DPBF1U & DPGF1U SERIES

OPERATING MANUAL

P O W E R I N G   T E C H N O L O G Y

Document Number: DPBF-DPGF-MAN Rev. 5

dpbf_dpgf-man-Rev5-0719.indd

7.0   SPECIFICATIONS

The following specifications are typical at 25°C unless otherwise noted.

INPUT / OUTPUT

Panel Capacity ...........................................

See Panel Configuration Table

Configuration

     DPBF1U

          Single Bus ................................................................ 1 to 8 Breakers 

          Dual Bus .......................................................... 1 to 4 Breakers Each

     DPGF1U

         Single Bus ...........................................................1 to 12 GMT Fuses

         Dual Bus .......................................................1 to 6 GMT Fuses Each

Breaker/Fuse Capacity

 1

 ............................................................. ½A to 30A

Voltage

 2

     24/48V Nominal .....................................................................21-60VDC

     12V Nominal .......................................................................10.5-15VDC

Polarity................................................................................ Polarity Neutral

ALARMS

Alarm Indicator .....................................................Dual-Color LED Per Bus

LED Status Indication ........................................................Green = Normal

                                                          Red = Breaker/Fuse Trip/Open Alarm

                                                                                             

Off = No Power

Alarm Connections .............................One Form C Relay Contact Per Bus

   

SAFETY STANDARDS

 ................................................UL60950-1 2nd Ed.

                                        CAS22.2 No.950-1 2nd Ed., EN60950-1 2nd Ed.

ENVIRONMENTAL 

Operating Temp. Range ..................................................... -10°C to +70°C

Storage Temp. Range ........................................................ -40°C to + 85°C

Humidity........................................................ 0% to 95%, Non-Condensing

PHYSICAL SPECIFICATIONS

Case Material ......................................................................................Steel

Finish ............................................................................ Powder Coat Black

Dimensions, Inches (mm) ..................................1.75 H x 19.00 W x 9.00 D

                                                                                         (44.5 x 483 x 229)

Weight .........................................................................

10.30 lbs. (4.67 kg.)

Rack Mounting Width .........................................................19 or 23 Inches

CONNECTIONS

Input Connections.......................................Crimp Type Lug or ¼ - 20 Stud

Output Connections ................................. Barrier Terminal Strips, No. 6-32

Chassis Ground Connection..................................................No. 8-32 Stud

Alarm Relay Connections ...................Spring Clamp Terminals,16-26AWG

NOTES: 

1.  See tables for available breaker & fuse sizes.

 

2.  See Ordering Guide to specify voltage.

Summary of Contents for DPBF1U Series

Page 1: ...U DPGF1U SERIES Document Number DPBF DPGF MAN Rev 5 UNIPOWER LLC 65 Industrial Park Rd Dunlap TN 37327 Phone 1 954 346 2442 Toll Free 1 800 440 3504 Web site www unipowerco com 2019 UNIPOWER LLC All Rights Reserved P O W E R I N G T E C H N O L O G Y ...

Page 2: ...1 0 INTRODUCTION 4 2 0 FEATURES OPTIONS 5 3 0 PRODUCT LINE 5 4 0 SAFETY INDUSTRY STANDARDS 6 5 0 WARRANTY summary 6 6 0 DESCRIPTION OF OPERATION 7 7 0 SPECIFICATIONS 8 8 0 CONFIGURATION 9 9 0 FRONT PANEL DESCRIPTION 11 10 0 UNPACKING AND INSPECTION 14 11 0 INSTALLATION 14 12 0 SETUP AND TESTING 15 REV DESCRIPTION CHK d APPR d DATE 5 PCO 45395 MM 07 31 19 ...

Page 3: ...iagram 7 Figure 3 DPBF1U Front Panel View 11 Figure 4 DPGF1U Front Panel View 11 Figure 5 Input Bus Bar Detail 11 Figure 6 Output Barrier Strip Detail 12 Figure 7 Alarm Contact Ground Detail 13 Figure 8 Series Connection of Multiple Panels 14 TABLES Table 1 Basic Configurations 5 Table 2 LED State Definitions 7 Table 3 GMT Fuse Values 9 Table 4 Input Cable Lug Sizes Types 12 Table 5 Alarm Relay Co...

Page 4: ...h existing rackmounted equipment Figure 1 shows the two series of panels The first is the DPGF1U Series which has 4 or 6 GMT fused circuits on both A and B sides The second is the DPBF1U Series with up to 4 circuit breaker circuits on both A and B sides NO C NC NO C NC B A T R T N 1 2 3 4 5 6 FA 1 5 6 B A T R T N 1 2 3 4 5 6 FA 1 5 6 DPGF1U GMT Fuse Distribution Panel NO C NC NO C NC ON I O OFF BA...

Page 5: ...three standard options available Option C Clear plastic rear cover to protect connectors and wiring from damage This option will be supplied automatically unless it is specificially requested to be deleted Option S This option internally links the A bus to the B bus so that a fully configured unit can be supplied DC from a single feed TheAand B sides have the same voltage and polarity 3 0 PRODUCT ...

