vacon • 96
Parameters
Local contacts: https://www.danfoss.com/en/contact-us/contacts-list/
7.1.3
Group 3.2: Start/Stop setup
Start/Stop commands are given differently depending on the control place.
Remote control place (I/O A):
Start, stop and reverse commands are controlled by 2 digital inputs
chosen with parameters P3.5.1.1 and P3.5.1.2. The functionality/logic for these inputs is then se-
lected with parameter P3.2.6 (in this group).
Remote control place (I/O B):
Start, stop and reverse commands are controlled by 2 digital inputs
chosen with parameters P3.5.1.4 and P3.5.1.5. The functionality/logic for these inputs is then se-
lected with parameter P3.2.7 (in this group).
Local control place (Keypad):
Start and stop commands come from the keypad buttons, while the
direction of rotation is selected by the parameter P3.3.1.9.
Remote control place (Fieldbus):
Start, stop and reverse commands come from fieldbus.
Table 64. Start/Stop Setup menu
Code
Parameter
Min
Max
Unit
Default
ID
Description
P3.2.1
Rem.Ctrl. Place
0
1
0
172
Selection of remote control
place (start/stop). Can be used
to change back to remote con-
trol from VACON
®
Live e.g. in
case of a broken panel.
0=I/O control
1=Fieldbus control
P3.2.2
Local/Remote
0
1
0
211
Switch between local and
remote control places
0=Remote
1=Local
P3.2.3
Keypad stop button
0
1
0
114
0=Stop button always enabled
(Yes)
1=Limited function of Stop but-
ton (No)
P3.2.4
Start function
0
1
0
505
0=Ramping
1=Flying start
P3.2.5
0
2
0
506
0: coasting
1: ramp to min frequency
2: ramp to zero frequency
P3.2.6
0
4
1
300
Logic = 0:
Start sign 1 = Start Forward
Start sign 2 = Start Backward
Logic =1:
Start sign 1 = Start
Start sign 2 = Reverse
Logic = 2:
Double Start
Logic = 3:
Start sign 1 + Analogue sign
Logic = 4:
Solar only
P3.2.7
I/O B logic
0
4
1
363
See above.
P3.2.8
FB Start logic
0
1
0
889
0=Rising edge required
1=State