Sageon III Power System
Circuit Breaker and Fuse Kit Installation
PM990-8800-00, Rev. 9
8-3
3.
From the existing GJ1 Distribution Option: carefully remove the insulated sleeving from the orange fuse alarm wire and the
red alarm wire for the breaker position you are installing.
4.
Remove a GJ1 type breaker kit from its packaging. The package label will identify the kit by part number.
5.
Connect the red alarm wire of the GJ1 Distribution Option to the Common (C) pole and the orange fuse alarm wire of the
GJ1 Distribution Option to the Normally Closed (NO) pole on the rear of the GJ1 type breaker.
Note: For GJ1 type breakers 200A and over, the breaker kit contains an alarm wire adapter that must be connected between
the breaker and the red alarm & orange FA alarm wires of the GJ1 Distribution Option.
6.
Carefully place the GJ1 type breaker from the kit over one of the vertical tabs of the L-shaped bus bar of the GJ1
Distribution Option (see Figure 8-3).
7.
Collect from the GJ1 type breaker Kit, one each of the following: 3/8-16 x 1 1/4" hex head bolt, 3/8 bevel washer and 3/8
flat washer. Insert through tab of the GJ1 type breaker and thread into the insert of the vertical tab of the L-shaped bus bar
of the GJ1 Distribution Option (see Figure 8-4) and tighten. See Table 2-2 for torque specifications.
8.
Replace the two painted breaker mounting bars of the GJ1 Distribution Option using the 10-32 x 1/2" screws removed in
step 2.
9.
Collect the two 10-32 x 1/2" from the GJ1 type breaker Kit and secure the new GJ1 type breaker to the two painted breaker
mounting bars of the GJ1 Distribution Option replaced in step 8.
10.
Use the remaining 3/8” hardware from the GJ1 type breaker Kit to secure load cabling to the GJ1 type breaker (see Figure
8-4).
Load Supply Cable with 3/8 Lug
and Output Terminal Hardware
Bus Bar, L-Shaped
Mounting Bracket, U-Shaped
Bracket Mounting Screw
12-24 x 3/4, 2 Places
Breaker Mounting Bar, 2 Places
Breaker Input Terminal Hardware
Bevel Washer
Flat Washer
3/8 x 1 Hex Bolt
3/8 Nut and Flat Washer
GJ1 Circuit Breaker, 4 Places
FIGURE 8-3 GJ1 TYPE BREAKER KIT COMPONENTS