Smart 1-Line
TM
Page 10
Though most of these gateways are standard “off-the-shelf” products that should work well, each
product is different and URC cannot guarantee the Smart 1-Line will work with all gateways.
Please contact URC with questions about external RS-485-to-Ethernet Gateways.
URC has used and tested the following products successfully with the Smart 1-Line:
•
Moxa MGate MB3180
•
Lantronix XPRESS DR
If using an external RS-485-to-Ethernet Modbus Gateway/Server, it must be configured with the
following settings:
•
Modbus TCP Exception should be Disabled
•
Response Timeout should be set to a shorter duration than the Smart 1-
Line “Trip Unit
Response Timeout” setting.
2.4.2
Modbus TCP communications to other systems
When the RS-485 network is wired directly to the Smart 1-Line, the Smart 1-Line can act as a
“Modbus server” to other systems (“clients”).
Requirements for using the Smart 1-
Line as a “Modbus server” to other systems:
•
“Other systems” must be capable of Modbus communications
•
“Other systems” must have drivers for AC-PRO-II and/or AC-PRO. A “driver” is simply
application programming that enables the system to correctly interpret the AC-PRO-II or
AC-PRO Register Map.
•
Smart 1-
Line “Modbus Server Settings” must be configured properly.
See Section 3 of this manual.
Ensure the included Power supply is connected to a reliable 120VAC source, and that the power
supply is also connected to the Panel PC.
Press the Power button to turn on the Smart 1-Line.
3.1.1
Logging into Windows
After Powering the Smart 1-Line, or after a screen timeout, you will be prompted for your Windows
Username and Password.
If logging into Windows for the first time, use the Smart 1-Line User account Username and
password provided by URC.
URC recommends changing the Smart 1-Line User account password. To change your
Smart 1-Line password, you must log into the Administrative account. See Section 7.
After logging in, the Smart 1-Line application will start automatically.
After the Smart 1-Line
application starts, click or tap the “Designer” button in the bottom right corner
to start creating your 1-Line in Designer Mode.
Figure 9: Designer Mode Button
3.0
Setup and Configuration
3.1
Powering On