Terminal numbers
Always connect the supply cables to the choke terminals marked with #1 (see Figure 5-29). Choose the
converter connection according to the table below:
Supply volt-
age
Converter
connection
(terminal no.)
400-480Vac
2
500Vac
3
575-690Vac
3
Figure 5-29. Example of input chokes for Vacon NX Liquid-Cooled. Sizes 261A…1150A
Choke type
H1
[mm]
H2
[mm]
W1
[mm]
W2
[mm]
W3
[mm]
W4
[mm]
D1
[mm]
D2
[mm]
D3
[mm]
S1
S2
Ø
Weight
[kg]
CHK0261N6A0 319 357 354 150 275 120 230 206 108 9*14
(8pcs) 9*14
(9
pcs) 53
CHK0400N6A0 383 421 350 150 275 120 262 238 140 9*14
(8pcs)
11*15
(9
pcs) 84
CHK0520N6A0 399 446 497 200 400 165 244 204 145 Ø13
(8pcs)
11*15
(9
pcs) 115
CHK0650N6A0 449 496 497 200 400 165 244 206 145 Ø13
(8pcs)
11*15
(9
pcs) 130
CHK0750N6A0 489 527 497 200 400 165 273 231 170 Ø13
(8pcs)
13*18
(9
pcs) 170
CHK0820N6A0 491 529 497 200 400 165 273 231 170 Ø13
(8pcs)
13*18
(9
pcs) 170
CHK1030N6A0 630 677 497 200 400 165 307 241 170 Ø13 (8pcs)
13*18 (36pcs)
213
CHK1150N6A0 630 677 497 200 400 165 307 241 170 Ø13 (8pcs)
13*18 (36pcs)
213
Table 5-19. Choke dimensions; Sizes 261A…1150A
If you have ordered the input chokes for Vacon NX Liquid-Cooled separately pay attention to the following
instructions:
1.
Protect the chokes from dripping water. You may even need to use plexiglass for protection because
jets of water may occur when working with the connections.
2.
Connection of cables:
Types CHK0023N6A0, CHK0038N6A0, CHK0062N6A0 (chokes with terminal blocks)
The terminals are marked with letters U,V,W and X,Y and Z in such an order, however, that terminals U
and X, V and Y as well as W and Z form pairs of which one is an input and the other an output. Further-
more, terminals U,V and W must all be used as either input or output. The same applies to terminals X,
Y and Z. See Figure 5-27.