VSL3.928.011VGASY

 

 

1

 

1. 

Feature 

 

Used as an warning device to generate fire alarm;   

 

Installation and wiring same as detector base;

 

 

 

Driven  by  detection  circuit,  no  need  for  extra  power 

line.Two adjustable modes, sharing the same address 

of detector, or occupying an individual address. 

2. 

Description

 

VG-6617S  Digital Alert  Base  is  designed  for  the  application  inside  a  closed  room. As  a  warning 

device, the base will generate alarm sound when the detector detects a fire occurred. Installed as a 

base, it is compatible with the range of digital detectors. For application, when sharing the same 

address  with  detector,  the  alert  base  will  be  triggered  by  that  detector  installed.  Setting  with  an 

individual address, the alert base can be as used a field warning device and activated by C&E Logic. 

It is usually installed in hotel room, residential bedroom or other locations that are far away from the 

audible and visual alarm.. 

3. 

Technical Data 

Operating voltage: 

Loop voltage: 24V /Allowance range: 15V~28V (Vp-p) 

Operating current: 

Standby current: ≤ 0.2mA 

Action current: ≤ 3mA 

Total starting current at alarm state both for the detector and 
alert base ≤ 3.5mA (maximum 20 pieces triggered at exactly 

the same time) 

Address 

1~254

 

Sound level 

>75dB 

Tonal modification cycle 

0.6~1.5S 

Temperature: 

-10

~+55

 

Relative humidity 

≤95%

non-condensing 

Weight 

67g 

Shell material and color 

ABS+PC, White 

Dimension 

diameter of 102mm, height of 25.5mm 

Installation hole distance 

73mm 

Wiring: directly connected with the detection loop of the control panel. 

VG-6617S Digital Alert Base

 

Base

 

 

 

Installation and Operation Manual V1.00

 

 