Coaxial Elbows - Equivalent length
4"/2" [100 mm/60 mm]
45°
1.64 ft. [0.5 m]
90°
3.28 ft. [1.0 m]
5” / 3” [128 mm/80 mm]
45°
1.64 ft. [0.5 m]
90°
3.28 ft. [1.0 m]
Coaxial Termination - Equivalent length 3 ft (0.9m)
NOTE:
Coaxial venting can run horizontal or vertical.
•
Connect flue elbow to top of boiler and adjust direction
of elbow to desired orientation (rear, right or left).
• Measure distance from outside wall face to elbow, this
dimension will be known as 'X", add distance "Y" + 2"
(60 mm) to "X" this is the total dimension of the vents.
See Figure 5-2.
• Mark dimension from above on outer aluminum intake
vent. Measure length of waste material, and transfer
dimension to inner grey flue pipe.
•
Remove waste from both vents (flue and air). Verify cut
ends are square and free from burrs. Insert flue back
into intake air vent and pass them through hole in wall.
• Check all measurements before cutting. Clearance to
combustible materials is zero when using coaxial vent
system.
• After installing venting use calibrated analyzer to verify
there is no recirculation of combustion.
• Ensure termination is positioned with slots at the
bottom.
WARNING
Asphyxiation hazard. Before securing the
screws ensure the pipe has been pushed in a
minimum of 1-3/4" (45 mm) into the gasket
end of the other pipe. Failure to follow these
instructions could result in death or serious
injury.
!
WT = Wall Thickness
FIGURE 5-2 - Coaxial Venting Horizontal or Vertical
CAN BE USED ON ALL SIZES
5 - COMBUSTION AIR AND VENT PIPING
5.6 Coaxial Venting Instructions
Maximum equivalent flue lengths for Coaxial venting
are:
Coaxial Pipe Vent Lengths
(
Includes First Elbow And Termination
)
Boiler
Size
100/115
125/150
165/205
ALL
Vent Size
4"/2"
[100mm/60mm]
5"/3"
[128mm/80mm]
ALL
Maximum
Minimum
Natalini
32.8 ft [10m]
32.8 ft [10m]
6 ft.
[1.8m]
DuraVent
27.88 ft [8.5m]
Centrotherm 24.60 ft [7.5m]
min. 7.09 in (180 mm)
min. 7.09 in (180 mm)
max. 13.78 in (350 mm)
max. 13.78 in (350 mm)
1.97 in (50 mm)
1.97 in (50 mm)
Note
: 2" is insertion depth of straight pipe to elbow.
240013371 REV B, [10/01/2021]
Summary of Contents for MACF-115
Page 2: ...MACF 150 ...
Page 4: ...MAHF 125 ...
Page 74: ...70 A 1 MODEL 100 Heat Only APPENDIX A WIRING DIAGRAMS 240013371 REV B 10 01 2021 ...
Page 75: ...71 A 2 MODEL 125 Heat Only APPENDIX A WIRING DIAGRAMS 240013371 REV B 10 01 2021 ...
Page 76: ...72 APPENDIX A WIRING DIAGRAMS A 3 MODEL 165 Heat Only 240013371 REV B 10 01 2021 ...
Page 77: ...73 APPENDIX A WIRING DIAGRAMS A 4 MODEL 115 Combi 240013371 REV B 10 01 2021 ...
Page 78: ...74 A 5 MODEL 150 Combi APPENDIX A WIRING DIAGRAMS 240013371 REV B 10 01 2021 ...
Page 79: ...75 A 6 MODEL 205 Combi APPENDIX A WIRING DIAGRAMS 240013371 REV B 10 01 2021 ...
Page 80: ...76 NOTES 240013371 REV B 10 01 2021 ...
Page 81: ...77 NOTES 240013371 REV B 10 01 2021 ...
Page 82: ...78 NOTES 240013371 REV B 10 01 2021 ...
Page 117: ...33 MODEL 100 Heat Only 100 HEAT ONLY WIRING DIAGRAM PN 240012875 REV C 10 01 2021 ...
Page 118: ...34 MODEL 125 Heat Only 125 HEAT ONLY WIRING DIAGRAM PN 240012875 REV C 10 01 2021 ...
Page 119: ...35 MODEL 165 Heat Only 165 HEAT ONLY WIRING DIAGRAM PN 240012875 REV C 10 01 2021 ...
Page 120: ...36 115 COMBI WIRING DIAGRAM MODEL 115 Comb PN 240012875 REV C 10 01 2021 ...
Page 121: ...37 MODEL 150 Combi 150 COMBI WIRING DIAGRAM PN 240012875 REV C 10 01 2021 ...
Page 122: ...38 MODEL 205 Combi 205 COMBI WIRING DIAGRAM PN 240012875 REV C 10 01 2021 ...
Page 127: ...43 LOW WATER CUTOFF DETAIL LOW WATER CUTOFF NO NO YES PN 240012875 REV C 10 01 2021 ...
Page 132: ...48 3 FAULT SOLUTION SECTIONS PN 240012875 REV C 10 01 2021 ...