are...

Page 21: ...98 Actual Values 99 Active Fault Code 100 Not Used 101 899 Parameter 900 999 Reserved Reserved for LonWorks board internal usage 1000 Not Used 1001 1999 Parameter Table 6 5 Grouping of ID numbers Exam...

Page 22: ...hour 0 h 65535 Status word nvoDrvStatus SNVT_state n a n a kWh trip counter nvoDrvEnrgy SNVT_elect_kwh 0kWh 65535kWh Active fault code nvoActFault SNVT_count 0 41 Process Out nvoProcessOut1 8 SNVT_ le...

Page 23: ...Description Value 0 Value 1 0 Not Ready Ready 1 FC stopped Running 2 Clockwise Counterclockwise 3 No fault Fault active 4 No warning Warning active 5 Reference Actual value Reference Actual value Tabl...

Page 24: ...DigitalOut1 8 These output network variables are sent directly from the application see more detailed explanation in chapter 6 5 Process data state value command 0 0 off 0 0 1 200 0xC8 on 200 1 1 0XfF...

Page 25: ...as a percentage of nominal speed in RPM as defined by the Nominal Speed nciNmlSpeed configuration value The value of the maximum speed must be validated against the value of the minimum speed as foll...

Page 26: ...rties nciMinSpeed nciMaxSpeed entered as a percentage of nominal speed nciNmlFreq This configuration property is used to provide the nominal frequency for the motor nciRampUpTm Defines the acceleratio...

Page 27: ...bit 4 bit 5 bit 6 bit 7 bit 10 bit 11 bit 12 nviDigitaln 2 nviDigitaln 3 nviDigitaln 4 nviDigitaln 5 nviDigitaln 6 nviDigitaln 7 nviDigitaln 8 bit 1 FBGeneralStatusWord bit 2 bit 3 bit 4 bit 5 bit 6...

Page 28: ...3 Fieldbus fault The received heartbeat time has expired Check the installation If installation is correct contact the nearest Vacon distributor 54 Slot fault Defective option board or slot Check the...

Page 29: ...T 6 Motor Voltage V 0 1 V Process data OUT 7 DC link voltage V 1 V Process data OUT 8 Active Fault Code The Multipurpose Control Application has a selector parameter for every Process Data The monitor...

Page 30: ...5 7 PID control and Pump and fan control applications Data Value Unit Step Process Data IN1 Reference for PID controller 0 01 Process Data IN2 Actual Value 1 to PID controller 0 01 Process Data IN3 Ac...

Page 31: ......

Page 32: ...D Rev A Manual authoring documentation vacon com Vacon Plc Runsorintie 7 65380 Vaasa Finland Subject to change without prior notice 2012 Vacon Plc Find your nearest Vacon office on the Internet at www...

Reviews: