background image

 

Unitronics 

 

 

Vision

™PLC+HMI 

Installation Guide 

V130-33-T2/V130-J-T2 
V350-35-T2/V350-J-T2 
V430-J-T2 

 

12 Digital Inputs, including 2 Analog,  
3 HSC/Shaft-encoder inputs 

 

 

12 Transistor Outputs

 

 

 

General Description 

 

All of the controllers covered in this guide are micro-PLC+HMIs, rugged programmable logic controllers 
that comprise built-in operating panels and on-board I/Os. 

 

Item 

V130-T2 

V130J-T2 

V350-T2 

V350J-T2 

   V430J-T2 

On-board I/O 

Model Dependent 

Screen 

2.4" 

3.5" Color Touch 

4.3" Color Touch 

Keypad 

Yes 

None 

Function Keys 

None 

Yes 

Com Port, Built-in 

 

 

RS232/485 

Yes 

Yes 

Yes* 

Yes* 

Yes* 

USB device,  

mini-B 

None 

None 

Yes* 

Yes* 

Yes* 

Com Ports, separate 
order, user-installed  

The user may install a CANbus port (V100-17-CAN), and 

one

 of the following: 

 

RS232/RS485 port (V100-17-RS4/V100-17-RS4X)  

 

Ethernet (V100-17-ET2)

 

 

 

Profibus Slave (V100-17-PB1) 

* V430J/V350/V350J comprises both RS232/485 and USB ports; note that only 

one

 channel may be used at a time. 

 

Standard Kit Contents 

 

Item 

V130-T2 

V130J-T2 

V350-T2 

V350J-T2 

V430J-T2 

 

Controller 

Yes 

Terminal Blocks 

Yes 

Battery (installed) 

Yes 

Slides  
(2 sets of key labels) 

None 

Yes 

None 

Mounting Brackets 

Yes (2 parts) 

Yes (4 parts) 

Rubber Seal 

Yes 

 

Summary of Contents for Vision V130-33-T2

Page 1: ... Color Touch Keypad Yes None Function Keys None Yes Com Port Built in RS232 485 Yes Yes Yes Yes Yes USB device mini B None None Yes Yes Yes Com Ports separate order user installed The user may install a CANbus port V100 17 CAN and one of the following RS232 RS485 port V100 17 RS4 V100 17 RS4X Ethernet V100 17 ET2 Profibus Slave V100 17 PB1 V430J V350 V350J comprises both RS232 485 and USB ports no...

Page 2: ...epairs Failure to comply with appropriate safety guidelines can cause severe injury or property damage Do not attempt to use this device with parameters that exceed permissible levels To avoid damaging the system do not connect disconnect the device when power is on Environmental Considerations Do not install in areas with excessive or conductive dust corrosive or flammable gas moisture or rain ex...

Page 3: ...V130J V350J 92x92 mm 3 622 x3 622 V430J 122 5x91 5 mm 4 82 x3 6 2 Slide the controller into the cut out ensuring that the rubber seal is in place 3 Push the mounting brackets into their slots on the sides of the panel as shown in the figure below 4 Tighten the bracket s screws against the panel Hold the bracket securely against the unit while tightening the screw 5 When properly mounted the contro...

Page 4: ...tronics V430J DIN rail Mounting V130 V350 V130J V350J 1 Snap the controller onto the DIN rail as shown in the figure to the right 2 When properly mounted the controller is squarely situated on the DIN rail as shown in the figure to the right ...

Page 5: ...n 4 Tighten enough to keep the wire from pulling free Input or output cables should not be run through the same multi core cable or share the same wire Allow for voltage drop and noise interference with I O lines used over an extended distance Use wire that is properly sized for the load The controller and I O signals must be connected to the same 0V signal I Os V130 V350 V130J V350J V430J T2 mode...

Page 6: ...nning on page 11 Incompatible jumper settings and wiring connections may seriously damage the controller Do not move JP2 Digital Inputs 0 11 Set Type Set to JP1 all Inputs npn sink A pnp source B Inputs 10 11 Set as Digital or Analog Set to JP5 Input 10 JP6 Input 11 Digital A A Analog B B Analog Inputs AN0 AN1 Set Type Set to JP3 AN0 JP4 AN1 Voltage A A Current B B Default settings I O Wiring npn ...

Page 7: ...ring HSC input wiring Shaft encoder Analog Input Analog input wiring current 2 3 wire Analog input wiring current 4 wire Voltage Shields should be connected at the signal s source The 0V signal of the analog input must be connected to the controller s 0V ...

Page 8: ...reaker Guard against short circuiting in external wiring Double check all wiring before turning on the power supply Do not connect either the Neutral or Line signal of the 110 220VAC to device s 0V pin In the event of voltage fluctuations or non conformity to voltage power supply specifications connect the device to a regulated power supply Earthing the PLC HMI To maximize system performance avoid...

Page 9: ...te with serial devices and applications such as SCADA Use RS485 to create a multi drop network containing up to 32 devices Pinouts The pinouts below show the PLC port signals RS232 RS485 Controller Port Pin Description Pin Description Pin 1 1 DTR signal 1 A signal 2 0V reference 2 RS232 signal 3 TXD signal 3 RS232 signal 4 RXD signal 4 RS232 signal 5 0V reference 5 RS232 signal 6 DSR signal 6 B si...

Page 10: ...d unit in an RS485 network USB Port Caution The USB port is not isolated Make sure that the PC and the controller are grounded to same potential The USB port may be used for programming OS download and PC access Setting RS232 RS485 Communication Parameters V130 V350 V130J V350J This port may be set to either RS232 or RS485 via jumper The accompanying figure shows the jumper factory default setting...

Page 11: ...ge the jumper settings according to the table shown above Changing Communication Settings V130 V350 V130J V350J Only 1 To access the communication jumpers hold the I O PCB board by its top and bottom connectors and steadily pull the board off 2 Locate the jumpers and then change the settings as required according to the jumpers settings shown on page 10 Closing the Controller 1 Gently replace the ...

Page 12: ...t not limited to any implied warranties of merchantability fitness for a particular purpose or non infringement Unitronics assumes no responsibility for errors or omissions in the information presented in this document In no event shall Unitronics be liable for any special incidental indirect or consequential damages of any kind or any damages whatsoever arising out of or in connection with the us...

Reviews: