GENERAL

MISUSE OF THIS PRODUCT MAY CAUSE EXPLOSION AND PERSONAL INJURY.  
THESE INSTRUCTIONS MUST BE THOROUGHLY READ AND UNDERSTOOD 
BEFORE UNIT IS INSTALLED.

THIS EQUIPMENT IS SUITABLE FOR USE IN CLASS I, DIVISIONS 1 & 2, 
GROUPS A, B, C AND D; CLASS II, DIVISIONS 1 & 2, GROUPS E, F AND G; 
CLASS III; OR NON-HAZARDOUS LOCATIONS ONLY. -50 °C (-58 °F) ≤ Tamb. 
≤ 95 °C (203 °F), ENCLOSURE TYPE 4X.

THIS EQUIPMENT IS ATEX CERTIFIED (OPTION M419) FOR EQUIPMENT CAT-
EGORY 2. SUITABLE FOR APPROPRIATE USE IN GAS ZONE 1 AND DUST ZONE 
21 APPLICATIONS. 

0539 DEMKO 03 ATEX 0252466X

 

 II 2 G EEx d IIC T6

 

 II 2 D T+85 °C

 

-50 °C ≤ Tamb. ≤+80 ºC, IP66

BEFORE INSTALLING, CHECK THE SENSOR MODEL SELECTED FOR 
COMPATIBILITY TO THE PROCESS MEDIA IN CONTACT WITH THE SENSOR AND 
WETTED PARTS.

PROOF PRESSURE* LIMITS STATED IN THE LITERATURE AND ON NAME-
PLATES MUST NEVER BE EXCEEDED, EVEN BY SURGES IN THE SYSTEM.  
OCCASIONAL OPERATION OF UNIT UP TO PROOF  PRESSURE IS ACCEPTABLE 
(E.G., START-UP, TESTING).  CONTINUOUS OPERATION SHOULD NOT EXCEED 

THE DESIGNATED OVER RANGE PRESSURE.

*Proof Pressure
The maximum pressure to which a pressure sensor may be occasionally subjected, 
which causes no permanent damage (e.g., start-up testing).  (May require set-point 
adjustment).

THESE PRODUCTS DO NOT HAVE ANY FIELD REPLACEABLE PARTS. ANY 
SUBSTITUTION OF COMPONENTS MAY IMPAIR SUITABILITY FOR CLASS I, 
DIVISION 1.

The Spectra-12 switch utilizes a diaphragm or a piston sensor to detect a pressure 

change.  The response, at a predetermined set point, actuates or deactuates a SPDT 

or DPDT  snap-acting switch, converting a pressure signal into an electrical signal. 

Control set point may be varied by turning the internal slotted adjustment screw 

according to procedures outlined in Part II-Adjustments.

Tools Needed

1-1/6" Open end wrench

MOUNTING

ALWAYS LOCATE UNITS WHERE SHOCK, VIBRATION AND AMBIENT TEMPERATURE 

FLUCTUATIONS ARE MINIMAL. DO NOT MOUNT IN AMBIENT TEMPERATURE 

AREAS EXCEEDING 203°F (IF UL/cUL APPROVAL IS APPLICABLE) OR 80 °F (IF 

ATEX APPROVAL IS APPLICABLE). IF SEVERE PRESSURE SURGES ARE EXPECTED, 

CONSIDER THE USE OF A PRESSURE SNUBBER.

FOR PRESSURE MODELS, MOUNT USING PRESSURE CONNECTION:  ALWAYS USE A 
WRENCH ON PRESSURE CONNECTION WRENCH FLAT. (SEE FIGURE 1)

FOR  DIFFERENTIAL  PRESSURE  MODELS,  MOUNT  UNIT  AGAINST  A  RIGID 
SUPPORT  USING  THE  MOUNTING  BRACKET  ATTACHED  TO  THE  SENSOR 
ASSEMBLY.  THEN CONNECT THE HIGH AND LOW PRESSURE CONNECTIONS 

(HIGH PRESSURE PORT IS ON THE LEFT, WHEN FACING THE UNIT).

