Pd8 FUNCTION TABLE

DISPLAY

DATA

DESCRIPTION

DEFAULT

MEMO

DATI

dEF

no / Si

Select item 

Si

to load the default values

no

t.AP

0.0" ÷ 2.0'

Gate opening time

22.5"

t.APP

0.0" ÷ t.AP1

Opening time of pedestrian gate

6.0"

t.Ch

0.0" ÷ 2.0'

Gate closing time

23.5"

t.ChP

0.0" ÷ t.Ch

Closing time of pedestrian gate

7.0"

t.PrE

0.5" ÷ 2.0'

Pre-flashing time

1.0"

no

- Pre-flashing disabled (it corresponds to 0)

dir

Gate direction (the direction you see from the inside)

dx

dx

- The gate opens rightwards

Sx

- The gate opens leftwards

Pot

30 ÷ 100%

Motor power

60

SPUn

no/Si

Start off

no

t.P.So

0.5" ÷ 3.0"

Slowed down starting time

1.5"

no

- Slowed down starting disabled

t.raL

0.5"÷22.5"

Slow down time

2.0"

no

- Slow down disabled

St.AP

Start in opening

PAUS

no

- Start command is not available

ChiU

- Command close gate

PAUS

- Stop the gate and goes in pause

St.Ch

Start in closing

StoP

Stop

- Start command stop the gate

APEr

- Start command open the gate

St.PA

Start in pause

ChiU

no

- Start command is not available

ChiU

- Start command closes the gate

SPAP

Pedestrian in opening

PAUS

no

- Pedestrian start command is not available

ChiU

- Pedestrian start command closes the gate

PAUS

- Gate goes in pause

Ch.AU 

Automatic closing 

no

no

- The gate closes after the setup time)

0.5"÷ 20.0'

- The automatic closing is not active (it corresponds to 0)

Ch.tr

Closing after passage

no

no

- Closing after passage disabled

0.5"÷ 20.0'

- Gate stop for a time to be set between 0.5" to 20'

LP.PA

no/Si

Flashlight in pause

no

Summary of Contents for GOLD230V-DM

Page 1: ...ettronica com COMPANY WITH QUALITY SYSTEM CERTIFIED BY QMSI UNI EN ISO9001 ATTUATORE ELETTROMECCANICO IRREVERSIBILE PER CANCELLI SCORREVOLI FINO A 600 KG DI PESO ELECTRO MECHANICAL IRREVERSIBLE ACTUAT...

Page 2: ...ISTRUZIONI 1 INSTRUCTIONS 23 NOTICES 45 INSTRUCCIONES 67 I GB F E...

Page 3: ...CRIZIONE DELLA CENTRALE 6 INSTALLAZIONE 6 ALIMENTAZIONE 6 MOTORE 6 LAMPEGGIATORE 6 FOTOCELLULE 6 COSTE SENSIBILI 7 FINE CORSA 7 STOP 8 INGRESSI DI ATTIVAZIONE 8 RICEVITORE AD INNESTO 8 ANTENNA 9 PANNE...

Page 4: ...icato in grado di rilasciare la dichiarazione di conformit di tipo A sull installazione completa Direttiva macchine 98 37 EEC allegato IIA E obbligo attenersi alle seguenti norme per chiusure veicolar...

Page 5: ...M e GOLD120V DM CARATTERISTICHE TECNICHE Peso massimo del cancello Alimentazione Potenza massima Assorbimento a vuoto Assorbimento a pieno carico Condensatore Velocit massima anta Spinta massima Ciclo...

Page 6: ...ra dovr essere fissata al suolo tramite due ancoraggi a tassello in corrispondenza dei fori predisposti A o annegando nel cemento le apposite alette B Fissare il motore sulla contropiastra tramite gli...

Page 7: ...el caso in cui il cancello superi il suo limite di corsa andando in battuta contro il fermo di arresto es errata regolazione dei finecorsa e sia necessario lo sblocco manuale prima di utilizzare la pr...

Page 8: ...ivo menu INSTALLAZIONE L installazione della centrale dei dispositivi di sicurezza e degli accessori deve essere eseguita con l alimentazione scollegata ALIMENTAZIONE La centrale deve essere alimentat...

Page 9: ...cancello la centrale fa richiudere il cancello per 3 secondi quindi va in blocco in caso di intervento delle coste di tipo 1 durante la chiusura del cancello la centrale va immediatamente in blocco I...

Page 10: ...Orologio analoga alla modalit standard ma il cancello rimane aperto completamente o parzialmente finanto che il contatto rimane chiuso sull ingresso quando il contatto viene aperto inizia il conteggi...

Page 11: ...cia pi in basso si accende quando il cancello in fase di chiusura Se lampeggia indica che la chiusura stata causata dall intervento di un dispositivo di sicurezza costa o rilevatore di ostacoli USO DE...

Page 12: ...guire inizialmente queste istruzioni per verificare velocemente il corretto funzionamento della centrale del motore e degli accessori e successivamente modificare la configurazione se qualche parametr...

Page 13: ...olo o se interviene il fine corsa Tempo di apertura parziale accesso pedonale Se viene ricevuto un comando di Start Pedonale la centrale apre il cancello per un tempo ridotto Il massimo tempo impostab...

Page 14: ...permette la regolazione della potenza del motore Il valore visualizzato rappresenta la percentuale rispetto alla massima potenza del motore Spunto Quando il cancello fermo e si appresta ad entrare in...

Page 15: ...prirsi il comando viene ignorato Per impostare la logica di funzionamento passo passo scegliere l opzione PAUS Per impostare la logica di funzionamento apre sempre scegliere l opzione no Start in chiu...

Page 16: ...viene disabilitata portando il valore a zero il display visualizza no il cancello pu essere richiuso solo con il comando di Start in questo caso l impostazione del menu St PA viene ignorata Se durante...

Page 17: ...i bloccarsi immediatamente Questo inconveniente si verifica quando si utilizza un motore scorrevole con frizione a disco su di un cancello molto pesante a causa dell inerzia il cancello non si blocca...

Page 18: ...do no la funzione test non attiva Si la funzione test attiva ATTENZIONE V2 ELETTRONICA consiglia di mantenere attivo il TEST delle fotocellule al fine di garantire una maggior sicurezza del sistema In...

Page 19: ...rrotta con un comando o per intervento della fotocellula il tempo impostato per la manovra opposta sarebbe eccessivo e perci la centrale aziona i motori solo per il tempo necessario a recuperare lo sp...

Page 20: ...a pressione del tasto Up o Down il valore attuale del contatore viene arrotondato alle migliaia ogni pressione successiva fa aumentare o diminuire l impostazione di 1000 unit Il conteggio precedenteme...

Page 21: ...e in caso di rilevamento di un ostacolo dipende dall impostazione del menu t rAL e dall istante in cui l ostacolo viene rilevato Rallentamento disabilitato Il motore quando viene rilevato un ostacolo...

Page 22: ...Partenza rallentata disabilitata t raL 0 5 22 5 Tempo di rallentamento 2 0 no Rallentamento disabilitato St AP Start in apertura PAUS no Il comando START non sentito ChiU Il cancello richiude PAUS Il...

Page 23: ...o fermo no Disabilitato Ch Funziona come fotocellula attiva solo in chiusura Ft tE no Si Test di funzionamento delle fotocellule no CoS1 no Si Ingresso costa 1 costa fissa no CoS2 no Si Ingresso costa...

Page 24: ...22 22 22...

Page 25: ...ON LAYOUT 27 DESCRIPTION OF THE CONTROL UNIT 28 INSTALLATION 28 POWER SUPPLY 28 MOTOR 28 BLINKER 28 PHOTOCELLS 28 SAFETY RIBBONS 29 END OF STROKE 29 STOP 30 ACTIVATION INPUTS 30 PLUG IN RECEIVER 30 EX...

Page 26: ...erning the whole installation Machine Directive 98 37 EEC Annex IIA The automated vehicular gates shall comply with the following rules EN 12453 EN 12445 EN 12978 as well as any local rule in force Al...

Page 27: ...0V DM and GOLD120V DM only TECHNICAL SPECIFICATIONS Gate maximum weight Power supply Maximum power Idling current Full load current Capacitor Gate maximum speed Maximum thrust Duty cicle Pinion Operat...

Page 28: ...counter plate shall be fixed to the ground by means of two anchors next to the already made holes A or sinking the special fins in the cement B Fix the motor on the counter plate by means of the cage...

Page 29: ...against the safety stroke end i e wrong regulation of the limit switches and a manual unclamp would be necessary before using the above procedure you have to replace the leaf setting away from the sa...

Page 30: ...this function from its relevant menu INSTALLATION Installation of control unit and safety devices must be carried out with power disconnected POWER SUPPLY The control unit must be fed by a 230V 50Hz 1...

Page 31: ...en it stands still when type 1 safety ribbons operate during the gate closing phase the control unit will stand still immediately Next Start or Pedestrian Start command will restore the gate motion to...

Page 32: ...s closed and it will immediately stop as the contact is open Timer mode it is similar to the standard mode but the gate stays open completely or partially while the contact is closed on input as soon...

Page 33: ...used by a safety device border or obstacle detector USE OF DOWN MENU AND UP KEYS FOR PROGRAMMING Control unit time and function programming is made within a special configuration menu to which you can...

Page 34: ...paragraph Control unit configuration for the item position inside the menu as well as for the available options for each item 1 Call up the default configuration item dEF 2 Set items StoP Fot1 Fot2 C...

Page 35: ...al opening time pedestrian access When the control unit receives a Start Pedestrian command it will open the gate only for a shorter time Max allowed time to be setup is t AP Closing time The motor wi...

Page 36: ...ng the motor power The displayed value is the percentage of max motor power Start off When the gate is standstill and it begins moving the initial inertia must be faced therefore if your gate is quite...

Page 37: ...The gate immediately starts closing no The gate go on with the opening phase command is ignored Select option PAUS to set up the step by step operation logic Select option no to set up the always ope...

Page 38: ...tic closing function is disabled by setting the value to zero no will be displayed the gate can be closed through the start command only in this case St PA menu setup will be ignored If the control un...

Page 39: ...ng a further movement This inconvenience happens when a sliding motor provided with single plate clutch is installed on a very heavy gate owing to inertia the gate does not stop immediately and it can...

Page 40: ...one second no the test function is not active Si the test function is active WARNING The PHOTOCELL OPERATIONAL TEST should be working in order to grant more safety during installation and programming...

Page 41: ...nabling the control unit to automatically find the best duration of the operation time See paragraph Quick Configuration When you select Go configuration menu closes and the learning cycle starts WARN...

Page 42: ...rounded down to the hundreds Area 3 is the setup of this latter counter if you press once UP or DOWN key the current counter value will be rounded up or down to thousands any following pressure will h...

Page 43: ...unit reaction in case an obstacle is detected depends on the t rAL menu setup and on the moment when such obstacle is detected Slowing down disabled The door motor on which an obstacle is detected wi...

Page 44: ...g disabled t raL 0 5 22 5 Slow down time 2 0 no Slow down disabled St AP Start in opening PAUS no Start command is not available ChiU Command close gate PAUS Stop the gate and goes in pause St Ch Star...

Page 45: ...still no Not available Ch Photocell is active during the closing Ft tE no Si Photocell operational test no CoS1 no Si Border 1 input fixed border no CoS2 no Si Border 2 input mobile border no FC En no...

Page 46: ...44 44 44...

Page 47: ...49 DESCRIPTION DE LA CENTRALE 50 INSTALLATION 50 ALIMENTATION 50 MOTEUR 50 CLIGNOTANT 50 PHOTOCELLULE 50 BARRES PALPEUSES 51 FIN COURSE 51 STOP 52 ENTREES DE ACTIVATION 52 RECEPTEUR EMBROCHABLE 52 ANT...

Page 48: ...et m caniques doit tre faite exclusivement par techniciens qualifi s en mesure de d livrer l attestation de conformit pour l installation Directive 98 37 EEC IIA Il est obligatoire se conformer aux n...

Page 49: ...0V DM et GOLD120V DM CARACT RISTIQUES TECHNIQUES Poids maximum du portail Alimentation Puissance maximum Absorption vide Absorption pleine charge Condensateur Vitesse maximum vantail Pouss e maximum C...

Page 50: ...r la contre plaque Une telle contre plaque devra tre fix e au sol par l interm diaire de deux ancrages cheville hauteur des trous am nag s l avance A ou en noyant dans le ciment les ailerons pr vus ce...

Page 51: ...tique pr vue cet effet ATTENTION Dans le cas que le portail va a en but es de fin de course ex mauvaise r gulation des fin course avant de d bloquer le moteur avec la proc dure sous d crite il faut de...

