18
Frequency Range
(Synchronized Range)
47 ~ 53 Hz or 57 ~ 63 Hz
Frequency Range
50 Hz ± 0.1 Hz or 60Hz ± 0.1 Hz (Batt. Mode)
Current Crest Ratio
3:1
Harmonic Distortion
≦
2 % THD (Linear Load); 4 % THD (Non-linear Load)
Transfer
Time
AC Mode to Batt.
Mode
Zero
Inverter to Bypass
< 4 ms
Waveform (Batt. Mode)
Pure Sinewave
EFFICIENCY
AC Mode
≧
91% @ full charged battery
ECO Mode
≧
96% @ full charged battery
Battery Mode
≧
90%
BATTERY
Battery Type
12V/9AH
Number
6
Recharge Time
3 hours recover to 95% capacity for internal battery@ 2A charging current
Charging Current
Default: 2A, Max: 8A adjustable
Charging Voltage
82.1 VDC ± 1%
PHYSICAL
Dimension, D X W X H (mm)
630 x 438 x 88
Net Weight
(kgs)
With battery
27.5
Without battery
12.4
ENVIRONMENT
Operation Humidity
20-95 % RH @ 0- 40°C (non-condensing)
Noise Level
Less than 50dBA @ 1 Meter (With fan speed control)
MANAGEMENT
Smart RS-232 or USB
Supports Windows® 2000/2003/XP/Vista/2008/7/8/10, Linux, Unix, and MAC
SNMP Network
Power management from SNMP manager and web browser
* Derate capacity to 90% of capacity when the output voltage is adjusted to 200VAC or 208VAC.
*** Product specifications are subject to change without further notice.
6.1 Runtime Chart
Model (VPN)
UPS2URM3000DC-NC-1N
Battery
Load percentage
Minutes
100.00%
2.64
90.00%
3.36
80.00%
4.34
70.00%
5.53
60.00%
7.33
50.00%
9.79
40.00%
13.51
30.00%
19.90