II. Panel and signal indicators

      

There are 11 indicator lights on the front panel of UT-1208H, 

and on the back panel there are 1 5-pin terminal for RS-485 or 
RS-232 input and 8 ports 3-pin terminals for photo electrical 
isolation input ports.

II. Parameters

1. Interface features: compatible with RS-232C and RS-485 
                                      standards of EIA/TIA.
2. Electric interface: RS-232C interface for the 1st -3rd pins 
                                     of the 5-PIN terminals, and RS-485 interface 
                                     for the 4th  5th pins of the 5-PIN terminals.
3. Transmission media: twisted-pair cable or shielded cable.
4. Working mode: asynchronous half-duplex. 
5. Signal indication: 12 signal indicator including power (PWR), 
                                     send(TXD), receive(RXD) and failure(E1-E8).
6. Isolation degree: a isolation voltage of 2,500V RMS 500VDC 
                                   non-stop and DC/DC isolation module.
7. Transmission rate: 300BPS-115.2K.
8. Protection grade: RS-232 interface 15KV ESD protection, 
                                   RS-485 interface 1,500W lighting strike surge 
                                   protection for each line.
9. Transmission distance: 0-5km (115,200-300BPS)
10.Measurements: 210mmX130mmX33mm
11.Working environment: -40

to 80

 relative humidity 5% to 95%.

Figure 1. Front Panel of UT-1208H

Figure 1. Back Panel of UT-1208H

1

2

3

With a double-core and non-stop inside design

UT-1208H is 

a RS-485 bus splitting hub specially designed to meet the requirements 

of RS-485 under sophisticated electromagnetic field environment. 

A transmission rate as high as 115.2 KBPS is supported by this 

product. What's more

 photoelectrical isolation technology is 

adopted for RS-485 interface to avoid induction of lighting or surge 

into the converter and equipments to make sure the safety and 

reliability of signal transmission. The built-inphotoelectrical 

isolator and the 1,500W surge protection circuit can provide a 

high isolation voltage of  2,500V for an efficient restriction of 

lighting and ESD, and  at the same time, lighting strike and 

grounding interference can be reduced to the least extent. This 

product is suitable for outdoors engineering with adoption of 

outside switch power supply.

Under RS-485 mode

the determination circuit adopted can 

determine the direct ion of the data stream and switch the control 

circuit on a automatic basis for an very easy solution of the long-

existed transmission delay of RS-485. The transmission distance

is as far as 1,200 meters with a very stable performance. This 

product is widely used in express way toll system road monitoring 

system and electricity monitoring system with nice performance 

and competitive price.

RS-485 star topology bus connection is provided by UT-1208H 

RS-485 HUB. Short circuit and open circuit is provided for all 

the terminals. Photo electrical isolation of 2,500V is provided. 

Re-constru ction of RS-485 bus structure and network range 

splitting can be easily realized to improve communication reliability. 

In the case of lighting strike or equipment failure  the affected 

range shall be isolated to make sure the normal function of other 

ranges. This feature can increase greatly the reliability of existing 

RS-485 with achievement of shorter time for network maintenance. 

Proper application of UT-1208H RS-485 HUB can help you with 

a nice design of RS-48 system of high stability.

UT-1208H 8-PORT RS-485 HUB

USER MANUAL

I. Summary

IV. Electric interfaces and definitions:

RS-232C/RS-485 definition

TXD 

RXD 

SGND

5

485+ 

485-

2

3

1

4

485+  485- SGND

2 3

1

Interpretation of front panel indicators:

PWR--Power, green for power on.
TXD--Data sending indication, green for normal 
            transmission from INPUT port to OUTPUT ports 1-8. 
RXD--Data receiving indication, yellow for normal 
             transmission from OUTPUT ports 1-8 to INPUT port.
E1-E8--Failure alarm indicators for ports 1-8, the lights           
              stay ON to indicate short circuit or wrong signal             
              connection of ports 1-8. E1 is for port 1, E2 for port             
              2, and so on. Problems can be determined by the user 
              according to different light indicators.

Fig 3. RS-232C/RS-485 input interface

Fig 4. RS-485 output interface

1.RS-232C/RS-485 input interface definition

2.RS-485 output interface definition

5-PIN Terminal Interface

1

2

3

RS-485

485+

485-

GND

5-PIN Terminal Interface

1

2

3

4

5

Signal Direction

OUT

IN

Definition

TXD

RXD

SGND

485+

485-

MODEL:UT-1208H

8-PORT RS-485 ISOLATED HUB

PWR1

TXD

RXD

E7

E5

E3

E2

E8

E6

E4

E1

DC9-48V

T

/R

8

+

T

/R

8

G

N

D

T

/R

7

+

T

/R

7

G

N

D

T

/R

6

+

T

/R

6

G

N

D

T

/R

5

+

T

/R

5

G

N

D

T

/R

4

+

T

/R

4

G

N

D

T

/R

3

+

T

/R

3

G

N

D

T

/R

2

+

T

/R

2

G

N

D

T

/R

1

+

T

/R

1

G

N

D

RS-485 PORT

RS-232/485

T

X

D

R

X

D

S

G

N

D

4

8

5

+

4

8

5

PWR2

Reviews: