22 Digital Inputs, including 3 HSC/Shaft-encoder Inputs, 
2 Analog inputs 

 

 

8 Relay Outputs

 

 

4 high-speed npn Transistor Outputs

 

V130-33-R34/V130-J-R34 
V350-35-R34/V350-J-R34 
V430-J-R34

 

 

22 Digital Inputs, including 3 HSC/Shaft-encoder Inputs,  
2 Analog Inputs

 

 

12 Relay Outputs 

 

  

General Description 

All of the controllers covered in this guide are micro-PLC+HMIs, rugged programmable logic controllers 
that comprise built-in operating panels and on-board I/Os. 

 

Item 

V130-TR34 

V130J-TR34 

V130-R34 

V130J-R34 

V350-TR34 

V350J-TR34 

V350-R34 

V350J-R34 

V430J-TR34 

V430J-R34 

On-board I/O 

Model Dependent 

Screen 

2.4" 

3.5" Color Touch 

4.3" Color 

Touch 

Keypad 

Yes 

None 

Function Keys 

None 

Yes 

Com Port, Built-in 

 

 

RS232/485 

Yes 

Yes 

Yes* 

Yes* 

Yes* 

USB device, mini-B 

None 

None 

Yes* 

Com Ports, separate 
order, user-installed  

The user may install a CANbus port (V100-17-CAN), and 

one

 of the following: 

 

RS232/RS485 port (V100-17-RS4/V100-17-RS4X)  

 

Ethernet (V100-17-ET2)

 

 

 

Profibus Slave (V100-17-PB1) 

* V430J/V350/V350J comprises both RS232/485 and USB ports; note that only 

one

 channel may be 

used at a time. 

 

Standard Kit Contents 

 

Item 

V130-TR34 

V130J-TR34 

V130-R34 

V130J-R34 

V350-TR34 

V350J-TR34 

V350-R34 

V350J-R34 

V430J-TR34 

V430J-R34 

Controller 

Yes 

Terminal Blocks 

Yes 

Battery (installed) 

Yes 

Slides  
(2 sets of key labels) 

None 

Yes 

None 

Mounting Brackets 

Yes (2 parts) 

Yes (4 parts) 

Rubber Seal 

Yes 

   

   

   

   

   

   

   

   

   

   

   

   

   

   

Summary of Contents for Vision V130-33-R34

Page 1: ... V350 R34 V350J R34 V430J TR34 V430J R34 On board I O Model Dependent Screen 2 4 3 5 Color Touch 4 3 Color Touch Keypad Yes None Function Keys None Yes Com Port Built in RS232 485 Yes Yes Yes Yes Yes USB device mini B None None Yes Com Ports separate order user installed The user may install a CANbus port V100 17 CAN and one of the following RS232 RS485 port V100 17 RS4 V100 17 RS4X Ethernet V100 ...

Page 2: ...lations Only qualified service personnel should open this device or carry out repairs Failure to comply with appropriate safety guidelines can cause severe injury or property damage Do not attempt to use this device with parameters that exceed permissible levels To avoid damaging the system do not connect disconnect the device when power is on Environmental Considerations Do not install in areas w...

Page 3: ...ision PLC HMI Unitronics 3 Mounting Note that figures are for illustrative purposes only Dimensions V130 V350 V130J V350J Note that for models V130J V350J the bezel width is 6 7 mm 0 26 Dimensions V430J ...

Page 4: ...30J V350J 92x92 mm 3 622 x3 622 V430J 122 5x91 5 mm 4 82 x3 6 2 Slide the controller into the cut out ensuring that the rubber seal is in place 3 Push the mounting brackets into their slots on the sides of the panel as shown in the figure below 4 Tighten the bracket s screws against the panel Hold the bracket securely against the unit while tightening the screw 5 When properly mounted the controll...

Page 5: ...0 5 N m 5 kgf cm Do not use tin solder or any substance on stripped wire that might cause the wire strand to break Install at maximum distance from high voltage cables and power equipment Wiring Procedure Use crimp terminals for wiring use 3 31 mm 0 13 mm wire 12 16 AWG 1 Strip the wire to a length of 7 0 5mm 0 270 0 300 2 Unscrew the terminal to its widest position before inserting a wire 3 Inser...

Page 6: ... as normal digital inputs Inputs 1 3 and 5 can function as either counter reset as part of a shaft encoder or as normal digital inputs If inputs 0 2 and 4 are set as high speed counters without reset inputs 1 3 and 5 can function as normal digital inputs Input Jumper Settings The tables below show how to set a specific jumper to change input functionality To access the I O jumpers you must open th...

Page 7: ...Vision PLC HMI Unitronics 7 I O Wiring npn sink Input Wiring Input wiring HSC input wiring pnp source Input Wiring Input wiring HSC input wiring Shaft encoder ...

Page 8: ...log input wiring current 2 wire Analog input wiring current 3 wire Analog input wiring current 4 wire Analog input wiring voltage Shields should be connected at the signal s source The 0V signal of the analog input must be connected to the controller s 0V npn Outputs TR34 ...

Page 9: ... functional earth line pin 3 and the 0V line pin 2 to the system earth ground Install an external circuit breaker Guard against short circuiting in external wiring Double check all wiring before turning on the power supply Do not connect either the Neutral or Line signal of the 110 220VAC to device s 0V pin In the event of voltage fluctuations or non conformity to voltage power supply specificatio...

Page 10: ... communicate with serial devices and applications such as SCADA Use RS485 to create a multi drop network containing up to 32 devices Pinouts The pinouts below show the PLC port signals RS232 RS485 Controller Port Pin Description Pin Description Pin 1 1 DTR signal 1 A signal 2 0V reference 2 RS232 signal 3 TXD signal 3 RS232 signal 4 RXD signal 4 RS232 signal 5 0V reference 5 RS232 signal 6 DSR sig...

Page 11: ... the instructions on page 12 Setting RS232 RS485 Communication Parameters V430J This port may be set to either RS232 or RS485 via DIP switches The table shows the DIP switches factory default settings Use the table to adapt the settings Switch Settings 1 2 3 4 5 6 RS232 ON OFF OFF ON OFF OFF RS485 OFF ON ON OFF OFF OFF RS485 with termination OFF ON ON OFF ON ON Default factory setting Causes the u...

Page 12: ...e controller and fasten the corner screws Note that you must replace the back cover securely before powering up the controller The information in this document reflects products at the date of printing Unitronics reserves the right subject to all applicable laws at any time at its sole discretion and without notice to discontinue or change the features designs materials and other specifications of...

Reviews: