SEQUENCE OF OPERATION

The unit is controlled by a conventional four wire heating/
cooling thermostat common to this class of equipment.

HEATING

When the thermostat calls for HEAT, the thermostat terminal 
W is energized, energizing the combustion air blower.

After airflow is established, the air proving switch closes, the 
hot surface ignitor is energized and the pilot valve opens 
igniting the pilot flame.

The flame rod senses a flame and de-energizes the ignitor 
opening the main gas valve and the main burners light.

30 seconds after the main burners light the circulating fan is 
energized at the heating speed.

When the thermostat is satisfied, terminal W  is de-energized, 
which de-energizes the ignition system and closes the gas 
valve.

After a 5 second postpurge timing period, the combustion air 
blower is de-energized and the heat fan off timing begins.

When this field selected heat fan off timing is completed, the 
circulating fan is de-energized.

If the primary, rollout and auxiliary limit switches open, the 
thermostat and ignition system is de-energized and the gas 
valve closes. The combustion blower and the circulating fan, 
at heat speed, are energized.

The combustion blower remains energized for the 5 second 
postpurge timing period if the primary, rollout and auxiliary 
limit switches remake the contact (the rollout and auxiliary 
limit switches must be manually reset). The circulating fan 
remains energized for the selected heat delay off timing.

Normal operation of the system resumes.

COOLING

When the thermostat calls for COOL, the thermostat termi-
nals G and Y are energized, which signals the compressor 
and outdoor fan to run.

After a cool fan on delay timing of 2 seconds, the circulating 
fan is energized at cooling speed.

When the thermostat is satisfied, terminals G and Y are de-
energized, de-energizing the compressor and outdoor fan.

After a cool fan off delay timing of 30 seconds, the circulating 
fan is de-energized.

CIRCULATING FAN 

When the thermostat calls for FAN, the thermostat terminal G 
is energized signaling the circulating fan to run at the heat 
speed 2 seconds after the G terminal is energized.

If a call for HEAT occurs, the circulating fan continues to run 
at the heat speed.

If a call for COOL occurs, the circulating fan switches to cool 
speed after a 4 second delay.

When the thermostat ends the call for FAN, the thermostat 
terminal G is de-energized, de-energizing the circulating fan.

START-UP

PRE-START CHECK LIST

Complete the following checks before starting the unit.

1.

Check the type of gas being supplied. Be sure that it is 
the same as listed on the unit nameplate.

2.

Make sure that the vent outlet air hood has been prop-
erly installed.

OPERATING INSTRUCTIONS

1.

STOP! Read the information on the unit safety label.

2.

Set the thermostat to the OFF position.

3.

Turn off all electrical power to the unit.

4.

DO NOT try to light the burners by hand. This appliance 
is equipped with an ignition device which automatically 
lights the burners. 

5.

Remove the access panel.

6.

Turn the gas valve switch to the OFF position.

7.

Wait five (5) minutes to clear out any gas. If you then 
smell gas, STOP! Follow B in the information on the unit 
safety label. If you don't smell gas, go to the next step.

8.

Turn the gas valve switch to the ON position.

9.

Replace the control access panel.

10. Turn on all electric power to the unit.

11. Set the thermostat to the desired setting.

12. If the unit will not operate, follow the instructions To Turn 

Off Gas To Appliance and call your service technician or 
gas supplier.

Summary of Contents for D YP024 Series

Page 1: ...and WARNING Notes are intended to clarify or make the installation easier Cautions are given to prevent equipment damage Warnings are given to alert installer that personal injury and or equipment dam...

Page 2: ...DIAGRAM 7 5 EXTERNAL SUPPLY CONNECTION EXTERNAL SHUT OFF 9 6 FLUE VENT OUTLET AIR HOOD 10 7 UNIT DIMENSIONS FRONT 12 8 UNIT DIMENSIONS FRONT BOTTOM 13 9 UNIT DIMENSIONS BACK BOTTOM 13 10 GAS VALVE FRO...

Page 3: ...sier CAUTIONS are given to prevent equipment damage WARNINGS are given to alert the installer that personal injury and or equipment damage may result if installation procedure is not handled properly...

Page 4: ...ness and size of the pad or slab used should meet local codes and unit weight Do not tie the slab to the building foundation FIGURE 1 PRODUCT NOMENCLATURE 3 352 8 7 7 25 6LQJOH 3DFNDJH LU RQGLWLRQHU 3...

Page 5: ...for unit weights and to Figure 2 for approxi mate center of gravity DUCT WORK These units are adaptable to downflow use as well as rear supply and return air duct openings To convert to downflow use...

Page 6: ...ESS Access to all serviceable components is provided by the fol lowing removable panels Blower compartment Gas control electrical service access Refer to Figure 7 for location of these access panels a...

Page 7: ...ATOR SHOULD BE SET AT 0 35 AMPS FOR ALL MODELS 24 VOLT TRANSFORMER FIGURE 4 POWER WIRING FIELD DIAGRAM G R O U N D L U G R E F E R T O E L E C T R I C A L D A T A T A B L E S T O S I Z E T H E D I S C...

