8 Troubleshooting

8.1 Fault description

Fault description

Cause

Solution

Hot water function

Hot water temperature too low or
fluctuating

Central heating

Buffer temperature too low

Buffer temperature must be 

5-10 K

 above hot water setpoint

Heating circuit pump type not
supported

Check the central heating pump

Setting for heating circuit pump is
not correct

Heating circuit pump setting: Constant pressure

Pump performance too low

Check the pump performance

Mixing valve faulty

Check the mixing valve function

Setting for heating circuit control is
not correct

Check the heating circuit control setting

Heating circuit control faulty

Check the heating control function

Air trapped in buffer storage

Vent buffer storage tank

Cold water pressure too low / too
high

Cold water pressure at unit: 

Min. 2 bar, Max. 4 bar

Heat interface unit

Strainer in primary flow dirty

Clean the strainer in the primary flow

Insufficient differential pressure

Clean the capillary of the differential pressure control, check if differential
pressure control is working

Air in the system

Vent/flush the system

Insufficient heating volume flow
passes through the heat exchanger

Check the volume flow using heat meters

Heat meter type not supported

Use heat meter type with 

Qn 1,5

 ultrasound

Insufficient heating volume flow

Increase differential pressure

Heat exchanger dirty

Clean the heat exchanger

Thermostatic hot water temperature
limiter setting is not correct:

Check the thermostatic hot water temperature limiter (if installed) is
working and correctly set

Proportional volume control does
not switch over

Replace the proportional volume controller

Waiting time for hot water is too
long

Check the pump setting in the
central heating system

Pump setting: Constant pressure

The temperature setting on the
thermostatic lead module (TTV) is
too low

Increase the temperature setting on the thermostatic lead module (TTV)
or in the line

The capillary on the thermostatic
lead module (TTV) is dirty

Clean the capillary on the thermostatic lead module (TTV) or in the line

No thermostatic lead module (TTV)
available

Retrofit the thermostatic lead module (TTV) or line

Noise generation

Noise generated in the station

Pipe clamps too tight

Loosen the pipe clamps

Cold water throttle disc is dirty

Clean the cold water throttle disc

Noise generated in the PM valve

Noise generated via a third route

Replace the inductor disc, spring and locking ring using are placement kit
for PM valves, 3rd route

Heating function

Heating system does not heat up

General

Supply temperature too low at the
heat source

Check the supply temperature at the heat source

Volumetric flow rate is too low

Check the fittings in the device

Check the heat meter type

The heat meter type must be 

Qn 1,5

Air trapped in buffer storage

Vent the buffer storage tank

Insufficient differential pressure

Clean the capillary of the differential pressure control, check the
differential pressure control is working

Air in the system

Vent/flush the system

Radiator supply

Supply flow rate too low / too high

Check the zone valve setting

16 

 |  

Combi Port XS

  |  

Installation and operation manual

Summary of Contents for Combi Port XS

Page 1: ...Combi Port XS EN Installation and operation manual SD0000126...

Page 2: ...shing 9 5 5 Tightness testing 10 5 6 Commissioning and hand over 10 6 Operation 11 6 1 Cold water throttle disc 11 6 2 Strainer 11 6 3 Thermostatic temperature lead module TTV 11 6 4 Circulation pump...

Page 3: ...pecified by Uponor is not connected to or used with non Uponor products parts or components except for those approved or specified by Uponor and does not show evidence of tampering mishandling insuffi...

Page 4: ...flammable vapours or gases Uponor cannot accept any responsibility for damage or breakdown that can result from ignoring these instructions 2 2 Standards and regulations Note The installation must be...

Page 5: ...for details of where and how they can take this item for environmentally safe recycling Business users should contact their supplier and check the terms and conditions of the purchase contract This p...

Page 6: ...alve is controlling the process As more hot water is required as more the valve is opening the flow of the heating water through the heat exchanger This ensures a constant hot water temperature If no...

Page 7: ...essure regulator optional L Zone valve for limiting heating flow to apartment M Sensor pocket heat meter N Heat meter distance piece O Strainer 3 4 Accessories Depending on customer requirement the ba...

Page 8: ...ort or installation Check the nuts to ensure that they are properly tightened before the connection to avoid property damages Before installing the heat interface unit ensure that the primary pipes ar...

Page 9: ...entation SD0000106 Connect the primary supply lines with the corresponding ball valves at the HIU 5 3 Electrical installation Warning Required electrical connections and installations commissioning an...

Page 10: ...iately Minimum 2 hours According to local standards and regulations 5 6 Commissioning and hand over Caution Improper commissioning can lead to property damage Complete commissioning by following these...

