Maintenance
Sageon III Power System
PM990-8800-00, Rev. 9
6-4
IMPORTANT:
Each rectifier position address must be unique; do not use an address number more than once. Addresses must be
in numerical order with the uppermost (in the System) Rectifier having address 1. The address number increases by 1 with each
Rectifier installed.
2.
To install the Rectifiers, go to Section 2.14 Installing and Removing Rectifiers.
TABLE 6-3 RECTIFIER POSITION ADDRESSES 1 THROUGH 24
Table Notes: ADR = Rectifier position address
ADR↓
SW1 Switch Positions
1
2
3
4
5
6
7
8
TOP SHELF
1
Off
Off
Off
Off
Off
Off
Off
On
2
Off
Off
Off
Off
Off
Off
On
Off
3
Off
Off
Off
Off
Off
Off
On
On
4
Off
Off
Off
Off
Off
On
Off
Off
5
Off
Off
Off
Off
Off
On
Off
On
6
Off
Off
Off
Off
Off
On
On
Off
7
Off
Off
Off
Off
Off
On
On
On
8
Off
Off
Off
Off
On
Off
Off
Off
9
Off
Off
Off
Off
On
Off
Off
On
10
Off
Off
Off
Off
On
Off
On
Off
11
Off
Off
Off
Off
On
Off
On
On
12
Off
Off
Off
Off
On
On
Off
Off
BOTTOM
SHELF
13
Off
Off
Off
Off
On
On
Off
On
14
Off
Off
Off
Off
On
On
On
Off
15
Off
Off
Off
Off
On
On
On
On
16
Off
Off
Off
On
Off
Off
Off
Off
17
Off
Off
Off
On
Off
Off
Off
On
18
Off
Off
Off
On
Off
Off
On
Off
19
Off
Off
Off
On
Off
Off
On
On
20
Off
Off
Off
On
Off
On
Off
Off
21
Off
Off
Off
On
Off
On
Off
On
22
Off
Off
Off
On
Off
On
On
Off
23
Off
Off
Off
On
Off
On
On
On
24
Off
Off
Off
On
On
Off
Off
Off
Non-Shaded
addresses 1 through 12 are used for 50-600A systems
Shaded
addresses 13 through 24 are used for 650-1200A systems
SW1
ON ADDRESS SWITCH DETAIL
ADDRESS 1 SHOWN
1
8