vacon • 103
Parameters
6
6.1.14.4
Group 3.13.4: FeedForward
Feedforward usually needs accurate process models, but in some simple cases a gain + offset
type of feedforward is enough. The feedforward part does not use any feedback measurements
of the actual controlled process value (water level in the example on page 144). Vacon feedfor-
ward control uses other measurements which are indirectly affecting the controlled process
value.
6.1.14.5
Group 3.13.5: Sleep Function
This function will put the drive into sleep mode if the frequency stays below the sleep limit for
a longer time than that set with the Sleep Delay.
Table 94. Feedforward settings
Code
Parameter
Min
Max
Unit
Default
ID
Description
P3.13.4.1
Function
1
9
1
1059 See P3.13.3.1.
P3.13.4.2
Gain
-1000
1000
%
100.0
1060 See P3.13.3.2
P3.13.4.3
FF 1 Source
0
25
0
1061 See P3.13.3.3
P3.13.4.4
FF 1 Minimum
-200.00
200.00
%
0.00
1062 See P3.13.3.4
P3.13.4.5
FF 1 Maximum
-200.00
200.00
%
100.00
1063 See P3.13.3.5
P3.13.4.6
FF 2 Source
0
25
0
1064 See P3.13.3.6
P3.13.4.7
FF 2 Minimum
-200.00
200.00
%
0.00
1065 See P3.13.3.7
P3.13.4.8
FF 2 Maximum
-200.00
200.00
%
100.00
1066 See P3.13.3.8
Table 95. Sleep function settings
Code
Parameter
Min
Max
Unit
Default
ID
Description
P3.13.5.1
SP 1 Sleep Freq
0.00
320.00
Hz
0.00
1016
Drive goes to sleep mode
when the output frequency
stays below this limit for a
time greater than that
defined by parameter
Sleep
delay
.
P3.13.5.2
0
3000
s
0
1017
The minimum amount of
time the frequency has to
remain below the Sleep level
before the drive is stopped.
P3.13.5.3
Varies
0.00
1018
Defines the level for the PID
feedback value wake-up
supervision. Uses selected
process units.
P3.13.5.4
SP 1 WakeUpMode
0
1
0
1019
Select if wake up level should
work as an absolute level or
as an offset below the actual
setpoing value.
0 = Absolute Level
1 = Relative Setpoint
P3.13.5.5
SP 2 Sleep Freq
0.00
320.00
Hz
0.00
1075
Drive goes to sleep mode
when the output frequency
stays below this limit for a
time greater than that
defined by parameter
Sleep
delay
.
Summary of Contents for 100X series
Page 1: ...vacon 100 x ac drives Solar pump application manual ...
Page 2: ......
Page 6: ...vacon 3 Vacon 100X Solar Pump Application 1 ...
Page 8: ...2 vacon 5 Safety ...
Page 160: ...vacon 157 Parameters 6 ...
Page 169: ...Fault vacon 166 Service support find your nearest Vacon service center at www vacon com 7 ...
Page 170: ...7 vacon 167 Fault ...
Page 171: ......