UNIT  MAY  BE  MOUNTED  IN  ANY  POSITION.    HOWEVER,  IF  INSTAL-
LATION  LOCATION  RESULTS  IN  FREQUENT  EXPOSURE  TO 
LIQUID IT IS RECOMMENDED THAT THE UNIT BE MOUNTED VERTICALLY WITH 

THE PRESSURE CONNECTION DOWN.  IF UNIT IS TO BE SET AFTER MOUNTING, VERIFY 
THAT ADJUSTMENT OPENING IS ACCESSIBLE. “FRONT” MARKING ON NAMEPLATE MUST 
FACE THE OPERATOR.

1/2” NPTM or M20 Electrical Connection

When  panel  mounting,  mount  through  7/8”  clearance  hole  in  panel.  Hold 

in  place  with  serrated  1/2”  or  M20  conduit  nut.  Always  support  the  unit  by 

holding a wrench on the hex.

TO ATTACH CONDUIT CONNECTION, HOLD ELECTRICAL CONNECTION STEADY WITH WRENCH ON 

HEX, THEN THREAD ON CONDUIT.

Surface Mounting Bracket Kit (P/N 62169-13), Option M449

Open the adjustment cover and orient the unit so that adjustment opening will be acces-

sible when the switch is mounted. Close the adjustment cover ensuring that the bracket 

does not interfere with the cover. Failure to do so may result in improper sealing of 

adjustment cover. Mount assembly in desired location, following instructions included with 

mounting bracket kit. 

WIRING

DISCONNECT ALL SUPPLY CIRCUITS BEFORE WIRING UNIT. ELECTRICAL RAT-

INGS STATED IN LITERATURE AND ON NAMEPLATE  MUST NOT BE EXCEED-

ED. OVERLOAD ON A SWITCH CAN CAUSE FAILURE ON THE FIRST CYCLE.

EXTERNAL GROUNDING SCREW (OPTION M460) IS REQUIRED FOR NON-
METALLIC CONDUIT SYSTEMS.

WIRE IN ACCORDANCE WITH LOCAL AND NATIONAL ELECTRICAL CODES.  BY 

THE INSTALLATION, THE WIRES SHALL BE PROTECTED AGAINST MECHANI-

CAL DAMAGE. E.G.  BY USE OF A CONDUIT.

DIN  CONNECTOR  (OPTION  M515)  IS  NOT  APPROVED  FOR  CLASS  I,  DIV. 

1/HAZARDOUS LOCATIONS/FLAMEPROOF ATMOSPHERES.

THE WIRING TO THE PRESSURE SWITCH MUST ONLY BE CONNECTED IN THE 

SAFE AREA OR BY AN APPROVED TERMINAL BOX CERTIFIED TO EN 50 018 

OR EN 50 019 FOR HAZARDOUS LOCATIONS/FLAMEPROOF ATMOSPHERES.

1/2" NPTM or M20 conduit connection is provided on top of the unit with 72” lead-

wires. Unit is available with SPDT or DPDT operation. External grounding screw and 

clamp is provided with option M460. 

Factory Sealed Leadwires are color coded:

TERMINALS          SPDT                DPDT

                                                SWT1    SWT2

Common                   Brown        Brown       Yellow
Normally Closed        Red            Red          Black
Normally Open          Blue           Blue         Violet
Ground                    Green         Green

DIN Connector with 4 Male Terminals (figure 3)

Wire in accordance with local and national electrical codes. Connector conforms to 

DIN 43650. Use a mating DIN connector (female type). Coding:
                          

TERMINALS

        

                 Terminal #1                    Common

                          Terminal #2              Normally Closed
                          Terminal #3               Normally Open
                                                                 Ground

IM12-03

Spectra 12 Series

Explosion Proof, Pressure and 

Differential Pressure Switches

Part I - Installation

figure 1

DO NOT TURN

SWITCH

 

HOUSING

MOUNT VIA

PRESSURE

 

CONNECTION

Please read all instructional literature carefully and thoroughly before starting.  Refer to the final page for the listing of 
Recommended Practices, Liabilities and Warranties.

U N I T E D   E L E C T R I C  
C O N T R O L S

Installation and Maintenance 

Instructions