background image

INSTALLATION 
MANUAL

SAVE THIS MANUAL

INSTALLATION & OPERATING INSTRUCTIONS

FOR RP007 - 060 SERIES 

 WATER SOURCE HEAT PUMPS 

 

036-21521-001-A-0103

RP007 TO 060

CONTENTS

INTRODUCTION  . . . . . . . . . . . . . . . . . . . . . . . . . . .3
PRE-INSTALLATION INSPECTION OF 
EQUIPMENT. . . . . . . . . . . . . . . . . . . . . . . . . . . . . .  3
INSTALLATION . . . . . . . . . . . . . . . . . . . . . . . . . . .  3
PRODUCT NOMENCLATURE. . . . . . . . . . . . . . . .  4
START-UP AND OPERATION. . . . . . . . . . . . . . .  10
MAINTENANCE . . . . . . . . . . . . . . . . . . . . . . . . . . .11

Complete Table of Contents on following pages.

NOTES, CAUTIONS AND WARNINGS

Installer should pay particular attention to the words:

NOTE

CAUTION

, and 

WARNING

. Notes are intended to

clarify or make the installation easier. Cautions are given
to prevent equipment damage. Warnings are given to
alert installer that personal injury and/or equipment dam-
age may result if installation procedure is not handled
properly.

CAUTION:

READ ALL SAFETY GUIDES BEFORE YOU 
BEGIN TO INSTALL YOUR UNIT.

Summary of Contents for RP007 Series

Page 1: ...TENANCE 11 Complete Table of Contents on following pages NOTES CAUTIONS AND WARNINGS Installer should pay particular attention to the words NOTE CAUTION and WARNING Notes are intended to clarify or ma...

Page 2: ...PIPING 10 WATER REGULATING VALVE INSTALLATION 10 START UP AND OPERATION 10 START UP 11 WATER REGULATING VALVE ADJUSTMENT 11 MAINTENANCE 11 STANDARD PRODUCT WARRANTY 17 LIST OF FIGURES Fig Pg 1 UNIT MO...

Page 3: ...available as field installed acces sories All units are completely factory wired with all necessary operating controls A 24 volt control circuit with over size transformer is provided for field conne...

Page 4: ...ING INSTALLATION Location To ensure unit operates at maximum effi ciencies choose a dry indoor area where the tempera ture is controlled between 40 F and 115 F Consideration of surrounding areas shoul...

Page 5: ...ber Used 1 1 1 1 1 1 1 1 1 Air Coil Type Enhanced Copper Tubes Enhanced Aluminum Fins Face Area sq ft 1 00 1 00 1 00 1 51 2 56 2 56 2 88 4 38 5 00 Rows FPI 2 14 2 14 3 14 3 14 3 14 3 14 3 14 3 14 3 14...

Page 6: ...he blower outlet flange Allowance must be made in the supply duct for removal of the first duct section adja cent to the unit for the servicing of the blower and motor assembly Return air may be ducte...

Page 7: ...dered as an optional accessory for delivery with the units if desired TABLE 3 ELECTRICAL DATA MODEL SERIES SUPPLY VOLTAGE COMPRESSOR BLOWER MIN CCT AMPACITY MAX FUSE CCT BKR AMP QTY RLA LRA HP FLA 007...

Page 8: ...0 0 1 0 2 0 3 0 4 0 5 0 6 0 7 0 8 007 High 270 235 195 150 Med 260 240 210 175 Low 225 215 200 180 150 009 High 380 360 330 290 240 Med 350 340 325 300 270 235 Low 285 275 260 240 210 012 High 495 475...

Page 9: ...ept if the inlet water temperature is constant and the flow rate can be pre set and turned on and off by some other means such as a dedicated pump circuit or solenoid valve Automatic water flow regula...

Page 10: ...the installation and before energizing the power supply to the unit the following checks should be made Verify that the electrical supply to the unit is of the correct voltage and rated for sufficient...

Page 11: ...ng the adjust ing screw counter clockwise will raise the opening pressure and raise the condensing pressure being maintained Turning the adjusting screw clockwise will lower the opening point and lowe...

Page 12: ...icient water flow rates excessive water temperatures air flow rates dirty filters and air temperatures TABLE 6 R 22 REFRIGERANT CHARGE UNIT SIZE CAPACITY TONS HORIZONTAL VERTICAL 060 5 0 5 lbs 8 oz 5...

Page 13: ...036 21521 001 A 0103 Unitary Products Group 13 FIGURE 2 TYPICAL SINGLE PHASE WIRING DIAGRAM APPLIES TO ALL 208 230 1 60 SINGLE PHASE MODELS Note Solenoid Valve SV used on Heat Pump version only...

Page 14: ...036 21521 001 A 0103 14 Unitary Products Group FIGURE 3 TYPICAL THREE PHASE WIRING DIAGRAM APPLIES TO MODELS RP030 RP036 RP048 RP060 NOTE Solenoid Valve SV used on Heat Pump version only...

Page 15: ...0 19 00 15 00 32 25 21 50 2 56 15 00 2 00 12 00 5 75 6 81 10 31 3 75 018 40 00 21 00 16 00 37 75 23 50 2 56 18 00 1 00 14 00 6 50 8 25 10 31 3 75 024 45 00 21 00 18 00 42 75 23 50 2 25 25 00 1 00 16 0...

Page 16: ...50 1 25 N A N A 009 22 50 22 50 33 00 6 81 10 31 2 00 7 81 14 88 12 50 1 25 N A N A 012 22 50 22 50 33 00 6 81 10 31 2 00 7 81 14 88 12 50 1 25 11 50 12 00 018 22 50 22 50 35 00 8 25 10 31 2 00 7 13...

Reviews: