Steel Body, Automatic Wood Pellet Feed Hot Water Boiler Operation and Maintenance
Manual
INSTALLATION LOCATION SELECTION
Installation
The space in which the boiler is installed must have sufficient space for the installation, combustion
and maintenance of the boiler. For service requirements, the gear unit and the burner group to which
the shaft is connected should be at a sufficient distance from the wall. For this purpose, the dimensions
in the paragraph entitled “Mounting place dimensions” must be applied.
In addition, there must be sufficient fresh air circulation for efficient combustion, the chimney design
must meet the required traction values for the model used and comply with the construction criteria
and relevant regulations given in the manual. The boiler should never be installed in open spaces,
balconies, living areas (kitchen, living room, bathroom, bedroom), or in areas with explosive and easily
flammable materials.
The boiler room door must not be opened directly to the escape staircase or general use staircase and
must be opened to a safety hall.
Doors opening from the boiler room into the building should have a threshold of at least 10 cm in
height. If it is possible to illuminate the boiler room naturally, it should be ensured that the lighting
openings do not coincide with the other windows of the building. If artificial lighting is provided, a
system should be installed that does not dazzle but illuminates the apartment thoroughly. The main
switch and panels of the boiler room shall be placed around the entrance door and shall be sealed
type. Fire tube should be available in boiler rooms.
There must be at least one 6 kg multi-purpose dry chemical powder fire extinguishing device in the
boiler room. If natural gas or liquid fuel boilers are used in the same boiler room, tear surface must be
designed.
The space must be directly connected to the outdoor environment and must have vents that allow the
entry of fresh air. One of the grills should be at most 40 cm below the ceiling of the boiler room and
the other 50 cm above the floor. These grilles should be open at all times. The lower orifice should be
at least 40 x 40 cm and the upper orifice should be at least 30 x 30 cm. Pets should not be fed in the
central heating area (boiler room), and smoke and food and beverages that may be affected should
not be stored.
All electrical and water installations must be installed by authorized installers approved by the relevant
legal authorities and in accordance with all applicable legal and technical rules.
Fuels to be burned in the boiler should be kept at a distance of at least 800 mm from the boiler. It is
recommended to store fuels in a separate room.
Boilers should be installed on a concrete base at a height of 10 cm from the base to protect the water
from moisture and fuel from ash dust. The concrete base prevents the fan from absorbing fuel or ash
dust on the ground.