![United Technologies Carrier Weathermaker 48A2 Controls, Start-Up, Operation, Service, And Troubleshooting Download Page 119](http://html1.mh-extra.com/html/united-technologies/carrier-weathermaker-48a2/carrier-weathermaker-48a2_controls-start-up-operation-service-and-troubleshooting_4065174119.webp)
119
Table 104 — Staged Gas Control Board (SCB) Inputs and Outputs
POINT
NAME
POINT DESCRIPTION
I/O POINT
NAME
PLUG AND PIN
REFERENCE
SIGNAL PIN(S)
PORT STATE
INPUTS
AN1
J5, 1-3
1=5v, 2=Vin, 3=GND (thermistor 1-2)
(0-5VDC, thermistor, ohms)
AN2
J5, 4-6
4=5v, 5=Vin, 6=GND (thermistor 4-5)
(0-5VDC, thermistor, ohms)
LAT1SGAS
Leaving air temperature 1
AN3
J5, 7-9
7=5v, 8=Vin, 9=GND (thermistor 7-8)
(0-5VDC, thermistor, ohms)
LAT2SGAS
Leaving air temperature 2
AN4
J5, 10-12
10=5v, 11=Vin, 12=GND (thermistor 10-11) (0-5VDC, thermistor, ohms)
LAT3SGAS
Leaving air temperature 3
AN5
J5, 13-15
13=5v, 14=Vin, 15=GND (thermistor 13-14) (0-5VDC, thermistor, ohms)
AN6
J6, 1-3
1=5v, 2=Vin, 3=GND (thermistor 1-2)
(0-5VDC, thermistor, ohms)
AN7
J6, 4-6
4=5v, 5=Vin, 6=GND (thermistor 4-5)
(0-5VDC, thermistor, ohms)
AN8
J6, 7-9
7=5v, 8=Vin, 9=GND (thermistor 7-8)
(0-5VDC, thermistor, ohms)
AN9
J7, 1-2
1
(thermistor, ohms)
AN10
J7, 3-4
3
(thermistor, ohms)
OUTPUTS
AO1
J8, 1-2
1=0-20mA, 2=GND
0-20mA OUT
AO2
J8, 3-4
3=0-20mA, 4=GND
0-20mA OUT
HS3
Heat Stage 3
RLY1
J9, 1-3
1 = 2 = RLY1A, 3 = RLY1B
1 = Closes RLY1A/RLY1B
HS4
Heat Stage 4
RLY 2
J9, 4-6
4 = 5 = RLY2A, 6 = RLY2B
1 = Closes RLY2A/RLY2B
HS5
Heat Stage 5
RLY 3
J9, 7-9
7 = 8 = RLY3A, 9 = RLY3B
1 = Closes RLY3A/RLY3B
HS6
Heat Stage 6
RLY 4
J9, 10-12
10 = 11= RLY4A, 12 = RLY4B
1 = Closes RLY4A/RLY4B
RLY 5
J9, 13-15
13 = 14 = RLY5A, 15 = RLY5B
1 = Closes RLY5A/RLY5B
ADDRESS DIP
SWITCHES ALL ON
RED LED-
STATUS
GREEN LED-
LEN (LOCAL EQUIPMENT NETWORK)
J2
J1
PWR
J4
LEN
LEN
J3
4-POSITION
DIP SWITCH
PWR
1
13
10
7
XDCR/THERM
4
1
J6
J5
7
4
1
3
1
3
1
J8
0-20mA OUT
J7
THERM
XDCR/THERM
1
4
13
10
7
RELA
YS
J9
CEBD430427 HK50AA032 CEPL130427
Fig. 31 — Staged Gas Heat Control Board (SCB)
A48-7707
Summary of Contents for Carrier Weathermaker 48A2
Page 105: ...105 Fig 20 Typical Main Control Box Wiring Schematic 48 50A2 A3 A4 A5 Units...
Page 106: ...106 Fig 21 Typical Auxiliary Control Box Wiring Schematic...
Page 107: ...107 Fig 22 Typical 2 Stage Gas Heat Wiring Schematic Size 060 Units Shown a48 8357...
Page 108: ...108 TO NEXT PAGE Fig 23 Typical Staged Gas Heat Wiring Schematic Size 060 Units Shown A48 7296...
Page 109: ...109 Fig 23 Typical Staged Gas Heat Wiring Schematic Size 060 Units Shown cont A48 8358...
Page 110: ...110 Fig 24 Typical Electric Heat Control Schematic 50 Series Size 060 Units Shown a50 8228...
Page 111: ...111 Fig 25 Typical Power Schematic 48 50A2 A3 A4 A5 060 Unit Shown...
Page 112: ...112 Fig 26 Typical Low Ambient Controls Option Wiring...
Page 113: ...113 Fig 27 Typical Small Chassis Component Location Size 020 035 Units...
Page 114: ...114 Fig 28 Typical Large Chassis Component Locations Size 040 060 Units...
Page 118: ...118 Fig 30 Economizer Control Board ECB1 and VAV Control Board ECB2 A48 7706...
Page 142: ...142 A48 3733 Fig 56 Main Burner Removal...
Page 176: ...176 APPENDIX C VFD INFORMATION cont Fig F Internal Enclosure Fan Replacement A48 7716...