4/19
Unitronics
146
URP-PS24V (PS24) - Input 24VDC, Output system Power 5VDC/1A
Items
Specification
System Input Voltage range
15VDC to 32VDC
System Power Input Voltage
Normal 24VDC
Indicators
1 Green System Power state , 1 Green Field Power state, 1 Green Uni-I/O
state
Field Power Input Voltage
Normal 24VDC (±20%)
Field Power Contacts Current
Max. 10A
Operating Temperature
-40°C to 50°C (-40°F to 122°F) : Max. 10A
50°C to 70°C (122F to 158°F) : Max. 7A
Uni-I/O
Output Voltage
Max. 5VDC, 1A
System power Dissipation
Max. 20mA @ 24VDC
Wring
I/O Cable Max. 2.0
𝑚𝑚
2
(AWG 14)
Weight
59g
Module size
12mm x 99mm x 70mm
Operating temperature
- 40°C to 70°C (-40°F to 158°F) temperature range specification can be
guaranteed under the following conditions:
Current for I/O Modules : Under 0.4A.
Otherwise, temperature specification can be guaranteed with -40°C to 60°C (-
40°F to 140°F)
Usage
URP-PS24V is system internal power expansion module.
The URB-TCP network adapter system supplies a current of 1.5A If your system current requirements exceed
1.5A, add a power supply such as the URP-PS24V.
Position the power supply directly before the first module that will cause the requirement to exceed 1.5A, as shown
in the example below.