background image

Unitronics  

1

Vision™ OPLC™ 

Installation Guide 
V560-T25B 

This guide provides basic information for Unitronics’ controllers V560-T25B.   

General Description 

V560 OPLCs are programmable logic controllers that comprise a built-in operating panel containing a 
5.7” Color Touchscreen. The V560 offers an alpha-numeric keypad with function keys as well as a 
virtual keyboard. Either may be used when the application requires the operator to enter data. 

Communications 

2 isolated RS232/RS485 ports 
Isolated CANbus port 
The user can order and install an Ethernet port 
Communication Function Blocks include: SMS, GPRS, MODBUS 
serial/IP Protocol FB enables PLC to communicate with almost any 
external device, via serial or Ethernet communications 

I/O Options 

V560 supports digital, high-speed, 
analog, weight and temperature 
measurement I/Os via: 

Snap-in I/O Modules
Plug into the back of the 
controller to provide an on-
board I/O configuration 
I/O Expansion Modules
Local or remote I/Os may be 
added via expansion port or 
CANbus. 

Installation instructions and other data may be found in the module’s technical 
specification sheet. 

Information Mode 

This mode enables you to: 

Calibrate the touchscreen 
View & Edit operand values, COM port settings, RTC and screen 
contrast/brightness settings 
Stop, initialize, and reset the PLC 

To enter Information Mode, press the <i> button, or press the touchscreen and 
maintain contact for several seconds. 

Programming 
Software,  
& Utilities 

The Unitronics Setup CD contains VisiLogic software and other utilities 

VisiLogic
Easily configure hardware and write both HMI and Ladder control 
applications; the Function Block library simplifies complex tasks 
such as PID. Write your application, and then download it to the 
controller via the programming cable included in the kit. 
Utilities
These include UniOPC server, Remote Access for remote 
programming and diagnostics, and DataXport for run-time data 
logging. 

To learn how to use and program the controller, as well as use utilities such as 
Remote Access, refer to the VisiLogic Help system. 

Summary of Contents for Vision OPLC V560-T25B

Page 1: ...ation I O Expansion Modules Local or remote I Os may be added via expansion port or CANbus Installation instructions and other data may be found in the module s technical specification sheet Information Mode This mode enables you to Calibrate the touchscreen View Edit operand values COM port settings RTC and screen contrast brightness settings Stop initialize and reset the PLC To enter Information...

Page 2: ...on Use caution Before using this product the user must read and understand this document All examples and diagrams are intended to aid understanding and do not guarantee operation Unitronics accepts no responsibility for actual use of this product based on these examples Please dispose of this product according to local and national standards and regulations Only qualified service personnel should...

Page 3: ...cover on the rear of the controller 1 Remove the battery cover shown on page 4 The polarity is marked on the battery holder and on the battery 2 Insert the battery ensuring that the polarity symbol on the battery is facing up aligned with the symbol on the holder 3 Replace the battery cover Mounting Dimensions Note that the LCD screen may have a single pixel that is permanently either black or whi...

Page 4: ... the right 2 Slide the controller into the cut out ensuring that the rubber seal is in place 3 Push the 4 mounting brackets into their slots on the sides of the controller as shown in the figure to the right 4 Tighten the bracket screws against the panel Hold the bracket securely against the unit while tightening the screw 5 When properly mounted the controller is squarely situated in the panel cu...

Page 5: ...etely into the terminal to ensure a proper connection 4 Tighten enough to keep the wire from pulling free Power Supply The controller requires either an external 12 or 24VDC power supply Permissible input voltage range 10 2 28 8VDC with less than 10 ripple The power supply must include double insulation Outputs must be rated as SELV PELV Class 2 Limited Power Do not connect either the Neutral or L...

Page 6: ...control signals are not used which is the standard case RS232 RS485 Controller Port Pin Description Pin Description Pin 1 1 DTR signal 1 A signal 2 0V reference 2 RS232 signal 3 TXD signal 3 RS232 signal 4 RXD signal 4 RS232 signal 5 0V reference 5 RS232 signal 6 DSR signal 6 B signal Standard programming cables do not provide connection points for pins 1 and 6 When a port is adapted to RS485 Pin ...

Page 7: ...pen the locking mechanism 3 Gently rock the module from side to side easing the module from the controller Re installing a Snap in I O Module 1 Line the circular guidelines on the controller up with the guidelines on the Snap in I O Module as shown below 2 Apply even pressure on all 4 corners until you hear a distinct click The module is now installed Check that all sides and corners are correctly...

Page 8: ...at any time at its sole discretion and without notice to discontinue or change the features designs materials and other specifications of its products and to either permanently or temporarily withdraw any of the forgoing from the market All information in this document is provided as is without warranty of any kind either expressed or implied including but not limited to any implied warranties of ...

Reviews: