Phone (828)323-8914
Fax
(828)323-8410
Web
101 33
rd
Street Drive SE · Hickory, NC 28602
!
!
DANGER
Contact with high voltage will cause death or grievous personal
injury to the operator. Only use this device in conjunction with
safe operating practices around energized lines and equipment.
!
!
WARNING
Carefully read and fully understand the INSTRUCTION
MANUAL prior to operating, maintaining or testing this
device. Improper operation, handling or maintenance of this
device can result in death, grievous personal injury and or
equipment damage.
Jack Jumper™ Cutout Bypass Tool
!
!
WARNING
Follow safe work procedures and practices when utilizing this
device. Failure to use this device in a safe manner can result
in death, grievous personal injury and or equipment damage.
!
!
WARNING
These instructions are not intended to replace or be a substitute
for proper safety training procedures. Failure to select the
proper tool in regards to minimum system requirements can
result in death, grievous personal injury and or equipment
damage.
!
!
WARNING
Only trained and qualified personnel should operate, inspect
and maintain this device.
Product Description
The Jack Jumper™ Cutout Bypass Tool permits a safe and quick method to bypass an overhead
cutout without the tedious use of bulky jumper cables. The tool is indispensable for fuse
coordination tasks and permits easy bypass of an underground dip. The Jack Jumper™ Cutout
Bypass Tool saves time and money, eliminates risk of service interruption and prevents accidental
cross phasing.
The primary purpose of the Jack Jumper™ Cutout Bypass Tool is to provide temporary fuse
replacement when performing fuse coordination on cutouts. The Jack Jumper™ Cutout Bypass
Tool is rated at 100 Amps continuous on AC current without exceeding a 40°C temperature rise.
Installation and removal of the Jack Jumper™ Cutout Bypass Tool is done with a shotgun stick.
!
!
WARNING
Never install or remove Jack Jumper™ Cutout Bypass Tool
without a working fuse in place. It is not a switch and should
never be used as one.
!
!
WARNING
Only install the Jack Jumper™ Cutout Bypass Tool with the use
of an insulated shotgun stick. When attaching or detaching the
Jack Jumper™ Cutout Bypass Tool do not use abrupt or rough
movements, be gentle and do not hurry.
!
!
WARNING
If you are servicing a fuse, replace the fuse as quickly as possible.
The fuse is a protective device. The Jack Jumper™ Cutout Bypass
Tool DOES NOT FUNCTION AS A FUSE. If you must leave
the area, replace any fuses and remove the Jack Jumper™ Cutout
Bypass Tool. It is not a fuse replacement or permanent by-
pass mechanism.
C-00805 USJJ-004/009 Instruction Manual (6-4-15)
USJJ-004 15 kV Cutout Bypass Tool
USJJ-009 27 kV Cutout Bypass Tool
For use on ABB® Polymer & Porcelain Loadbreak Cutouts
Top Ring
Spring Mechanism
Bottom Ring
Upper
Attachment Hook
Lower
Attachment Hook