Appendix A: Unit Vent Network Points List
Unit Ventilator
CARRIER CORPORATION ©2019
Integration Guide
All rights reserved
32
Network points list for N2 and LonWorks
N2
LonWorks
Point Name
Point
Access
Units
Default
Value
N2 Network
Point Type
N2 Network
Point Address
SNVT Type
SNVT Name
Return Air
Temperature
R
°F
°F
ADF
50
nvoRtnAirTmp
Output (active) -
default
Setpoint
R/W
°F
°F
ADF
4
nviOccCoolSP
Input (passive) -
default
Setpoint
R/W
°F
°F
ADF
9
nviOccHeatSP
Input (passive) -
default
Setpoint
R/W
°F
°F
ADF
7
nviUnoccClSP
Input (passive) -
default
Setpoint
R/W
°F
°F
ADF
8
nviUnoccHtSP
Input (passive) -
default
Supply Fan Status R
Off
On
BI
24
nvoFanStatus
Output (active) -
default
Supply Air
Temperature
R
°F
°F
ADF
49
nvoSAT
Output (active) -
default
Cooling Lockout
Temperature
R/W
°F
°F
ADF
16
nviClLckTemp
Input (passive) -
default
Cooling Output
R
%
%
ADF
14
nvoCoolOut
Output (active) -
default
Damper Lockout
Temp
R/W
°F
°F
ADF
15
nviDmpLckTmp
Input (passive) -
default
Damper Output
R
%
%
ADF
74
nvoOAVntDmpr
Output (active) -
default
Damper Setpoint
Override Value
R/W
°F
°F
ADF
19
nviDmpSetOvr
Input (passive) -
default
Economizer Purge
Min Pos
R/W
%Open
%Open
ADF
5
nviEcnPrgMin
Input (passive) -
default
Effective Cool
Setpoint
R
°F
°F
ADF
22
nvoEffCoolSP
Output (active) -
default
Effective Heat
Setpoint
R
°F
°F
ADF
23
nvoEffHeatSP
Output (active) -
default
Filter Service
Alarm Timer
R/W
hr
hr
ADF
28
nviFltAlmTm
Input (passive) -
default
Heating Lockout
Temperature
R/W
°F
°F
ADF
29
nviHtLckTmp
Input (passive) -
default
Heating Output
R
%
%
ADF
26
nvoHeatOut
Output (active) -
default
Occ Override Delay R/W
min
min
ADF
47
nviOccOvrDly
Input (passive) -
default
Outdoor Air
Temperature
R
°F
°F
ADF
38
nvoOAT
Output (active) -
default
Override Time
Remaining
R
min
min
ADF
41
nvoOvrTmRem
Output (active) -
default
Power Fail Restart
Delay
R/W
seconds
seconds
ADF
58
nviUntStrDly
Input (passive) -
default
Setpoint
Adjustment
R
°F
°F
ADF
44
nvoSPAdjust
Output (active) -
default
Setpoint
Adjustment Range
R/W
°F
°F
ADF
45
nviSPAdjRng
Input (passive) -
default
Space
Temperature -
Prime Variable
R
°F
°F
ADF
48
nvoSpaceTemp
Output (active) -
default
System Outdoor Air R/W
°F
°F
ADF
54
nviSysOAT
Input (passive) -