Page 52: ...es bornes relatives la securit pas install a suffit d s habiliter la fonction du menu relatif INSTALLATION L installation de l armoire des dispositifs de s curit et des accessoires doit tre faite avec...

Page 53: ...moire referme le portail pour 3 seconds et puis se bloque en cas d intervention des barres du type 1 pendant la fermeture du portail l armoire va se bloquer immediatement Le commande de Start ou Start...

Page 54: ...arr te immediatement si le contact viens ouvert Mode Horloge est similaire au mode standard mais le portail reste ouvert compl tement ou partiellement jusqu quand le contact reste ferm sur l entr e qu...

Page 55: ...bas s allume quand le portail est en phase de fermeture Si elle clignote cela indique que la fermeture a t caus e par l intervention d un dispositif de s ret barre palpeuse ou d tecteur d obstacles E...

Page 56: ...tement en ouvre On conseille de suivre du d but ces notices pour v rifier rapidement le correct fonctionnement de l armoire du moteur et des accessoires et apr s modifier la configuration si par hasar...

Page 57: ...l ouverture avant l puisement du temps Temps ouverture partielle acc s pi tonne S il re oit un commande de Start Pi tonne l armoire ouvre seulement le portail pour un temps r duit Le maximum du temps...

Page 58: ...ion de la puissance du moteur Le valeur visualis montre le pourcentage face la puissance maximum du moteur D marrage Quand le portail est ferme et commence bouger il est contrast par la force d inerti...

Page 59: ...ement se fermer no Le portail continue s ouvrir le commande est ignor Pour tablir la logique de fonctionnement pas pas choisir l option PAUS Pour tablir la logique de fonctionnement ouvre toujours cho...

Page 60: ...habilit en mettant le valeur z ro le display visualise no le portail peut tre re ferm seulement avec le commande de Start en ce cas le postage du menu St PA viens ignor Si pendant la pause il re oit...

Page 61: ...inconv nient peut se v rifier quand on utilise un moteur coulissant avec friction disque sur un portail tr s lourd cause de l inertie le portail ne se bloque pas imm diatement et son mouvement peut se...

Page 62: ...ns d une seconde no la fonction test n est pas activ e Si la fonction test est activ e IMPORTANT V2 ELETTRONICA conseille de maintenir active le text des photoc llules avec le but de garantir une s cu...

Page 63: ...cup rer l inertie Activation du capteur d obstacles Ce menu permet le r glage de la sensibilit du capteur d obstacles sur 10 niveaux de 1 10 Si la valeur 0 a t r gl e les capteurs sont d sactiv s en a...

Page 64: ...ompteurs la premiers pression du touche Up ou Down le valeur actuel du compteur viens arrondi au millier chaque pression apr s augmente ou diminue le postage de 1000 unit Le comptage pr c demment visu...

Page 65: ...portement de l armorie en cas de d tection obstacle d pend de l tablissement du menu t rAL et du moment que l obstacle est d tect Ralentissement des habilit Le moteur ou on a d tect l obstacle arr te...

Page 66: ...i d sactiv t raL 0 5 22 5 Temps de ralentissement 2 0 no Ralentissement d sactiv St AP D marrage en ouverture PAUS no Le command START n est pas capt e ChiU Le portail se referme PAUS Le portail se me...

Page 67: ...t no D sactiv Ch Fonctionne photocellule active uniquement en fermeture Ft tE no Si Test de fonctionnement des photocelluleIngresso costa 1 costa fissa no CoS1 no Si Entr e barre palpeuse 1 barre pal...

Page 68: ...66 66 66...

Page 69: ...DEL CUADRO 72 INSTALACION 72 ALIMENTACION 72 MOTOR 72 LAMPARA DE SE ALIZACION 72 FOTOCELULAS 72 BANDAS DE SEGURIDAD 73 FINALES DE CARRERA 73 STOP 74 ENTRADAS DE ACTIVACION DEL CUADRO 74 RECEPTOR ENCHU...

Page 70: ...de conformidad en la instalaci n Directiva m quinas 98 37 EEC anexo IIA Es obligatorio atenerse a las siguientes normas para cierres automatizados con paso de veh culos EN 12453 EN 12445 EN 12978 y a...

Page 71: ...LD230V DM CARACTERISTICAS TECNICAS Peso maximo de la puerta Alimentacion Potencia maxima Absorcion en vacio Absorcion con carga Condensador Velocidad maxima hoja Empuje maximo Ciclo de trabajo Pi on T...

Page 72: ...ca deber ser fijada al suelo con tacos mediante dos anclajes correspondiendo con los agujeros predispuestos A o anegando en el cemento las aletas expresas B Fijar el motor a la placa mediante las tuer...

Page 73: ...CUIDADO En el caso di que la puerta corredera toque con el tope de final de carrera ej pour una regulaci n erronea del final de carrera antes de desbloquear el motor con el procedimiento descrito ante...

Page 74: ...deshabilitar la funci n en el men correspondiente INSTALACION La instalaci n del cuadro de los dispositivos de seguridad y de los accesorios tiene que hacerse con la alimentaci n desconectada ALIMENT...

Page 75: ...vuelve a cerrar la puerta durante 3 segundos y se bloquea en caso de intervenci n de las bandas del tipo 1 durante el cierre de la puerta el cuadro se bloquea inmediatamente El siguiente comando de St...

Page 76: ...o se abre Modalidad Reloj es como la modalidad est ndar pero la puerta queda abierta completamente o parcialmente mientras que el contacto permanece cerrado en la entrada cuando el contacto se abre em...

Page 77: ...o para el cierre autom tico La flecha m s abajo se enciende cuando la puerta est en fase de cierre Si parpadea indica que el cierre ha sido causada por la intervenci n de un dispositivo de seguridad b...

Page 78: ...r pidamente el correcto funcionamiento del cuadro del motor y de los accesorios y posteriormente modificar la configuraci n si alg n par metro no satisface Para la posici n de la voces en el interior...

Page 79: ...tecta un obst culo o si interviene el final de carrera Tiempo de apertura parcial entrada peatonal Si se recibe un comando de Start Peatonal el cuadro abre la puerta por un tiempo reducido El tiempo m...

Page 80: ...de la potencia del motor El valor visualizado representa el porcentaje respecto la potencia m xima del motor Arranque Cuando la puerta est parada y tiene que entrar en movimiento se encuentra con el o...

Page 81: ...uerta continua a abrirse el comando no viene sentido Para programar la l gica de funcionamiento paso paso elegir la opci n PAUS Para programar la l gica de funcionamiento abre siempre elegir la opci n...

Page 82: ...ramando el valor cero el display visualiza no la puerta puede volver a cerrarse solo con el comando de Start en este caso la programaci n del men St PA no influye Si durante la pausa se recibe un coma...

Page 83: ...movimiento durante unos segundos en lugar de bloquearse inmediatamente Este inconveniente se manifiesta cuando se utiliza un motor de corredera con embrague mec nico o no en una puerta muy pesada deb...

Page 84: ...no est activava Si la funci n test est activada ATENCION V2 ELETTRONICA aconseja de mantener activo el TEST de las fotoc lulas para garantizar una major seguridad de todo el sistema Entrada Banda de S...

Page 85: ...r la intervenci n de la fotoc lula el tiempo programado para la siguiente maniobra en sentido contrario ser a excesivo y por eso el cuadro acciona los motores solo por el tiempo necesario para recuper...

Page 86: ...primera pulsaci n de la tecla Up o Down el valor actual del contador se redondea a los millares cada pulsaci n siguiente aumenta o disminuye la programaci n de 1000 unidades El contador anterior visu...

Page 87: ...mueven a velocidad reducida El comportamiento del cuadro en caso de detecci n de un obst culo depende de la programaci n del men t rAL y del momento en el que se detecta el obst culo Paro suave deshab...

Page 88: ...ue suave 1 5 no Arranque suave deshabilitado t raL 0 5 22 5 Tiempo de paro suave 2 0 no Paro suave deshabilitado St AP Start en apertura PAUS no El comando START no la admite ChiU La puerta se cierra...

Page 89: ...ctiva en cierre y con la puerta parada no Deshabilitada Ch Funciona como fotoc lula activa s lo en cierre Ft tE no Si Test de funcionamiento de las fotoc lulas no CoS1 no Si Entrada banda 1 banda fija...

Page 90: ...88 88 88...

Page 91: ......

Page 92: ...V2 ELETTRONICA SPA Corso Principi di Piemonte 63 12035 RACCONIGI CN ITALY tel 39 01 72 81 24 11 fax 39 01 72 84 050 info v2elettronica com www v2elettronica com...

Reviews: