SIGA-HFD Intelligent Fixed-
Temperature Heat Detector 
Installation Sheet 

 

 

Description 

The Signature Series SIGA-HFD Intelligent Fixed-Temperature Heat 
Detector 

that contains a fixed-temperature heat sensor to detect heat 

from fire. The heat sensor monitors the temperature of the air in its 
surroundings and the detector analyzes the data to determine whether 
to initiate an alarm. 

LED indicator. 

The LED indicator (see Figure 1) displays the following 

states: 

• 

Normal: Green LED indicator flashes, no action 

• 

Alarm/active: Red LED indicator flashes, evacuate the area 

Figure 1: SIGA-HFD features 

 

(1)  Self-locking tab 
(2)  LED indicator 
 

 

Installation 

Install and wire this device in accordance with applicable national and 
local codes, ordinances, and regulations. 

WARNINGS

 

• 

This detector does not operate without electrical power. As fires 
frequently cause power interruption, discuss further safeguards 
with the local fire protection specialist. 

• 

This detector does not sense fires in areas where heat cannot 
reach the detector. Heat from fires in walls, roofs, or on the 
opposite side of closed doors may not reach the detector. 

• 

This detector by itself does not provide smoke or fire protection. 
Use this detector with ionization or photoelectric smoke detectors, 
or both. 

• 

This detector does not detect oxygen levels, smoke, toxic gases, 
or flames. Use this device as part of a broad-based life safety 
program, which includes a variety of information sources pertaining 
to heat and smoke levels, extinguishment systems, visible and 
audible devices, and other safety measures. 

• 

Independent studies indicate that heat detectors should only be 
used when property protection alone is involved. Never rely on 
heat detectors as the sole means of fire protection. 

Note 

 

• 

To ensure proper operation, store the detector within the 
recommended ranges. Allow the detector to stabilize to room 
temperature before applying power. 

• 

The dust cover (supplied) must remain on the detector during 
installation and be removed prior to commissioning and service. 
The dust cover is not a substitute for removing the detector during 
new construction or heavy remodeling. 

• 

In Canada, install according to CAN/ULC-S524 

Standard for the 

Installation of Fire Alarm Systems

, CSA C22.1 

Canadian Electrical 

Code 

Part 1, and the local authority having jurisdiction. 

To install the detector: 

1.  Install and wire the base, as described on the installation sheet 

supplied with the base. 

2.  Remove the serial number label from the detector and attach it to 

the project documentation. 

3.  Attach the detector to the base by rotating the detector clockwise 

until it snaps into the locked position. 

Testing 

Before testing, notify the proper authorities that the fire alarm system is 
undergoing maintenance and will be temporarily out of service. 

Caution: 

Heat damage. Excessive heat may damage the detector 

outer cover. Do not apply excessive heat when using a hair dryer. 
When using a Testifire detector tester, you must install a SIGA2 
Testifire Adapter Assembly. 

Make sure the SIGA2 Testifire Adapter Assembly (model 
SIGA2-TSTSPACER) is installed in the Testifire detector tester before 
testing. Refer to the 

SIGA2-TSTSPACER Testifire Adapter Assembly 

Installation Sheet

 (P/N 3101942-ML) for further details. 