Uponor Combi Port XS Installation And Operation Manual Download Page 6

3 System description

Combi Port XS is a prefabricated heat interface unit (HIU) suited for
use in single family houses. The ready-to-install unit supplies
domestic hot water, controls the domestic heating and measures the
heating energy as well as cold water consumption.

In the Combi Port XS unit, the cold water is heated only when
required following the flow-through principle with a stainless steel
high performance plate heat exchanger. This always ensures a low
return temperatures on the heating water. The energy is supplied by
heating water with a flow temperature of at least 55 °C via the heating
water flow.

Domestic hot water:

 The domestic hot water is generated only on

demand. A mechanical proportional quantity control valve is
controlling the process. As more hot water is required, as more the
valve is opening the flow of the heating water through the heat
exchanger. This ensures a constant hot water temperature. If no hot
water is needed, the valve stops the supply of hot water through the
heat exchanger. It can cool down which is beneficial for the hygiene.

Domestic heating:

 Combi Port XS manages independently the

hydraulic balancing between hot water and heating. The room
temperature control is carried out in the heating system.

3.1 Operating principle

SD0000105

WZ

FIL

3.2 Connection description

A

C

D

E

F

G

H

SD0000133

B

Item

Description

A

Cold water to apartment (CW)

B

Warm tap water with circulation (optional)

C

Cold water from riser (CW) (optional)

D

Domestic hot water to apartment (DHW)

E

Heating return (primary)

F

Heating supply (primary)

G

Heating return (secondary)

H

Heating supply (secondary)

 |  

Combi Port XS

  |  

Installation and operation manual

Summary of Contents for Combi Port XS

Page 1: ...Combi Port XS EN Installation and operation manual SD0000126...

Page 2: ...shing 9 5 5 Tightness testing 10 5 6 Commissioning and hand over 10 6 Operation 11 6 1 Cold water throttle disc 11 6 2 Strainer 11 6 3 Thermostatic temperature lead module TTV 11 6 4 Circulation pump...

Page 3: ...pecified by Uponor is not connected to or used with non Uponor products parts or components except for those approved or specified by Uponor and does not show evidence of tampering mishandling insuffi...

Page 4: ...flammable vapours or gases Uponor cannot accept any responsibility for damage or breakdown that can result from ignoring these instructions 2 2 Standards and regulations Note The installation must be...

Page 5: ...for details of where and how they can take this item for environmentally safe recycling Business users should contact their supplier and check the terms and conditions of the purchase contract This p...

Page 6: ...alve is controlling the process As more hot water is required as more the valve is opening the flow of the heating water through the heat exchanger This ensures a constant hot water temperature If no...

Page 7: ...essure regulator optional L Zone valve for limiting heating flow to apartment M Sensor pocket heat meter N Heat meter distance piece O Strainer 3 4 Accessories Depending on customer requirement the ba...

Page 8: ...ort or installation Check the nuts to ensure that they are properly tightened before the connection to avoid property damages Before installing the heat interface unit ensure that the primary pipes ar...

Page 9: ...entation SD0000106 Connect the primary supply lines with the corresponding ball valves at the HIU 5 3 Electrical installation Warning Required electrical connections and installations commissioning an...

Page 10: ...iately Minimum 2 hours According to local standards and regulations 5 6 Commissioning and hand over Caution Improper commissioning can lead to property damage Complete commissioning by following these...

Page 11: ...e capillary pipe 6 mm Note A too high value can cause the heating water return temperature to rise Note A too low maintenance temperature setting can lead to longer waiting times when preparing domest...

Page 12: ...70 C 35 40 45 50 55 60 65 70 Change default settings Caution Make sure not to bend or break the capillary line SI0000286 2 3 4 The thermostat is equipped with a pin that limits the temperature to 60 C...

Page 13: ...for assembly in the line and protects other control valves such as the proportional volume control from the excessive differential pressure that otherwise could cause the fitting to overflow Descript...

Page 14: ...are filled and pressurised The cold water supply for the apartment is provided via the central house connection and distribution line The heat interface unit is equipped with a central shut off ball v...

Page 15: ...iter infinitely adjustable downwards 35 70 C limited to 60 C 6 Scale value 35 70 C 1 2 3 4 5 6 7 8 Hot water temperature 35 C 40 C 45 C 50 C 55 C 60 C 65 C 70 C TTV Thermostatic lead module TTV capill...

Page 16: ...rmostatic hot water temperature limiter if installed is working and correctly set Proportional volume control does not switch over Replace the proportional volume controller Waiting time for hot water...

Page 17: ...rically Radiator thermostatic valves or return screw connections closed Check the thermostatic valves and return screw connections on the radiators No hot water and no heating Ball valves closed Open...

Page 18: ...495 mm 200 mm 501 mm 350 mm 198 mm Connection measurents w l l1 l2 l3 l4 l5 h1 ZD0000062 w2 w1 w3 h l l1 l2 l3 l4 l5 495 mm 303 mm 60 mm 94 mm 93 mm 95 mm w w1 w2 w3 h h1 501 mm 361 mm 401 mm 406 mm...

Page 19: ...tial pressure regulator M Cold water meter distance piece N Heat meter distance piece O Sensor pocket heat meter P Strainer Q Swivel nut R Ball valve 9 3 Technical specifications Combi Port XS Value M...

Page 20: ...differential pressure regulator kvs 1 46 H HIU without strainer kvs 1 70 Pressure losses including ball valve Additional pressure losses e g heatmeter with Qn 1 5 of approximately 0 05 bar and other...

Page 21: ...ture C X Primary heating supply temperatures Y Tapping capacity in litres minute l min Z Max range Cold water warming 40 K 10 50 C 55 50 45 40 35 30 25 20 15 10 5 10 15 20 25 W Y 1200 1100 1000 900 80...

Page 22: ...ng supply temperatures Y Tapping capacity in litres minute l min Z Max range Cold water warming 50 K 10 60 C 55 50 45 40 35 30 25 20 15 10 5 10 15 20 25 W X 1200 1100 1000 900 800 700 600 500 400 300...

Page 23: ...al pressure regulator kvs 1 46 H HIU without strainer kvs 1 70 Pressure losses including ball valve Additional pressure losses e g heatmeter with Qn 1 5 of approximately 0 05 bar and other internal ex...

Page 24: ...ture C X Primary heating supply temperatures Y Tapping capacity in litres minute l min Z Max range Cold water warming 40 K 10 50 C 40 35 30 25 20 15 10 5 0 5 10 15 20 25 W Y 1200 1100 1000 900 800 700...

Page 25: ...ng supply temperatures Y Tapping capacity in litres minute l min Z Max range Cold water warming 50 K 10 60 C 40 35 30 25 20 15 10 5 0 5 10 15 20 25 W Y 1200 1100 1000 900 800 700 600 500 400 300 200 1...

Page 26: ...al pressure regulator kvs 1 46 H HIU without strainer kvs 1 70 Pressure losses including ball valve Additional pressure losses e g heatmeter with Qn 1 5 of approximately 0 05 bar and other internal ex...

Page 27: ...X Primary heating supply temperatures Y Tapping capacity in litres minute l min Z Max range Cold water warming 40 K 10 50 C 40 35 30 25 20 15 10 5 0 5 10 15 20 25 W Y 1200 1100 1000 900 800 700 600 5...

Page 28: ...ng supply temperatures Y Tapping capacity in litres minute l min Z Max range Cold water warming 50 K 10 60 C 40 35 30 25 20 15 10 5 0 5 10 15 20 25 W Y 1200 1100 1000 900 800 700 600 500 400 300 200 1...

Page 29: ...ermany 1120090 v1_04_2021_EN Production Uponor DCO Uponor reserves the right to make changes without prior notification to the specification of incorporated components in line with its policy of conti...

Reviews: