4.4
Vacon CX103OPT
*) NOTE!
Thermistor input (terminals 221 and 222) must be shorted if not used.
Figure 4-4 Control connections of Vacon CX103OPT.
Terminal
Signal
Description
206
+24V
Control voltage output
Voltage for switches, etc. max. 50 mA
207
GND
I/O ground
Ground for reference and controls
208
CMC
Common for DIC1-DIC5
Connect to GND or + 24 V
209
DIC1
External fault
Contact open = no fault
(closing contact)
Contact closed = fault
210
DIC2
Run disable Cont.
open = start of motor enabled
Cont. closed= start of motor disabled
211
DIC3
Acceler. / Decel. time
Contact open = time 1 selected
selection
Contact closed = time 2 selected
212
DIC4
Jogging speed selection
Contact open = no action
Contact closed = jogging speed
213
DIC5
Fault reset
Contact open = no action
Contact closed = fault reset
214
GND
I/O ground
215
I
out
+
Analogue output
Programble
0—20 mA/R
L
max. 500
Ω
(Motor current as default value)
221
T I +
Thermistor input
222
T I -
223
RO3/1
Relay output 3
READY
224
RO3/2
225
RO4/1
Relay output 4
RUN
226
RO4/2
227
RO5/1
Relay output 5
FAULT
228
RO5/2
Signal from
motor thermistors *)