Unitronics 

 

 

Vision™ OPLC™ 

User Guide 

V1040-T20B 

This guide provides basic 

information for Unitronics’ controllers V1040-T20B.   

General Description 

V1040 OPLCs are programmable logic controllers that comprise a built-in operating panel containing 
a 10.4

” Color Touchscreen. The V1040 offers function keys along with a virtual alpha-numeric 

keyboard which is automatically displayed when the application requires the operator to enter data. 

Communications 

  2 isolated RS232/RS485 ports 

  USB programming port (Mini-B) 

  Isolated CANbus port 

  The user can order and install an additional port. This may be 

either Ethernet 

or

 serial. 

  Communication Function Blocks include: SMS, GPRS, MODBUS 

serial/IP; Protocol FB enables PLC to communicate with almost 
any external device, via serial or Ethernet communications 

I/O Options 

V1040 supports digital, high-speed, 
analog, weight and temperature 
measurement I/Os via: 

  Snap-in I/O Modules 

Plug into the back of the 
controller to provide an on-
board I/O configuration 

  I/O Expansion Modules 

Local or remote I/Os may be 
added via expansion port or 
CANbus. 

 

 

Installation instructions and other data may be found in the module’s technical 
specification sheet. 

Information Mode 

This mode enables you to: 

  Calibrate the touchscreen 

  View & Edit operand values, COM port settings, RTC and screen 

contrast/brightness settings 

  Stop, initialize, and reset the PLC 

To enter Information Mode, press the touchscreen and maintain contact for 
several seconds. 

Programming 
Software,  
& Utilities 

The Unitronics Setup CD contains VisiLogic software and other utilities 

  VisiLogic  

Easily configure hardware and write both HMI and Ladder control 
applications; the Function Block library simplifies complex tasks 
such as PID. Write your application, and then download it to the 
controller via the programming cable included in the kit. 

  Utilities 

These include UniOPC server, Remote Access for remote 
programming and diagnostics, and DataXport for run-time data 
logging. 

To learn how to use and program the controller, as well as use utilities such as 
Remote Access, refer to the VisiLogic Help system. 

 

 

Summary of Contents for Vision OPLC V1040-T20B

Page 1: ...troller to provide an on board I O configuration I O Expansion Modules Local or remote I Os may be added via expansion port or CANbus Installation instructions and other data may be found in the module s technical specification sheet Information Mode This mode enables you to Calibrate the touchscreen View Edit operand values COM port settings RTC and screen contrast brightness settings Stop initia...

Page 2: ...uct the user must read and understand this document All examples and diagrams are intended to aid understanding and do not guarantee operation Unitronics accepts no responsibility for actual use of this product based on these examples Please dispose of this product according to local and national standards and regulations Only qualified service personnel should open this device or carry out repair...

Page 3: ...ect equipment unless power has been switched off or the area is known to be non hazardous WARNING Exposure to some chemicals may degrade the sealing properties of material used in Relays This equipment must be installed using wiring methods as required for Class I Division 2 as per the NEC and or CEC Panel Mounting For programmable controllers that can be mounted also on panel in order to meet the...

Page 4: ...sition à certains produits chimiques peut dégrader les propriétés des matériaux utilisés pour l étanchéité dans les relais Cet équipement doit être installé utilisant des méthodes de câblage suivant la norme Class I Division 2 NEC et ou CEC Montage de l écran Pour les automates programmables qui peuvent aussi être monté sur l écran pour pouvoir être au standard UL l écran doit être monté dans un c...

Page 5: ...ver on the rear of the controller 1 Remove the battery cover shown on page 6 The polarity is marked on the battery holder and on the battery 2 Insert the battery ensuring that the polarity symbol on the battery is facing up aligned with the symbol on the holder 3 Replace the battery cover Mounting Dimensions Note that the LCD screen may have a single pixel that is permanently either black or white...

Page 6: ...oller into the cut out ensuring that the rubber seal is in place 3 Push the 8 mounting brackets into their slots on the sides of the controller as shown in the figure to the right 4 Tighten the bracket screws against the panel Hold the bracket securely against the unit while tightening the screw 5 When properly mounted the controller is squarely situated in the panel cut out as shown below Caution...

Page 7: ...to the terminal to ensure a proper connection 4 Tighten enough to keep the wire from pulling free Power Supply The controller V1040 T20B requires either an external 12 or 24VDC power supply Permissible input voltage range 10 2 28 8VDC with less than 10 ripple The power supply must include double insulation Outputs must be rated as SELV PELV Class 2 Limited Power Do not connect either the Neutral o...

Page 8: ...ontaining up to 32 devices Pinouts The pinouts below show PLC port signals To connect a PC to a port that is set to RS485 remove the RS485 connector and connect the PC to the PLC via the programming cable Note that this is possible only if flow control signals are not used which is the standard case RS232 RS485 Controller Port Pin Description Pin Description Pin 1 1 DTR signal 1 A signal 2 0V refe...

Page 9: ...Line the circular guidelines on the Snap in I O Module with the slots on the controller as shown below 3 Apply even pressure on all 4 corners until you hear a distinct click The module is now installed Check that all sides and corners are correctly aligned Removing a Snap in I O Module 1 Locate the four buttons on the sides of the controller two on either side 2 Press the buttons and hold them dow...

Page 10: ...r external devices CANLayer 2 J1939 Unitronics proprietary UniCAN 60 controllers 512 data bytes per scan The CANbus port is galvanically isolated CANbus Wiring Use twisted pair cable DeviceNet thick shielded twisted pair cable is recommended Network terminators These are supplied with the controller Place terminators at each end of the CANbus network Resistance must be set to 1 121Ω 1 4W Connect g...

Page 11: ... brightness Via software Store value to SI 9 Keypad Displays virtual keyboard when the application requires data entry Notes 1 Note that the LCD screen may have a single pixel that is permanently either black or white Keypad Number of keys 9 programmable function keys Key type Metal dome sealed membrane switch Program Memory size Application Logic 2MB Images 80MB Fonts 1MB Operand type Quantit y S...

Page 12: ...5200 bps Cable USB 2 0 compliant up to 3m CANbus port 1 Nodes CANopen Unitronics CANbus protocols 127 60 Power requirements 24VDC 4 40mA max per unit See Note 5 Galvanic isolation Yes between CANbus and controller Cable length baud rate See Note 5 25 m 100 m 250 m 500 m 500 m 1000 m 1000 m 1 Mbit s 500 Kbit s 250 Kbit s 125 Kbit s 100 Kbit s 50 Kbit s 20 Kbit s If you require cable lengths over 50...

Page 13: ...oducts at the date of printing Unitronics reserves the right subject to all applicable laws at any time at its sole discretion and without notice to discontinue or change the features designs materials and other specifications of its products and to either permanently or temporarily withdraw any of the forgoing from the market All information in this document is provided as is without warranty of ...

Reviews: