Parameter lists
vacon • 9
24-hour s358 (0)40 837 1150 • Email: [email protected]
3.2
Basic parameters (Control keypad: Menu M2 G2.1)
Code
Parameter
Min
Max
Unit
Default
Cust
ID
Note
P2.1.1
0,00
Par. 2.1.2
Hz
25,00
101
P2.1.2
Par.
2.1.1
320,00 Hz 50,00
102
NOTE: If f
max
> than the
motor synchronous speed,
check suitability for motor
and drive system
P2.1.3
0,1 3000,0 s
1,0
103
NOTE: If PID-controller is
used, Acceleration time 2
(par. 2.4.3) is automatically
applied
P2.1.4
0,1 3000,0 s
1,0
104
NOTE: If PID-controller is
used, Deceleration time 2
(par. 2.4.4) is automatically
applied
P2.1.5
0
2 x I
H
A
I
L
107
P2.1.6
180 690 V 400V
110
P2.1.7
30,00 320,00 Hz 50,00
111
Check the rating plate of the
motor
P2.1.8
300 20
000 rpm 1440
112
The default applies for a 4-
pole motor and a nominal
size frequency converter.
P2.1.9
0,4 x I
H
2
x
I
H
A
I
H
113
Check the rating plate of the
motor.
P2.1.10
0,30 1,00
0,85
120
Check the rating plate of the
motor
P2.1.11
0
1
0
505
0=Ramp
1=Flying start
P2.1.12
0
3
0
506
0=Coasting
1=Ramp
2=Ramp+Run enable coast
3=Coast+Run enable ramp
P2.1.13
0
1
0
109
0=Not used
1=Automatic torque boost
P2.1.14
0
1
0
117
0=Keypad reference
1=Fieldbus reference
P2.1.15
0,00
Par. 2.1.2
Hz
10,00
105
P2.1.16
0
1
0
731
0=Not used
1=Automatic restart
P2.1.17
0
1
1
115
0=All parameters visible
1=Basic group (G2.1) visible
Table 10. Basic parameters G2.1