CANopen option board interface
vacon • 69
Local contacts: http://drives.danfoss.com/danfoss-drives/local-contacts/
8
8.2.2
CiA-402 objects
8.2.2.1
0X6040 - Controlword
Controlword is used to control the drive operation according to the PDS state machine. By default,
Controlword is mapped into the first two bytes of rxPDO1.
Table 66. 0x6040:Controlword
8.2.2.2
0X6041 - Statusword
Statusword indicates whether the drive is in remote control and if the target velocity is reached. By
default, Statusword is mapped into the first two bytes of txPDO1.
Table 67. 0x6041:Statusword
8.2.2.3
0X6042 - vl Target Velocity
The signed value of motor rpm speed request to drive. A negative value means that the motor is run-
ning clockwise. By default, the object is mapped into the last two bytes of rxPDO1.
Bit
Name
Description
12-15
na
Not used
Bits 12 through 15 are not in use.
11
ar
Alarm reset
Rising edge resets alarm
10
r
Reserved
Bit 10 is not in use
9
oms
Operation mode specific
Bit 9 is not in use
8
h
Halt
Bit 8 is not in use
7
fr
Fault reset
Rising edge resets fault
4-6
na
Not Used
Bits 4 through 6 are not in use.
3
eo
Enable operation
Start drive
2
qs
Quick stop
Stops the drive using the drive/application specific stop function
used as quick stop
1
ev
Enable voltage
Enables/disables output voltage
0
so
Switch on
Enables possibility to start drive together with ev
Bit
Name
Description
15
na
Not in use
Bit 15 is not in use
14
idm
Incorrect drive mode
Indicates that the drive is in incorrect “Control mode” for the used
CiA-402 profile
12-13
oms
Operation mode specific
Bits 12 through 13 are not in use
10
tr
Target reached
Target velocity reached
9
rm
Remote
Indicates if the drive is controllable by Fieldbus
8
na
Not in use
Bit 8 not in use.
7
w
Warning
The AC drive has an active Alarm.
6
sod
Switch on disabled
PDS switch on disable
5
qs
Quick stop
PDS quick stop active
4
ve
Voltage enabled
Voltage is enabled
3
f
Fault
PDS Fault (indicates fault condition)
2
oe
Operation enabled
PDS operation enabled (drive is running)
1
so
Switched on
PDS switched on
0
rtso
Ready to switch on
PDS ready to switch on