Page 11: ...e capillary pipe 6 mm Note A too high value can cause the heating water return temperature to rise Note A too low maintenance temperature setting can lead to longer waiting times when preparing domest...

Page 12: ...70 C 35 40 45 50 55 60 65 70 Change default settings Caution Make sure not to bend or break the capillary line SI0000286 2 3 4 The thermostat is equipped with a pin that limits the temperature to 60 C...

Page 13: ...for assembly in the line and protects other control valves such as the proportional volume control from the excessive differential pressure that otherwise could cause the fitting to overflow Descript...

Page 14: ...are filled and pressurised The cold water supply for the apartment is provided via the central house connection and distribution line The heat interface unit is equipped with a central shut off ball v...

Page 15: ...iter infinitely adjustable downwards 35 70 C limited to 60 C 6 Scale value 35 70 C 1 2 3 4 5 6 7 8 Hot water temperature 35 C 40 C 45 C 50 C 55 C 60 C 65 C 70 C TTV Thermostatic lead module TTV capill...

Page 16: ...rmostatic hot water temperature limiter if installed is working and correctly set Proportional volume control does not switch over Replace the proportional volume controller Waiting time for hot water...

Page 17: ...rically Radiator thermostatic valves or return screw connections closed Check the thermostatic valves and return screw connections on the radiators No hot water and no heating Ball valves closed Open...

Page 18: ...495 mm 200 mm 501 mm 350 mm 198 mm Connection measurents w l l1 l2 l3 l4 l5 h1 ZD0000062 w2 w1 w3 h l l1 l2 l3 l4 l5 495 mm 303 mm 60 mm 94 mm 93 mm 95 mm w w1 w2 w3 h h1 501 mm 361 mm 401 mm 406 mm...

Page 19: ...tial pressure regulator M Cold water meter distance piece N Heat meter distance piece O Sensor pocket heat meter P Strainer Q Swivel nut R Ball valve 9 3 Technical specifications Combi Port XS Value M...

Page 20: ...differential pressure regulator kvs 1 46 H HIU without strainer kvs 1 70 Pressure losses including ball valve Additional pressure losses e g heatmeter with Qn 1 5 of approximately 0 05 bar and other...

Page 21: ...ture C X Primary heating supply temperatures Y Tapping capacity in litres minute l min Z Max range Cold water warming 40 K 10 50 C 55 50 45 40 35 30 25 20 15 10 5 10 15 20 25 W Y 1200 1100 1000 900 80...

Page 22: ...ng supply temperatures Y Tapping capacity in litres minute l min Z Max range Cold water warming 50 K 10 60 C 55 50 45 40 35 30 25 20 15 10 5 10 15 20 25 W X 1200 1100 1000 900 800 700 600 500 400 300...

Page 23: ...al pressure regulator kvs 1 46 H HIU without strainer kvs 1 70 Pressure losses including ball valve Additional pressure losses e g heatmeter with Qn 1 5 of approximately 0 05 bar and other internal ex...

Page 24: ...ture C X Primary heating supply temperatures Y Tapping capacity in litres minute l min Z Max range Cold water warming 40 K 10 50 C 40 35 30 25 20 15 10 5 0 5 10 15 20 25 W Y 1200 1100 1000 900 800 700...

Page 25: ...ng supply temperatures Y Tapping capacity in litres minute l min Z Max range Cold water warming 50 K 10 60 C 40 35 30 25 20 15 10 5 0 5 10 15 20 25 W Y 1200 1100 1000 900 800 700 600 500 400 300 200 1...

Page 26: ...al pressure regulator kvs 1 46 H HIU without strainer kvs 1 70 Pressure losses including ball valve Additional pressure losses e g heatmeter with Qn 1 5 of approximately 0 05 bar and other internal ex...

Page 27: ...X Primary heating supply temperatures Y Tapping capacity in litres minute l min Z Max range Cold water warming 40 K 10 50 C 40 35 30 25 20 15 10 5 0 5 10 15 20 25 W Y 1200 1100 1000 900 800 700 600 5...

Page 28: ...ng supply temperatures Y Tapping capacity in litres minute l min Z Max range Cold water warming 50 K 10 60 C 40 35 30 25 20 15 10 5 0 5 10 15 20 25 W Y 1200 1100 1000 900 800 700 600 500 400 300 200 1...

Page 29: ...ermany 1120090 v1_04_2021_EN Production Uponor DCO Uponor reserves the right to make changes without prior notification to the specification of incorporated components in line with its policy of conti...

Reviews: