United States Stove HOTBLAST 1950 Installation And Operating Instructions Manual Download Page 20

 

19

11. TROUBLE SHOOTING 

 

 
PROBLEM 

 
CAUSES 

 
SOLUTIONS 

 
Heating inefficient during the first 
combustions.  Lack of draft. 

 
Improper adjustment of the 
barometric damper (opened too 
wide).  Chimney flue restriction (too 
long., or too many 90

o

 elbows) 

 

 
Adjust the damper, minimize the 
chimney length and use 45

o

 elbows. 

 
Furnace heats well, warm air plenum 
is very hot by there is not much heat 
coming out in the room. 

 
Improper installation of the ducts, 
little static pressure, unbalanced 
system (too many warm air outlets 
and not enough cold air inlets). 
 

 
Reinstall the ducts correctly. 
Respect the minimum static pressure 
of 0.20 in. w.c. 

 
Furnace consumes a lot of wood. 

 
The thermostat which controls the 
damper is continuously activated or 
is too close to a source of cold air.  
Damper not properly adjusted.  
House not insulated enough.  Ash 
drawer is not tightly closed.  Furnace 
too small for the surface to be 
heated. Unbalanced ventilation 
system, very little heat where the 
thermostat is located. 
 

 
Relocate the thermostat. Adjust the 
chain that links the damper to the 
damper motor.  Rebalance the 
ventilation system in order to 
increase the air flow in the room 
where the thermostat is located. 

 
Fan start-up is too slow. 

 
Fan “ON” setting too high.  Return air 
is too cold (temperature lower than 
65 degrees).  Limit control not well 
located in the warm air plenum. 

 
Lower the temperature starting point.  
The “fan ON” setting on limit control 
is set at 150°F, it may reduced in 
some particular installations. Reduce 
the fresh air flow. Relocate the limit 
control. 
 

 
A lot of creosote, moderate heat 
output. 

 
Wet wood, lack of draft.  Barometric 
damper not properly adjusted.  Dirty 
chimney. 
 

 
Use dry wood.  Adjust the barometric 
damper.  Clean the chimney flue and 
the furnace exchangers. 

 
Furnace heats a lot but the warm air 
plenum does not get hot. 

 
Wet wood or low grade wood.  Too 
much cold air return for the hot air 
ducts.  Unbalanced ventilation 
system. Blower speed too high 
 

 
Use dry wood.  Reinstall the 
ventilation system correctly. Use a 
lower blower speed. 

 

IMPORTANT NOTE 

FOR, INSTALLATION OF A CENTRAL HEATING VENTILATION SYSTEM, IT IS HIGHLY 

RECOMMENDED TO CONSULT A HEATING SYSTEM VENTILATION SPECIALIST. 

N.B.:  UNITED STATES STOVE COMPANY IS NOT RESPONSIBLE FOR POOR APPLIANCE 

PERFORMANCES, DUE TO AN IMPROPER INSTALLATION. 

Summary of Contents for HOTBLAST 1950

Page 1: ...Testing Services Distributed by UNITED STATES STOVE COMPANY 227 INDUSTRIAL PARK ROAD P O BOX 151 SOUTH PITTSBURG TN 37380 Tel 423 837 2100 Fax 423 837 2109 8BDC3 Tm TjETEMC P 41302957 1302957 1302957...

Page 2: ...ECTRICAL CONNECTION 8 3 6 THERMOSTAT 8 3 7 FAN CONTROL 8 4 OPERATING INSTRUCTIONS 9 4 1 LIGHTING 9 4 2 PREHEATING 9 4 3 HEATING 10 4 3 1 EARLY SIGNS OF OVERFIRED FURNACE 10 4 3 2 WOOD AS HEATING FUEL...

Page 3: ...anges in the warm air bonnet of the furnace see General Technical Data static pressure 1 CHIMNEY AND DRAFT This furnace must be connected to a chimney certified for wood burning heating appliances a 7...

Page 4: ...the chimney cleaning buy your firewood at least one year before using it Store it in a dry place in order to obtain the minimum moisture content and optimize its efficiency Do not store wood or combus...

Page 5: ...eaners are available on the market and their efficiency makes no doubt WARNING Avoid knocking or scratching the glass which could be damaged 2 6 1 GLASS SPECIFICATIONS The glass is made of Pyroceram t...

Page 6: ...e connector is as short as possible minimize the use of 90o elbows The owner must ensure a proper installation to allow a safe operation of the appliance 3 2 CLEARANCES TO COMBUSTIBLE MATERIALS N B Th...

Page 7: ...raft exceed 0 06 in W C a barometric damper should be installed on the smoke pipe Never install a manual damper REDUCER DIAMETER 7 For a proper installation follow the advices below 1 All the joints o...

Page 8: ...hat a house constructed or renovated in order to be airtight is liable to lack fresh air necessary for a proper combustion and operation of flame producing heating appliance In such a case when starti...

Page 9: ...6 THERMOSTAT The thermostat must be installed on an inside wall in a location where it is not likely to be affected by the draft coming from an air outlet It must be installed at a minimum of 55 inche...

Page 10: ...ating 2 Remove the steel plate on the ash grid and dump the ashes in the ash drawer 3 Put the steel plate back in place making sure it is properly seated The steel plate on the ash grid is intended to...

Page 11: ...THE PURPOSE IS TO STABILIZE THE PRESSURE INSIDE THE FURNACE 4 3 1 EARLY SIGNS OF OVERFIRED FURNACE 1 Roaring fire 2 Chimney connector is glowing red 3 Extreme heat coming from the furnace 4 If this oc...

Page 12: ...anches or small pieces of wood can ignite the creosote residues accumulated in the evacuation flue system The usual signs are 1 Rumbling 2 The flue gets extremely hot 3 Sparks are coming out of the ch...

Page 13: ...e exchanger pipes move the upper plate of the combustion chamber forward Using the scraper clean the three exchanger pipes The accumulated dirt in the lateral exchangers will fall into the combustion...

Page 14: ...e otherwise it must be replaced Use only wood as a combustible Seasoned hard wood logs 18 to 22 long are recommended as a combustible 5 3 MAINTENANCE OF THE BLOWER MOTOR The two bearings of the motor...

Page 15: ...ediately Never operate a furnace with a broken glass If you have to change your door glass you must use Pyroceram 3 16 5mm thick glass available at your HOTBLAST authorized dealer To replace the glass...

Page 16: ...LOW L2 120 V A C L1 BLACK TRANSFO JUNCTION BOX 24 V A C 24 V A C THERMOSTAT SERVO MOTOR RED BLACK WHITE BLACK BLACK 24 V A C 120 V A C TRANSFORMER SWITCH MOVE THIS WIRE TO CHANGE MOTOR SPEED REVISION...

Page 17: ...DIRECT DRIVE OUTPUT TEMP VAR BTU HR STATIC PRESSURE FILTER FAN MOTOR SPEED CFM O F WOOD MIN MAX 2 H2O HOTBLAST 1950 DD 10 1 3 3 or 4 1300 78 140000 0 2 0 6 12 x 24 X 1 8 2 TECHNICAL DATA ELECTRIC CON...

Page 18: ...t 2 x 12 damper or 4 x 10 For a 6 warm air outlet 2 x 14 damper or 4 x 12 WARM AIR SYSTEM INSTALLATION HOUSE DIMENSIONS Example 28 x 40 bungalow 1 120 sq ft 28 x 40 x 8 8 960 cu ft x 1 8 Ch air hr 16...

Page 19: ...5 8 9 6 3 8 9 4 1 4 7 1 2 1 1 2 1 1 4 3 1 8 6 3 1 5 9 7 9 9 9 8 6 7 7 7 7 7 7 7 7 7 6 6 6 6 2 2 7 7 7 7 7 7 7 7 7 7 4 ITEM PART DESCRIPTION QTY 1 BRICK 4 1 4 X 9 SPECIAL 1 2 BRICK 4 1 2 X 7 5 8 2 3 B...

Page 20: ...to the damper motor Rebalance the ventilation system in order to increase the air flow in the room where the thermostat is located Fan start up is too slow Fan ON setting too high Return air is too co...

Reviews: