9.7 Digital outputs (Control panel: Menu PAR -> P8)
8.1
RO1
SIGNAL
SELECTION
8.2
RO2
SIGNAL
SELCETION
8.3
DO1
SIGNAL
SELCETION
Table 9.2: Output signals via RO1, RO2 and DO1
Setting
Signal content
0 =
Not used
Output is not in operation.
1 =
Ready
The frequency converter is ready to operate.
2 =
Run
The frequency converter operates (motor is running).
3 =
Fault
A fault trip has occurred.
4 =
Fault inverted
A fault trip has not occurred.
5 =
Warning
A warning is active.
6 =
Reversed
The reverse command has been selected, output fre-
quency to the motor is negative.
7 =
At speed
The output frequency has reached the set reference.
8 =
Motor regulator active
Each of motoring current regulator,generating current
reg. ,over voltage reg. ,under voltage reg. is active.
9 =
FB Control Word.B13
Output can be controlled with B13 in the fieldbus control
word.
10 =
FB Control Word.B14
Output can be controlled with B14 in the fieldbus control
word.
11 =
FB Control Word.B15
Output can be controlled with B15 in the fieldbus control
word.
Summary of Contents for 10
Page 1: ......
Page 17: ...14 vacon installation Tel 358 0 201 2121 Fax 358 0 201 212205 3 MI1 MI3 3P 230 V POWER LOSS ...
Page 18: ...installation vacon 15 24 hour support 0 201 212 575 Email vacon vacon com 3 ...
Page 19: ...16 vacon installation Tel 358 0 201 2121 Fax 358 0 201 212205 3 MI1 MI3 1P 230 V POWER LOSS ...
Page 20: ...installation vacon 17 24 hour support 0 201 212 575 Email vacon vacon com 3 ...