Page 8: ...own Continuous return air temperature should not be below 55 F TABLE 4 PROPANE1 LP GAS APPLICATION DATA AVAILABLE ON MODELS INPUT CAPACITY MBH 2 OUTPUT CAPACITY MBH GAS RATE 3 FT 3 HR NUMBER OF BURNER...

Page 9: ...l shut off valve may have to be installed outside of the unit 3 Use wrought iron or steel pipe for all gas lines Pipe dope should be applied sparingly to male threads only FIGURE 5 EXTERNAL SUPPLY CON...

Page 10: ...stened to the outside of the side gas control electri cal compartment with the screws provided in the bag attached to the inside of the gas control electrical compart ment see Figure 6 If flexible sta...

Page 11: ...RICAL DATA MODEL DYP POWER SUPPLY VOLTAGE LIMITATIONS1 COMPRESSOR COND FAN MOTOR FLA SUPPLY AIR BLOWER MOTOR FLA MINIMUM CIRCUIT AMPACITY MAX FUSE SIZE AMPS2 MAX HACR BREAKER SIZE AMPS UNIT POWER FACT...

Page 12: ...I N L E T L O U V E R S F R O N T G A S E L E C T R I C C O N T R O L S E R V I C E A C C E S S C O M P A R T M E N T P A N E L O V E R A L L O V E R A L L All dimensions are in inches They are subje...

Page 13: ...8 DIA KNOCKOUT 1 2 NPTI CONNECTION LOW VOLTAGE CONN DIA KNOCKOUT 8 7 FIGURE 9 UNIT DIMENSIONS BACK BOTTOM 1 3 4 1 5 2 9 9 1 6 1 5 3 1 2 1 3 4 1 3 4 1 5 4 1 4 1 2 3 1 2 3 3 8 1 4 1 2 2 8 3 8 1 4 1 2 C...

Page 14: ...un After a cool fan on delay timing of 2 seconds the circulating fan is energized at cooling speed When the thermostat is satisfied terminals G and Y are de energized de energizing the compressor and...

Page 15: ...tor adjusting screw on the automatic gas valve Refer to Figure 10 Adjust as follows 1 Remove the cap from the valve body See Figure 11 for location 2 To decrease the gas pressure turn the adjusting sc...

Page 16: ...s of both the return air and the heated air in the ducts about six feet from the furnace where they will not be affected by radiant heat The temperature rise or temperature difference between the retu...

Page 17: ...12 150 300 14 129 257 16 113 225 18 100 200 20 90 180 22 82 164 24 75 150 26 69 138 28 64 129 30 60 120 32 56 113 34 53 106 36 50 100 38 47 95 40 45 90 42 43 86 44 41 82 46 39 78 48 37 75 50 36 72 52...

Page 18: ...HECKOUT procedures Troubleshooting of components necessitates opening the electrical control box with the power connected to the unit Use extreme care when working with the live circuits Check the uni...

Page 19: ...176230 BIM A 0206 Unitary Products Group 19 FIGURE 14 TYPICAL WIRING DIAGRAM DAYP 024 208 230 1 60 POWER SUPPLY...

Page 20: ...ROL BOX T1 CONTROL BOARD 1 2 S DI LEADS MOTOR UNUSED 4 3 2 1 C X XFMR CN1 6 5 4 3 2 1 OFF DELAY TB1 Y C R W Y G C SEC C 230 LUG GND LUG GND NOTES 4 SEE UNIT NAMEPLATE FOR MAXIMUM FUSE SIZE AND MINIMUM...

Page 21: ...176230 BIM A 0206 Unitary Products Group 21 FIGURE 16 TYPICAL WIRING DIAGRAM DAYP 060 208 230 1 60 POWER SUPPLY...

Page 22: ...RD CB 1 2 S DI LEADS MOTOR UNUSED 4 3 2 1 C X XFMR CN1 6 5 4 3 2 1 OFF DELAY TB1 Y C R W Y G C SEC C 230 RC2 LUG GND T3 T2 T1 L3 L2 L1 B A M1 LUG GND NOTES 4 SEE UNIT NAMEPLATE FOR MAXIMUM FUSE SIZE A...

Page 23: ...176230 BIM A 0206 Unitary Products Group 23 FIGURE 18 TYPICAL WIRING DIAGRAM DAYP 060 208 230 3 60 POWER SUPPLY...

Page 24: ...176230 BIM A 0206 24 Unitary Products Group FIGURE 19 TYPICAL WIRING DIAGRAM DAYP 030 036 042 048 460 3 60 POWER SUPPLY...

Page 25: ...176230 BIM A 0206 Unitary Products Group 25 FIGURE 20 TYPICAL WIRING DIAGRAM DAYP 060 460 3 60 POWER SUPPLY...

Page 26: ...l all wires prior to disconnection when servic ing controls Wiring errors can cause improper and dangerous operation if any of the wire as sup plied with this unit must be removed it must be replaced...

Page 27: ...176230 BIM A 0206 Unitary Products Group 27...

Page 28: ...t to change without notice Printed in U S A 176230 BIM A 0206 Copyright by Unitary Products Group 2006 All rights reserved Supersedes 166051 BIM A 0905 Unitary 5005 Norman Products York OK Group Drive...

Reviews: