P O W E R I N G T E C H N O L O G Y
Document Number: MS0031-MAN rev. 7
guardian_access_ms31-man-rev7-0521.indd
CAUTION
Care must be taken when installing this system. The units can be damaged
and can cause damage if not handled with care. Pay particular attention to the order in
which units are installed.
4.4 Cable Size
Please use the recommended cable size given below for the system installation.
Port
Current
Max.
Cable Size
Min.(mm²)
Cable Size
Min.(AWG)
Temperature
Rating
AC Input -L1
32A
10mm²
7 AWG
105°C
AC Input -L2
32A
10mm²
7 AWG
105°C
AC Input -L3
16A
10mm²
7 AWG
105°C
AC Input -N
32A
10mm²
7 AWG
105°C
AC Input -PE
-
10mm²
7 AWG
105°C
Battery MCB
80A
20mm²
4 AWG
105°C
Battery MCB
100A
25mm²
3 AWG
105°C
Battery MCB
125A
35mm²
2 AWG
105°C
DC Load -MCB
63A
16mm²
5 AWG
105°C
DC Load -MCB
50A
14mm²
6 AWG
105°C
DC Load -MCB
40A
10mm²
7AWG
105°C
DC Load -MCB
32A
8mm²
8 AWG
105°C
DC Load -MCB
25A
8mm²
8 AWG
105°C
DC Load -MCB
20A
6mm²
9 AWG
105°C
DC Load -MCB
16A
4mm²
10 AWG
105°C
DC Load -MCB
10A
2.5mm²
14 AWG
105°C
DC Load -MCB
6A
2.5mm²
14 AWG
105°C
DC Load -MCB
4A
1.5mm²
15 AWG
105°C
Table 4-1 Recommended Electrical Cable Sizes