55 HT Series Thermostats are designed to control heat

tracing and freeze protection circuits. Temperature varia-

tions are sensed by a liquid filled sensing bulb which

hydraulically transmits to a diaphragm which either actu-

ates or deactuates a snap-acting switch at a predeter-

mined set point. 

MAXIMUM TEMPERATURE IS THE HIGHEST

TEMPERATURE TO WHICH A SENSING ELE-

MENT MAY BE OCCASION- ALLY SUBJECTED

WITHOUT ADVERSELY AFFECTING SET POINT CALI-

BRATION AND REPEATABILITY.  MAXIMUM TEMPERA -

TURE LIMITS STATED IN LITERATURE MUST NEVER

BE EXCEEDED, EVEN BY SURGES IN THE SYSTEM.

OCCASIONAL OPERATION OF UNIT UP TO MAX. TEM-

PERATURE IS ACCEPTABLE (E.G. START-UP, TEST-

ING).  CONTINUOUS OPERATION SHOULD BE

RESTRICTED TO THE DESIGNATED ADJUSTABLE

RANGE.

Tools Needed

Flathead screwdriver

MOUNTING

INSTALL UNIT WHERE SHOCK,  VIBRATION

AND TEMPERATURE FLUCTUATIONS ARE MIN-

IMAL.  ORIENT UNIT SO THAT MOISTURE IS

PREVENTED FROM ENTERING THE ENCLOSURE.  

Do not mount unit in ambient temperatures exceeding

product specifications. 55 Series Thermostats can be

mounted in any position. 

For remote sensing thermostats, mount the unit via the (2)

3/16” screw clearance holes on the enclosure (See

Dimensions on back page.)  Locate the bulb and 6” of 

Installation and
Maintenance Instructions

IM55HT

Please read all instructional literature carefully and thoroughly before starting.  Refer to the final page for the listing of Recommended
Practices, Liabilities and Warranties.

55HT Series

Thermostats for Heat Tracing 

and Freeze Protection Applications in

Ordinary 

Locations

Type E55HT

Part I - Installation

Part I - Installation

capillary in the area that is exposed to the coldest tempera-

ture. Be sure to locate the bulb so that it will not be

exposed to temperatures beyond sensor  exposure limits.

Avoid bending or coiling the capillary tube smaller  than

1/2” radius. Exercise caution when making bends near the

capillary ends.

For ambient sensing thermostats, locate the unit in area

that is exposed to coldest temperature.

WIRING

DISCONNECT ALL SUPPLY CIRCUITS BEFORE

WIRING UNIT. ELECTRICAL RATINGS STATED

IN LITERATURE AND NAMEPLATES MUST NOT

BE EXCEEDED. OVERLOAD ON A SWITCH CAN

CAUSE FAILURE ON THE FIRST CYCLE. WIRE UNITS

ACCORDING TO NATIONAL AND LOCAL ELECTRICAL

CODES. RECOMMENDED WIRE SIZE IS 14 AWG. 

Remove the four screws retaining the cover and cover gasket.

Connect  conduit to the 1/2” NPT connection located on the

side of the enclosure. Wire directly to the switch terminals

according to local and national electrical codes. The three

switch terminals are clearly labeled “common”, “norm

open”, and “norm closed”.  

Start-Up Process

Turn dial and knob to the desired temperature setting.

Thermostat is ready for operation.  