vacon • 64
Service
Local contacts: https://www.danfoss.com/en/contact-us/contacts-list/
5.3.5
IUS_13 / IUS_14
1
Open the cabinet door.
2
Release the service ramp and turn it down in front of the drive.
NOTE!
The height of the surface in front of the cabinet should not differ more than
5mm from the level of the cabinet installation.
Figure 44. Lowering the service ramp
3
1. Loosen the four M5 screws (tightening torque 3 Nm) and remove the touch cover.
2. Remove the eight M8 screws (torque 20 Nm) and remove the upper holder plate.
3. Remove the four M8 screws (torque 20 Nm) from the drive bottom holder plate.
Figure 45. Removing the drive touch cover and holder plates
13938_00
±5mm
13939_00
3
2
1