Installation
Sageon III Power System
PM990-8800-00, Rev. 9
2-14
Load Supply Cables, GJ1 Type Breaker Distribution
When ordered, GJ1 type distribution assemblies are always the upper-most distribution assemblies in a plant since no more
distribution can be installed above a GJ1 type assembly. Cable routing and connection are shown in Figure 2-12. Connect the top
breaker terminals to user loads. The bottom breaker terminals are bolted to the battery discharge bus at the factory.
Bus Bars
Tier 1
Group A
Tier 1
Group B
Tier 2
Group A
Tier 2
Group B
Distribution
Assemblies
Fuse Alarm
(FA) Wire
L
ef
t
Re
ar
C
or
ne
r
of
Rac
k
Le
ft
F
ro
nt
C
or
ne
r
of
R
ac
k
Distribution Assemblies
Tier 3, Grp A
Tier 3, Grp B
Fuse Alarm
(FA) Wire
FIGURE 2-11 GJ1 TYPE BREAKER DISTRIBUTION ASSEMBLIES, TYPICAL
1.
Select a starting point, the lowest Group letter, Position 1 is recommended.
2.
For the load supply cable end, use a single-hole lug for a 3/8" bolt. See Figure 2-12.
3.
Bolt the supply cable end to the breaker terminal using 3/8" hardware per figure 2-12.
4.
Repeat the above steps for each GJ1 type breaker in the Group
5.
Repeat the above steps for each GJ1 type breaker group.
Load Supply Cable with 3/8 Lug
and Output Terminal Hardware
Bus Bar, L-Shaped
Mounting Bracket, U-Shaped
Bracket Mounting Screw
12-24 x 3/4, 2 Places
Breaker Mounting Bar, 2 Places
Breaker Input Terminal Hardware
Bevel Washer
Flat Washer
3/8 x 1 Hex Bolt
3/8 Nut and Flat Washer
GJ1 Circuit Breaker, 4 Places
FIGURE 2-12 GJ1 TYPE BREAKER DISTRIBUTION WIRING