Page 6: ... operating this Distribution Panels the chassis ground terminal must be connected to the system frame ground or other proper safety ground for the protection of personnel 4 5 All connections to the Distribution Panels should be carefully checked for errors before applying power to them 4 6 The internal voltages may be at hazardous potentials The top cover should not be removed There are no user se...

Page 7: ...BATT BATT INPUT RET INPUT RET HI CURRENT BUS BAR HI CURRENT BUS BAR HI CURRENT BUS BAR HI CURRENT BUS BAR LOADS LOADS 1 2 3 N N 3 2 1 A SIDE ALARM CIRCUITS b SIDE ALARM CIRCUITS A SIDE B SIDE S OPTION S OPTION Figure 2 Block Diagram 6 2 Alarm Circuits The alarm circuits detect a tripped circuit breaker or blown and in this event turn on the red part of the LEDs The alarm circuits also each drive F...

Page 8: ...ED Status Indication Green Normal Red Breaker Fuse Trip Open Alarm Off No Power Alarm Connections One Form C Relay Contact Per Bus SAFETY STANDARDS UL60950 1 2nd Ed CAS22 2 No 950 1 2nd Ed EN60950 1 2nd Ed ENVIRONMENTAL Operating Temp Range 10 C to 70 C Storage Temp Range 40 C to 85 C Humidity 0 to 95 Non Condensing PHYSICAL SPECIFICATIONS Case Material Steel Finish Powder Coat Black Dimensions In...

Page 9: ...X 20A max 6 4 x 15A max 2 x 20A max Model DPGF1U A B NOTES 1 If section B is not used a blank panel is installed at the factory 2 The sum of all fuse currents on either side must not exceed the total rating GMT FUSES AMPS PART NUMBER COLOR 401 1500 0010 Red Order fuses separately UNIPOWER recommends Bussman fuses for this panel They may be ordered from UNIPOWER using the part numbers shown 401 150...

Page 10: ...section B is not used a blank panel is installed at the factory The sum of all breaker currents on either side must not exceed the total rating When the S option is specified each side of the panel is limited to 75A total 150A Model No DPBF1U A B CODE AMPS F 1 G 2 5 H 5 I 10 J 15 K 20 L 25 M 30 STANDARD BREAKERS CODE OPTION C Front Cover Clear Plastic CODE VOLTAGE POLARITY 1 24 48V polarity neutra...

Page 11: ... OFF ON I O OFF A SIDE B SIDE Alarm LED A A Side Breakers B Side Breakers Alarm LED B 1 2 3 4 1 2 3 4 Alarm Contacts A Input 20 Studs Ground 8 32 Stud B Outputs 6 32 Terminal Strip A Outputs 6 32 Terminal Strip B Input 20 Studs Figure 3 DPBF1U Front Panel View NO C NC NO C NC B A T R T N 1 2 3 4 5 6 FA 1 5 6 B A T R T N 1 2 3 4 5 6 FA 1 5 6 A SIDE B SIDE Alarm LED A A Side Fuses B Side Fuses Alarm...

Page 12: ...0150 Table 4 Input Cable Lug Sizes Types 9 4 Output Connections Output connections for A and B loads are shown in Figure 6 There are 10 sets of barrier terminal strip connections for each side A and B The connections are numbered to correspond with the numbers of the front panel breakers The upper strip connections are from the battery through the breakers the lower strip connections are the retur...

Page 13: ...act of side B and ALM A is for the Form C relay contact of side A The terminals viewed from left to right are the normally open NO common C and normally closed NC contacts respectively See table 5 below PIN FUNCTION CONTACT SCHEMATIC NC N C normally closed RELAY CONTACTS OUTPUTS N C C N O C C common NO N O normally open Table 5 Alarm Relay Contacts Normally Closed and Normally Open are defined wit...

Page 14: ...in either 19 or 23 inch racks by using the supplied reversible brackets Mount it from the front of the rack using the correct offsets to align with existing rack mounted equipment The bracket offsets are every quarter inch from front to back 11 2 Connections Input connections should be made with one or two terminal crimp type lugs using copper wire size from no 1 to 8 AWG depending on current and ...

Page 15: ...sary to have loads connected to the panel for this testing 12 2 With the input power source off connect the input wires to the A side of the distribution panel Connect ground to the chassis ground terminal Insert all fuses into fuse holders or set all circuit breakers to on 12 3 Turn on the input power source The A side LED should be green If it is red one of the fuses is blown or a circuit breake...

Page 16: ...ct support can be obtained using the following addresses and telephone numbers Corporate office UNIPOWER LLC 210 N University Dr Coral Springs FL 33071 United States Manufacturing facility UNIPOWER LLC 65 Industrial Park Rd Dunlap TN 37327 United States Manufacturing facility UNIPOWER Slovakia SRO ZLATOVSKA 1279 Business Center 22 91105 Trencin Slovakia Phone 1 954 346 2442 Toll Free 1 800 440 350...

Reviews: