This operating manual should be read through carefully before installing and
operating this AC power distribution panel.
This distribution panel provides protected AC power distribution to telecom-
munication equipment. It provides up to four circuit breakers on both the A
and B sides of the panel. See Figure 1. The A and B loads can be in common
(standard version) or isolated from each other (optional version). Total capac-
ity for each A or B side is 50 amperes.
The DPAC1U distribution panel is only 1.75 inches (1 rack space) high to
minimize rack space and can be mounted in either a 19- or 23-inch relay rack
with corresponding brackets. It can be mounted from the front of the rack
with offsets every ¼-inch from front to back to align with existing rack-
mounted equipment.
The distribution panel can be configured differently for the A and B sides.
The A and B sides can have different numbers of breakers and different
breaker capacities. Each breaker on Option T can be from 5 to 30 amperes
capacity; each breaker on Option C can be from 5 to 15 amperes capacity.
The maximum capacity for each A or B side is 50 amperes. The distribution
panel must be configured at the factory.
The rear panel connections have two options: Positronics connector input with
NEMA 5-15R AC output receptacles (C Option) or barrier terminal strip
connectors for both input and output connections (T Option).