BEFORE INSTALLING, CHECK THE SENSOR MODEL SELECTED 
FOR COMPATIBILITY TO THE PROCESS MEDIA IN CONTACT 
WITH THE SENSOR AND WETTED PARTS.

J21K Differential Pressure Switch utilizes opposing metal bellows to detect 
pressure  differences  between  two  pressure  sources.  The  bellows  are 
connected  to  a  mechanical  linkage.  When  the  pressure  at  the  high  port 
exceeds  the  pressure  at  the  low  port  by  a  pre-determined  amount,  the 
mechanism  operates  a  snap-action  electrical  switch.  The  predetermined 
actuation pressure can be adjusted by the user as described below.

Part I - Installation

Tools Needed

- Adjustable wrenches (2)

- Flat blade screwdriver

MOUNTING

INSTALL UNIT WHERE SHOCK, VIBRATION AND TEMPERATURE 
FLUCTUATIONS  ARE  MINIMAL.  MOUNT  UNIT  SO  THAT 
MOISTURE IS PREVENTED FROM ENTERING THE ENCLOSURE. 
DO NOT MOUNT UNIT IN AMBIENT TEMPERATURES EXCEEDING 

PUBLISHED LIMITS.

Surface mount in any position via two mounting ears. Never turn this unit 
by grasping enclosure. Always hold a wrench on the bellows housing (or 
fitting) when connecting pressure joints.

WIRING

DISCONNECT ALL SUPPLY CIRCUITS BEFORE WIRING UNIT. 
WIRE  UNITS  ACCORDING  TO  NATIONAL  AND  LOCAL 
ELECTRICAL CODES. MAXIMUM RECOMMENDED WIRE SIZE 
IS 14 AWG.

ELECTRICAL  RATINGS  STATED  IN  LITERATURE  AND  ON 
NAMEPLATES  MUST  NOT  BE  EXCEEDED,  OVERLOAD  ON  A 
SWITCH CAN CAUSE FAILURE ON THE FIRST CYCLE.

Remove the two (2) screws retaining the cover and gasket. Remove cover. 
Connect conduit to the enclosure using a conduit fitting that is suitable for 
your  installation.  A  watertight  conduit  fitting  (option  M900  or  equivalent) 
must be used for NEMA 4 protection. Wire directly to the switch terminals 
in accordance with local and national electrical codes. Bring the wires up to 
the terminals from the rear of the enclosure to prevent interference with the 
mechanism.

Part II - Adjustments

Tools Needed

- 5/16" open end wrench

For  set  point  adjustment  and  re-calibration,  connect  the  unit  to  a  calibrated 
pressure source.

Set point adjustment is achieved by varying the gap between the mechanical 
actuator and the plunger on the electrical switch

J21K

To raise the differential pressure setting, turn the 5/16" hex head screw out 
(to the left).
To lower the differential pressure setting, turn the 5/16" hex head screw in 
(to the right).

IMJ21K-01

Differential Pressure Switch

Type J21K

UNITED ELECTRIC
CONTROLS

Installation and Maintenance

Instructions